3-6
T-292
3.3.10 Temperature Control -- Frozen Mode
With configuration variable CnF26 (Heat Lockout
Temperature) set to --10
_
C the frozen mode of operation
is active with set points
at or below --10
_
C (+14
_
F). With
the variable set to --5
_
C, the frozen mode is active at or
below --5
_
C (+23
_
F).
When in the frozen mode the controller maintains the
return air temperature at set point, the RETURN
indicator light will be illuminated on the display module
and the default reading on the display window will be the
return air probe reading.
When the return air temperature enters the in-range
temperature tolerance as selected at function code
Cd30, the in-range light will energize.
3.3.11 Frozen Mode -- Conventional
Frozen range cargos are not sensitive to minor
temperature changes. The method of temperature
control employed in this range takes advantage of this to
greatly improve the energy efficiency of the unit.
Temperature control in the frozen range is
accomplished by cycling the compressor on and off as
the load demand requires.
When cooling from a temperature that is more than
2.5
_
C (4.5
_
F) above set point, the system will be in the
frozen pull down mode. It will transition to economized
operation with a target SMV position of 100% open.
However, pressure and current limit functions may
restrict the valve, if either exceeds the preset value.
Once set point is reached, the unit will transition to the
frozen steady state mode. (Economized operation with
maximum allowed suction modulating valve opening.)
When temperature drops to set point minus 0.2
_
C and
the compressor has run for at least five minutes, the unit
will transition to the frozen idle mode. The compressor is
turned off and the evaporator fans continue to run to
circulate air throughout the container. If temperature
rises above set point +0.2
_
C, the unit will transition back
to the frozen steady state mode.
If the temperature drops 10
_
C below set point, the unit
will transition to the frozen “heating” mode. In the frozen
heating mode the evaporator fans are brought to high
speed. The unit will transition back to the frozen steady
state mode when the temperature rises back to the
transition point.
3.3.12 Frozen Mode -- Economy
In order to activate economy frozen mode operation, a
frozen set point temperature must be selected. The
economy mode is active when function code Cd34 is set
to “ON”. When economy mode frozen is active, the
system will perform normal frozen mode operations
except that the entire refrigeration system, excluding
the controller, will be turned off when the control
temperature is less than or equal to the set point -- 2
_
C.
After an off-cycle period of 60 minutes, the unit will turn
on high speed evaporator fans for three minutes, and
then check the control temperature. If the control
temperature is greater than or equal to the set point +
0.2
_
C., the unit will restart the refrigeration system and
continue to cool until the previously mentioned off-cycle
temperature criteria are met. If the control temperature
is less than the set point + 0.2
_
C, the unit will turn off the
evaporator fans and restart another 60 minute off-cycle.
3.4 CONTROLLER ALARMS
Alarm display is an independent controller software
function. If an operating parameter is outside of
expected range or a component does not return the
correct signals back to the controller an alarm is
generated. A listing of the alarms is provided in
Table 3-6, page 3-16.
The alarm philosophy balances the protection of the
refrigeration unit and that of the refrigerated cargo. The
action taken when an error is detected always considers
the survival of the cargo. Rechecks are made to confirm
that an error actually exists.
Some alarms requiring compressor shutdown have
time delays before and after to try to keep the
compressor on line. An example is alarm code “LO”,
(low main voltage), when a voltage drop of over 25%
occurs, an indication is given on the display, but the unit
will continue to run.
When an Alarm Occurs:
a. The red alarm light will illuminate for alarm code num-
bers 13, 17, 20, 21, 22, 23, 24, 25, 26, and 27.
b. If a detectable problem is found to exist, its alarm
code will be alternately displayed with the set point on
the left display.
c. The user should scroll through the alarm list to deter-
mine what alarms exist or have existed. Alarms must
be diagnosed and corrected before the Alarm List can
be cleared.
To Display Alarm Codes :
a. While in the Default Display mode, press the ALARM
LIST key. This accesses the Alarm List Display Mode,
which displays any alarms archived in the Alarm
Queue.
b. The alarm queue stores up to 16 alarms in the se-
quence in which they occurred. The user may scroll
through the list by depressing an ARROW key.
c. The left display will show “AL##,” where ## is the
alarm number sequentially in the queue.
d. The right display will show the actual alarm code.
“AA##” will display for an active alarm, where “##” is
the alarm code. Or “IA##” will display for an inactive
alarm, See Table 3-6, page 3-16,
e. “END” is displayed to indicate the end of the alarm list
if any alarms are active.
f. “CLEAr” is displayed if all alarms are inactive. The
alarm queue may than be cleared by pressing the EN-
TER key. The alarm list will clear and “
-- -- -- -- --
” will
be displayed.
Downloaded from
Summary of Contents for 69NT40-531 Series
Page 2: ...Downloaded from ManualsNet com search engine ...
Page 4: ...Downloaded from ManualsNet com search engine ...
Page 8: ...Downloaded from ManualsNet com search engine ...
Page 16: ...Downloaded from ManualsNet com search engine ...
Page 57: ...Downloaded from ManualsNet com search engine ...
Page 104: ...Downloaded from ManualsNet com search engine ...
Page 106: ...7 2 T 292 Figure 7 2 SCHEMATIC DIAGRAM Downloaded from ManualsNet com search engine ...