4-11
T-294-01
Table 4-2. Electrical Control Positions -- ABOVE --10
_
_
_
_
C (+14
_
_
_
_
F), or --5
_
_
_
_
C (+23
_
_
_
_
F) optionally
CONTROL CIRCUIT
COOLING
Holding Zone
* Dehumidifica-
tion
HEATING
DEFROST
Compressor Contactor
(CH)
Energized
De-energized
**
**
De-energized
1
Condenser Fan
Contactor (CF)
Energized
De-energized
Energized
De-energized
De-energized
High Speed Evaporator
Contactor (EF)
Energized
Energized
Refer to section
3.1.7.a.2
Refer to section
3.1.7.a.2
De-energized
2
Low Speed Evaporator
Contactor (ES)
De-energized
De-energized
Refer to section
3.1.7.a.2
Refer to section
3.1.7.a.2
De-energized
Heater Contactor (HR)
De-energized
De-energized
Energized
Energized
Energized
INDICATING LIGHTS
Cool
ON
OFF
ON
OFF
OFF
Defrost
OFF
OFF
OFF
OFF
ON
In-Range
On -- If In-Range (Refer to paragraph 3.1.4, Code 30)
Heat
OFF
OFF
ON
ON
ON
POWER CIRCUIT
Compressor
Energized
De-energized
Energized
De-energized
De-energized
Condenser Fan Motor
Energized
De-energized
Energized
De-energized
De-energized
Heaters
De-energized
De-energized
Energized
Energized
Energized
Evaporator Fan Motors
Energized
Energized
Energized
Energized
De-energized
*
Unit with optional Humidity sensor
** Dehumidification and heating modes do not operate at set points below --10
_
C (14
_
F), or --5
_
C (23
_
F) optionally
1
-- May be energized in defrost if snap freeze portion of defrost is run.
2
-- May be energized in defrost if probe check portion of defrost is run.