5-5
T-292
CONDITION
POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
5.14 COMPRESSOR OPERATING IN REVERSE
CAUTION
Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal
compressor damage. Turn the start--stop switch OFF immediately.
Incorrect wiring of compressor
Electrical
Incorrect wiring of compressor contactor(s)
Check
Electrical
Incorrect wiring of current sensor
Check
5.15 ABNORMAL TEMPERATURES
Discharge temperature sensor drifting high
Replace
High discharge temperature
Failed economizer, TXV or solenoid valve
Replace
High discharge temperature
Plugged economizer, TXV or solenoid valve
Replace
Loose or insufficiently clamped sensor
Replace
Low suction temperature
Discharge temperature sensor drifting low
Replace
Low suction temperature
Loose or insufficiently clamped sensor
Replace
5.16 ABNORMAL CURRENTS
Unit reads abnormal currents
Current sensor wiring
Check