62-10848
6-2
A06
Condenser Fan Motor (CFM)
high amp draw
Verify motor rotates freely
--
Verify condition of brushes
Replace motor
--
A07
Evaporator Fan Motor (EFM) high
amp draw
Verify motor rotates freely.
--
Replace motor
--
A08
Standby
Units Only
Heating option control - Either the
hot water control relay or the
electric heat contactor coil amp
draw is high
Verify coil resistance
--
Check wiring to controls
--
A09
Hot Gas Solenoid Valve (HGS1)
high amp draw
Current draw of coil high or low (approx 1.6 amp)
--
Replace coil
A10
Quench Valve (BPV) high amp
draw
Current draw of coil high or low (approx 1.2 amp)
--
Replace coil
A11
Condenser Pressure Control
Valve (HGS2) high amp draw
Current draw of coil high or low (approx 1.6 amp)
--
Replace coil
A12
Standby
Units Only
Out of Range - High Temperature
Unit out of range for 15 minutes
--
Verify cooling operation of unit
Hot gas solenoid open
Verify setting
A13
Standby
Units Only
Out of Range - Low Temperature
Unit out of range for more than 15 minutes
--
Verify heating operation of unit
Heating option not active (Set configuration)
--
A14
Standby
Units Only
Defrost Cycle > 45 minutes
Unit terminated defrost after 45 minutes
--
Verify HGS1/HGS2 valve operation
A15
Set point adjusted out of the
range -20.2 to 86°F (-29°C/
+30°C) or below the programmed
low threshold
Check set point
EE
Return Air Sensor
Return air sensor defective
Replace
bAt
Low Battery Voltage
Vehicle battery voltage low
Correct
Check alternator system
--
---
Using Road and Standby
operation at the same time
If operating on road, disconnect standby power
supply
--
If operating on standby, shut down vehicle
engine.
--
Err
Set point error
Programming error. Reset.
Table 6–1 Alarm Indications (Continued)