62-12023
3-14
NOTE
If no key is activated after validating a configuration, the system reverts to box temperature display
and the configuration procedure is aborted. Only validated changes are recorded.
3.9
Stopping the Unit
Press the OFF key or turn the ignition key to the off position.
Hybrid Unit (option)
EUOF: Adjusting Standby set-point identical to road set-point
EUOn: Set-point locked at -31°F (-35°C) in standby mode
1. Press the + or - keys to change EUOFF or EUOn.
2. Press the SET key to validate and go to the next configuration.
Setpoint Lock (option)
SPOF: setpoint lock option is not active
SPON: setpoint lock option is active
1. Press the + or - keys to change the setting to desired selection.
2. Press the SET key to validate and go to the next configuration.
Pump Down (option)
PdOF: Pump down option disactivated
PdON: Pump down option activated
1. Press the + or - keys to change the setting to desired selection.
2. Press the SET key to validate and go to the next configuration.
If Pump Down option is activated, the following 2 configurations
are then available:
Compressor shutdown delay
(Negative box temperature)
t-.40 up to t-.10: Adjustable on a 30secs range
1. Press the + or - keys to change the setting to desired selection.
2. Press the SET key to validate and go to the next configuration.
Compressor shutdown delay
(Positive box temperature)
:
t.120 down to t.10: Adjustable on a 110secs range
1. Press the + or - keys to change the setting to desired selection.
2. Press the SET key to validate and go to the next configuration.
Summary of Contents for Integra 35X
Page 2: ......
Page 8: ......
Page 12: ......
Page 68: ......
Page 69: ...wiring schematics ...
Page 70: ......
Page 71: ...wiring schematics ...
Page 72: ......
Page 73: ...wiring schematics ...
Page 74: ......
Page 75: ...wiring schematics ...
Page 76: ......
Page 79: ......