62-12023
4-2
4.1.3
Frozen Mode
The unit operates in the frozen mode with setpoints at or below 10°F (-12°C).Operation in the frozen mode is the
same as in the perishable mode except no heating takes place.
Figure 4.2 Operating Sequence - Frozen Mode
4.2
Defrost Cycle
Defrost is an independent cycle overriding cooling and heating functions to melt frost and ice from the evaporator
when necessary. Defrost may be initiated by the microprocessor or manually by the operator once the defrost ter-
mination thermostat has closed at approximately 38°F (3.3°C). In defrost mode, the microprocessor displays “dF”
on the cab command and set-point is no longer displayed.
During defrost, the evaporator fans shut down and operation of the condenser fan is controlled by the microproces-
sor. For road only units, the end of the defrost cycle is time based only. For standby units, the end of the cycle is
controlled by the opening of the defrost termination thermostat (See
for DTT settings. The same
logic for component control that applies to heating also applies to defrost. (See
for a description of
the refrigeration circuit during heat and defrost.)
4.3
Minimum Off Time
Once the unit has cycled off, it will remain off for the minimum off time of five minutes. This prevents rapid cycling
due to changes in air temperature. Air temperature in the box changes rapidly but it takes time for the product tem-
perature to change.
SETPOINT
COOL
UNIT STOPPED
+5.4°F (+3°C)
or +3.6°F (+2°C)
or +1.8°F (+1°C)
-1.8°F (-1°C)
or -3.6°F (-2°C)
or -5.4°F (-3°C)
(setting)
Summary of Contents for Integra 35X
Page 2: ......
Page 8: ......
Page 12: ......
Page 68: ......
Page 69: ...wiring schematics ...
Page 70: ......
Page 71: ...wiring schematics ...
Page 72: ......
Page 73: ...wiring schematics ...
Page 74: ......
Page 75: ...wiring schematics ...
Page 76: ......
Page 79: ......