background image

4–11

T-372

When the defrost mode is in the active state, defrost can be initiated when any one of the following additional con

-

ditions become true:

1.

Manually: 

While in the Defrost screen, when the Manual Defrost soft key is selected, if conditions will allow

for a defrost, a manual defrost is initiated. The Defrost Indicator light is lit, and the user is brought back to

the Main / Default screen. If conditions are NOT allowing for a defrost, a pop up message screen appears.

2.

Timer: 

The Defrost Interval Timer reaches the user selectable Interval. The user-selected intervals are 3, 6,

9, 12, 24 Hours, Off, AUTO, or AUTO2; factory default is AUTO. Refer to Defrost Interval setting on the Trip

Settings screen.
a. Automatic defrost starts with an initial defrost at three hours and then adjusts the interval to the next

defrost based on the accumulation of ice on the evaporator coil. Following a start-up or after termination

of defrost, the time will not begin counting down until the DTS reading falls below 10°C (50°F). If the

reading of DTS rises above termination setting any time during the timer count down, the interval is reset

and the countdown starts over. The Auto defrost time is reset to three hours start time after every PTI ini

-

tiation or trip start interval.

b. After a new Defrost Interval is selected, the previously selected Interval is used until the next defrost ter

-

mination, the next time the DTS contacts are OPEN, or the next time power to the control is interrupted.

If the previous value or the new value is “OFF”, the newly selected value will be used immediately.

3.

Probe Check:

 If defrost is initiated due to Probe Check immediately following the defrost cycle the evapora

-

tion fans are started and run for eight minutes to stabilize the temperature throughout the container. A probe

check comparison is carried out at the end of the eight minute period if any sensor is found out of calibration.

At this time its alarm set is no longer used for control/reorder purposes.

4.

Probe Check Logic:

 The logic determines that a Probe Check is necessary based on temperature values

currently reported by the supply and return probes

5.

Delta T Logic:

 If the difference between return and supply air temperature (Delta T) becomes too great indi

-

cating possible reduced airflow over the evaporator coil caused by ice buildup requiring a defrost.
a. In Perishable Pull Down - Delta T increases to greater than 12°C, and 90 minutes of compressor run

time have been recorded.

b. In Perishable Steady State - A baseline Delta T is recorded following the first defrost cycle after steady

state conditions are reached, (the unit is cooling, and the evaporator fans and heaters must remain in a

stable state for a period of five minutes). Defrost will be initiated if Delta T increases to greater than 4°C

above the baseline, and 90 minutes of compressor run time have been recorded.

c. In Frozen Mode - Defrost will be initiated if Delta T increases to greater than 16°C and 90 minutes of

compressor run time have been recorded.

When defrost is initiated, the controller closes the EEV, opens contacts TC, TN and TE (or TV) to de-energize the

compressor, condenser fan and evaporator fans. The controller then closes contacts TH to supply power to the

heaters. The orange DEFROST light and HEAT light are illuminated and the COOL light is also de-energized.

Figure 4.9 Defrost

24 VOLT POWER

ENERGIZED
DE-ENERGIZED

TN

ST

F

HPS

PB

IP-CM

TC

CF

TE

IP-EM1

EF

IP-EM2

HTT

TH

HR

ESV

TS

TV

EF

ES

Summary of Contents for PrimeLINE 69NT40-571-001

Page 1: ...Container Refrigeration OPERATIONS AND SERVICE MANUAL For PrimeLINE 69NT40 571 001 to 199 PrimeLINE ONE 69NT40 575 001 to 199 Container Refrigeration Units T 372 Rev B TM ...

Page 2: ......

Page 3: ... 2020 Carrier Corporation Printed in USA December 2020 OPERATIONS AND SERVICE MANUAL For PrimeLINE 69NT40 571 000 to 199 PrimeLINE ONE 69NT40 575 000 to 199 Container Refrigeration Units ...

Page 4: ......

Page 5: ...r 2 2 2 4 7 Evaporator Fan Operation 2 2 2 4 8 Plate Set 2 2 2 5 OPTION DESCRIPTIONS 2 2 2 5 1 Battery 2 2 2 5 2 Dehumidification 2 2 2 5 3 USDA 2 2 2 5 4 Interrogator Receptacle 2 2 2 5 5 Quest 2 2 2 5 6 Autotransformer 2 3 2 5 7 Handles 2 3 2 5 8 Water Cooling 2 3 2 5 9 Back Panels 2 3 2 5 10 460 Volt Cable 2 3 2 5 11 230 Volt Cable 2 3 2 5 12 Cable Restraint 2 3 2 5 13 Upper Fresh Air Makeup 2 ...

Page 6: ...4 4 4 3 6 Perishable Idle Mode Air Circulation 4 4 4 3 7 Perishable Heating Mode 4 4 4 3 8 Perishable Dehumidification 4 5 4 3 9 Perishable Dehumidification Bulb Mode 4 6 4 3 10 Perishable Economy Fan Mode 4 6 4 3 11 Perishable Mode Cooling Sequence of Operation 4 7 4 3 12 Perishable Mode Heating Sequence of Operation 4 8 4 3 13 Perishable Mode Trim Heat 4 8 4 3 14 Frozen Mode Temperature Control ...

Page 7: ... Wireless Communications 4 23 4 8 CONTROLLER CONFIGURATION VARIABLES 4 25 4 9 CONTROLLER FUNCTION CODES 4 26 4 10 CONTROLLER ALARM INDICATIONS 4 37 4 11 CONTROLLER PRE TRIP TEST CODES 4 53 OPERATION 5 1 5 1 INSPECTION 5 1 5 2 CONNECT POWER 5 1 5 2 1 Connecting to 380 460 VAC Power 5 1 5 2 2 Connecting to 190 230 VAC Power 5 1 5 3 ADJUST FRESH AIR MAKEUP VENT 5 2 5 3 1 Upper Fresh Air Makeup Vent 5...

Page 8: ...6 12 AUTOTRANSFORMER MALFUNCTION 6 4 6 13 WATER COOLED CONDENSER OR WATER PRESSURE SWITCH 6 5 6 14 COMPRESSOR OPERATING IN REVERSE 6 5 6 15 ABNORMAL TEMPERATURES 6 5 6 16 ABNORMAL CURRENTS 6 5 SERVICE 7 1 7 1 SECTION LAYOUT 7 1 7 2 MANIFOLD GAUGE SET 7 1 7 2 1 Evacuating the Manifold Gauge Set 7 2 7 3 SERVICE CONNECTIONS 7 2 7 3 1 Connecting the Manifold Gauge Set 7 3 7 3 2 Removing the Manifold G...

Page 9: ...the Evaporator Fan Assembly 7 19 7 17 2 Disassemble the Evaporator Fan Assembly 7 20 7 17 3 Assemble the Evaporator Fan Assembly 7 20 7 18 EVAPORATOR SECTION CLEANING 7 21 7 18 1 Cleaning Preparation 7 21 7 18 2 Cleaning Procedure 7 22 7 19 ELECTRONIC EXPANSION VALVE EEV 7 22 7 19 1 Removing an EEV 7 22 7 19 2 Installing an EEV 7 22 7 20 HUMIDITY SENSOR 7 23 7 20 1 Checking the Operation of the Hu...

Page 10: ...SOR SERVICE 7 34 7 28 1 Ice Bath Preparation 7 34 7 28 2 Sensor Checkout Procedure 7 35 7 28 3 GDP Supply and Return Sensor Calibration 7 37 7 28 4 Sensor Replacement 7 43 7 28 5 Sensor STS and SRS Reinstallation 7 45 7 28 6 Sensor RTS and RRS Reinstallation 7 45 7 28 7 Sensor DTS Reinstallation 7 46 7 28 8 Sensor ETS1 and ETS2 Reinstallation 7 46 7 28 9 Sensor CPDS Reinstallation 7 46 7 29 VENT P...

Page 11: ...oting Sequence 4 14 Figure 4 11 DataCORDER Configuration Screen 4 20 Figure 4 12 DataCorder Probe Calibration Screen 4 21 Figure 4 13 DataCorder Probe Calibration Screen 4 21 Figure 4 14 DataCORDER Systems Tool Screen 4 22 Figure 4 15 DataLINE and DataLINE Connect 4 23 Figure 5 1 Autotransformer 5 2 Figure 5 2 Upper Fresh Air Make Up Flow Chart 5 3 Figure 5 3 TripWise Status in DataCORDER 5 9 Figu...

Page 12: ...utting Wire Ties 7 40 Figure 7 26 DataLINE Probe Calibration 7 40 Figure 7 27 DataLINE Calibrate Sensors Button 7 41 Figure 7 28 DataLINE Enter Service Center Information 7 41 Figure 7 29 Ice Bath 7 42 Figure 7 30 DataLINE Start Cal Button 7 42 Figure 7 31 DataLINE Calibration Results 7 43 Figure 7 32 Sensor Types 7 44 Figure 7 33 Sensor and Cable Splice 7 44 Figure 7 34 Supply Sensor Positioning ...

Page 13: ...ngs Menu nEt Options 4 24 Table 4 7 Controller Configuration Variables 4 25 Table 4 8 Controller Function Codes 4 26 Table 4 9 Controller Pre Trip Test Codes 4 53 Table 4 10 DataCORDER Pre Trip Result Records 4 59 Table 7 1 Valve Override Control Displays for Cd41 SELCt 7 29 Table 7 2 Sensor Resistance AMBS DTS ETS RRS RTS SRS STS 7 36 Table 7 3 Sensor Resistance PrimeLINE CPDS 7 37 Table 7 4 R 13...

Page 14: ......

Page 15: ...f and power supply is disconnected In case of severe vibration or unusual noise stop the unit and investigate 1 4 Maintenance Precautions Beware of unannounced starting of the evaporator and condenser fans Do not open the condenser fan grille or evaporator access panels before turning power off disconnecting and securing the power plug Be sure power is turned off before working on motors controlle...

Page 16: ...ING Do not attempt to remove power plug s before turning OFF the Start Stop switch ST unit circuit breaker s and external power source WARNING Make sure the power plugs are clean and dry before connecting to power receptacle WARNING Make sure that the unit circuit breaker s CB 1 CB 2 and the Start Stop switch ST are in the O OFF position before connecting to any electrical power source WARNING Mak...

Page 17: ...ccording to nameplate specifications to ensure optimal unit performance CAUTION Do not remove wire harnesses from controller modules unless you are grounded to the unit frame with a static safe wrist strap CAUTION Unplug all controller module wire harness connectors before performing arc welding on any part of the container CAUTION Pre trip inspection should not be performed with critical temperat...

Page 18: ...formance and premature system failure due to the precision machinery and assembly required within the compressor To repair the unit remove the faulty compressor and replace with an approved Carrier compressor If the return of the compressor is not required follow local waste collection recycling regulations in discarding the compressor CAUTION Take necessary steps place plywood over coil or use sl...

Page 19: ...tion 2 2 Refrigerant PrimeLINE models 69NT40 571 000 to 099 and PrimeLINE ONE models 69NT40 575 000 to 099 are units designed to only be charged with R 134a refrigerant PrimeLINE models 69NT40 571 100 to 199 and PrimeLINE ONE models 69NT40 575 100 to 199 are R 513A ready units They are supplied with a complete charge of R 134a refrigerant But they are capable of being field converted to R 513A ref...

Page 20: ...wire battery would charge but the controller will not monitor anything related to it A standard 2 wire NiCAD battery would not charge NOTE If ambient temperature is greater than 45 deg C the carrier provided rechargeable batteries will not charge 2 5 2 Dehumidification The unit may be fitted with a humidity sensor This sensor allows setting of a humidity set point in the controller In dehumidifica...

Page 21: ...o each customer s requirements 2 5 12 Cable Restraint Various designs are available for storage of the power cables These options are variations of the compressor section cable guard 2 5 13 Upper Fresh Air Makeup The unit may be fitted with an upper fresh air makeup assembly The fresh air makeup assembly is available with a Vent Positioning Sensor VPS and may also be fitted with screens 2 5 14 Lab...

Page 22: ...FRESH Manual located in the Literature section of the Container Refrigeration website To find the manual from the Literature section click on Options EverFRESH 2 5 18 TripWise TripWise is a new premium option available for PrimeLINE units TripWise is software logic that runs in the background during every voyage and will let you know whenever a standard pre trip inspection PTI is needed See Sectio...

Page 23: ...sh Air Makeup Vent Panel Located inside are Evaporator Fan 2 Defrost Tempera ture Sensor DTS 2 Access Panel Located inside are Evaporator Fan 1 Electronic Expansion Valve EEV Heat Termi nation Thermostat HTT 3 Fork Lift Pockets 4 Control Panel 5 Unit Display 6 Keypad 7 Start Stop Switch ST 8 Compressor 9 Access Panel for Supply Temperature Sensor Supply Recorder Sensor STS SRS 10 Ambient Temperatu...

Page 24: ...ng it at the bottom Most evaporator components are accessible by removing the upper rear panel or by removing the evaporator fan access panels Figure 3 2 Evaporator Section 1 Evaporator Fan 1 2 Return Temperature Sensor RTS Return Recorder Sensor RRS 3 Humidity Sensor HS location 4 Evaporator Fan 2 5 Evaporator Coil 6 Evaporator Coil Heaters 7 Defrost Temperature Sensor DTS 8 Heat Termination Ther...

Page 25: ...Economizer Connection 8 Discharge Pressure Transducer DPT 9 Digital Unloader Valve DUV 10 Suction Pressure Transducer SPT 11 Evaporator Pressure Transducer EPT 12 High Pressure Switch HPS 13 Discharge Service Valve 14 Suction Service Valve 15 Supply Temperature Sensor STS Supply Recorder Sensor SRS 16 Warning Label 3 1 5 Air Cooled Condenser Section The air cooled condenser section see Figure 3 4 ...

Page 26: ...an 4 Condenser Coil Cover 5 Condenser Fan Motor 6 Receiver 7 Receiver Sight Glass 8 Receiver Moisture Liquid Indicator 9 Fusible Plug 10 Filter Drier 11 Economizer 12 Economizer Solenoid Valve ESV 13 Economizer Expansion Valve EXV 14 Service Access Valve Not visible in view located behind Filter Drier 3 2 4 5 8 7 14 11 12 13 6 9 10 1 ...

Page 27: ...r The brazed plate water cooled condenser section see Figure 3 5 consists of the brazed plate water cooled condenser water couplings a water pressure switch and a fusible plug The receiver is retained in this configuration and the brazed plate heat exchanger is placed between the air cooled condenser and the receiver Figure 3 5 Brazed Plate Water Cooled Condenser 1 Water Cooled Condenser WCC 2 Cou...

Page 28: ...le Figure 3 6 Control Box Section 1 Compressor Contactor CH 2 Compressor Phase A Contactor PA 3 Compressor Phase B Contactor PB 4 Heater Contactor HR 5 Condenser Fan Contactor CF 6 Low Speed Evaporator Fan Contactor ES 7 High Speed Evaporator Fan Contactor EF 8 Current Sensor Module 9 Circuit Breaker CB1 460V 10 Control Transformer 11 Transformer AC Line Filter 12 Start Stop Switch ST 13 Controlle...

Page 29: ...jury and or property damage Never use air or gas mixtures containing oxygen O2 for leak testing or operating the product Charge only with refrigerants R 134a or R 513A as specified for the unit model number Refrigerant must conform to AHRI Standard 700 specification Refrigerant R 134a R 513A Conforming to AHRI standard 700 specifications CAUTION Charge water cooled condenser or receiver according ...

Page 30: ...ower High Speed 0 36 0 63 Nominal Horsepower Low Speed 0 05 0 8 Rotations Per Minute High Speed 2850 rpm 3450 rpm Rotations Per Minute Low Speed 1425 rpm 1725 rpm Voltage and Frequency 360 460 VAC 1 25 Hz 400 500 VAC 1 5 Hz Bearing Lubrication Factory lubricated additional grease not required Rotation CW when viewed from shaft end Fuses Control Circuit 7 5 amps F3 F4 Controller DataCORDER 7 5 amps...

Page 31: ...90 2 97 V Controller Setpoint Range 35 to 30 C 31 to 86 F Table 3 3 Safety and Protective Devices Unsafe Condition Device Device Setting Excessive current draw Circuit Breaker CB 1 25 amp Manual Reset Trips at 29 amps 460 VAC Circuit Breaker CB 2 50 amp Manual Reset Trips at 62 5 amps 230 VAC Circuit Breaker CB 2 70 amp Manual Reset Trips at 87 5 amps 230 VAC Excessive current draw in the control ...

Page 32: ...itch cut out setting the condenser fan will automatically start During the standard mode of operation the normally closed digital unloader valve DUV controls the system refrigerant flow and capacity by loading and unloading the compressor in frequent discrete time intervals If the system capacity has been decreased to the lowest allowable capacity with the DUV the unit will enter a trim heat mode ...

Page 33: ...er 12 Economizer Solenoid Valve ESV 13 Economizer Expansion Valve EXV 14 Economizer Expansion Valve EXV Sensing Bulb 15 Economizer Connection 16 Electronic Expansion Valve EEV 17 Evaporator 18 Evaporator Temperature Sensor ETS1 19 Evaporator Temperature Sensor ETS2 20 Digital Unloader Valve DUV 21 Evaporator Pressure Transducer EPT 22 Suction Pressure Transducer SPT 23 Suction Service Valve 18 19 ...

Page 34: ...zer 12 Economizer Solenoid Valve ESV 13 Economizer Expansion Valve EXV 14 Economizer Expansion Valve EXV Sensing Bulb 15 Economizer Connection 16 Electronic Expansion Valve EEV 17 Evaporator 18 Evaporator Temperature Sensor ETS1 19 Evaporator Temperature Sensor ETS2 20 Digital Unloader Valve DUV 21 Evaporator Pressure Transducer EPT 22 Suction Pressure Transducer SPT 23 Suction Service Valve 18 19...

Page 35: ...id Line Service Valve 14 Filter Drier 15 Economizer 16 Economizer Solenoid Valve ESV 17 Economizer Expansion Valve EXV 18 Economizer Expansion Valve EXV Sensing Bulb 19 Economizer Connection 20 Electronic Expansion Valve EEV 21 Evaporator 22 Evaporator Temperature Sensor ETS1 23 Evaporator Temperature Sensor ETS2 24 Digital Unloader Valve DUV 25 Evaporator Pressure Transducer EPT 26 Suction Pressu...

Page 36: ......

Page 37: ...onnectivity Figure 4 1 Control Module 1 Micro Link 5 Controller DataCORDER Module 2 Controller Power Connector 3 Fuses 7 5A 4 Device Power Connector 5 Micro USB Port 6 Mounting Screw CAUTION Do not remove wire harnesses from circuit boards unless you are grounded to the unit frame with a static safe wrist strap or equivalent static drain device CAUTION Remove the controller module and unplug all c...

Page 38: ...be is used for control When this LED is illumi nated the temperature displayed in the AIR TEMPERATURE display is the read ing at the return air probe Table 4 2 Keypad Function Key Function CODE SELECT Access function codes PRE TRIP Display Pre Trip selection menu Discontinue pre trip in progress ALARM LIST Display alarm list and clear alarm queue MANUAL DEFROST INTERVAL Display selected defrost mo...

Page 39: ...ctivates or deactivates compo nents in accordance with current unit operating conditions and selected modes of operation The programming is divided into function codes Some of the codes are read only while the remaining codes may be user configured The value of the user configurable codes can be assigned in accordance with user desired mode of operation A list of the function codes is provided in ...

Page 40: ...be in Perishable Pulldown mode in economized operation However pressure and current limit functions may restrict the valve if either exceeds the preset value 4 3 5 Perishable Steady State Mode In Perishable Steady State Mode the control temperature is maintained near a setpoint that is above the Heat Lockout Temperature Once setpoint is reached the unit will transition to Perishable Steady State M...

Page 41: ...y sensed is 2 below the dehumidification setpoint the high speed evaporator fans will be energized During dehumidification power is applied to the defrost heaters This added heat load causes the controller to open the electronic expansion valve EEV to match the increased heat load while still holding the supply air tem perature very close to the setpoint Opening the EEV reduces the temperature of ...

Page 42: ...e temperature at which the DTT is considered closed for interval timer start or demand defrost is 10 C 50 F for open values from 25 6 C 78 F down to a 10 C 50 F setting For open values lower than 10 C the closed values will decrease to the same value as the open setting Bulb Mode is terminated when Bulb Mode function code Cd35 is set to Nor Dehumidification function code Cd33 is set to Off The use...

Page 43: ...ill open contacts TS to close the ESV and take the unit out of economized operation f The controller continuously monitors supply air temperature Once the supply air temperature falls below setpoint the controller periodically records supply air temperature setpoint and time A calculation is then performed to determine temperature drift from setpoint over time If the calculation determines that co...

Page 44: ...troller will pulse the HR relay to energize the evaporator heaters in sequence with the compressor digital signal 4 3 14 Frozen Mode Temperature Control In Frozen Mode the controller maintains the return air temperature at setpoint the yellow RETURN indicator light is illuminated and the default reading on the display window is the return temperature sensor RTS reading When the return air temperat...

Page 45: ...ding the controller will be turned off when the control temperature is less than or equal to the setpoint 2 C 4 F After an off cycle period of 60 minutes the unit will turn on the high speed evaporator fans for three minutes and then check the control temperature If the control temperature is greater than or equal to the frozen setpoint 0 2 C 0 4 F the unit will restart the refrigeration system an...

Page 46: ...of removing power to the cooling components compressor evaporator fans and con denser fan closing the EEV and turning on the heaters which are located below the evaporator coil During normal operation de icing will continue until temperatures indicate that the ice on the coil has been removed proper air flow has been restored and the unit is ready to control temperature efficiently If defrost was ...

Page 47: ...ck immediately following the defrost cycle the evapora tion fans are started and run for eight minutes to stabilize the temperature throughout the container A probe check comparison is carried out at the end of the eight minute period if any sensor is found out of calibration At this time its alarm set is no longer used for control reorder purposes 4 Probe Check Logic The logic determines that a P...

Page 48: ... may be operator set to select the action the controller will take upon a system failure The fac tory default is full system shutdown See Table 4 8 4 3 25 Protection Mode Generator Protection Function codes Cd31 Stagger Start Offset Time and Cd32 Current Limit may be operator set to control the start up sequence of multiple units and operating current draw The factory default allows on demand star...

Page 49: ...ng to return air high and low limits Depending on the fan mode of operation selected the evaporator fans may be programmed to run at low speed some or all of the time according to the control logic 4 4 Controller Alarms Alarm display is an independent controller software function If an operating parameter is outside of expected range or a component does not return the correct signals back to the c...

Page 50: ...ip inspection Active Alarms Correct software version Did Evaporator fans start Operating pressures normal Check Power Supply Install Latest Software Revision Load correct unit configuration See alarm details repair Correct all faults Yes Yes Yes Yes No Yes No Yes No No No No Correct Refrigerant issue Unit OK Yes No Refer to CONNECT POWER Refer to CONNECT POWER Refer to CONTROLLER SOFTWARE Refer to...

Page 51: ...st run to completion A detailed description of the pre trip tests and test codes is provided in Table 4 9 Detailed operating instructions are provided in Section 5 8 4 6 DataCORDER 4 6 1 Description Carrier Transicold DataCORDER software is integrated into the controller and serves to eliminate the tempera ture recorder and paper chart DataCORDER Software is subdivided into operational software co...

Page 52: ...emperature Current reading of the cargo probe 4 dC15 19 Future Expansion These codes are for future expansion and are not in use at this time dC20 24 Temperature Sensors 1 5 Calibration Current calibration offset values for each of the five probes supply return USDA 1 2 and 3 These values are entered via the interrogation program dC25 Future Expansion This code is for future expansion and is not i...

Page 53: ...ndard Mode the user may configure the DataCORDER to record data using one of seven standard config urations The seven standard configuration variables with their descriptions are listed in Table 4 5 The inputs of the six thermistors supply return USDA 1 USDA 2 USDA 3 and cargo probe and the humidity sensor input will be generated by the DataCORDER NOTE The DataCORDER software uses the supply and r...

Page 54: ...sor AMBS 13 Evaporator temperature sensor ETS 14 Compressor discharge temperature sensor CPDS 15 Return temperature sensor RTS 16 Supply temperature sensor STS 17 Defrost temperature sensor DTS 18 Discharge pressure transducer DPT 19 Suction pressure transducer SPT 20 Evaporator pressure transducer EPT 21 Vent position sensor VPS 4 6 5 Logging Interval dCF03 The user may select four different time...

Page 55: ...s 1 Press the ALT MODE key on the keypad 2 Use the Arrow keys until dCdSP is displayed 3 Press the ENTER key 4 Use the Arrow keys to toggle through S supply R Return P1 P2 P3 and C4 Cargo sensors 5 Press the ENTER key and a temperature value will appear in the right window and 1 with sensor designa tion will appear in the left window to signify the temperature displayed is the most recent reading ...

Page 56: ...ations in the cargo Provision is made to connect these probes to the DataCORDER via receptacles located at the rear left hand side of the unit Four or five receptacles are provided The four 3 pin receptacles are for the probes The 5 pin receptacle is for the Interrogator The probe receptacles are sized to accept plugs with tri cam coupling locking devices A label on the back panel of the unit show...

Page 57: ...he Arrow keys to bring up code Cd19 Select btESt 6 Place the three probes Refer to the USDA Treatment Manual for directions on placement of probes in fruit and probe locations in container Sensor 1 USDA1 Place in a box at the top of the stack of the fruit nearest to the air return intake Sensor 2 USDA2 Place slightly aft of the middle of the container halfway between the top and bottom of the stac...

Page 58: ...ifying the values and ensuring a successful connection has been made with the DataCORDER click on the Send button to send the modified parameter values The maximum allowed length of the ISO Trip Header is 128 characters If the user tries to refresh the screen or close the utility without sending the changes made on the screen to the DataCORDER the user is alerted with a message 4 6 15 DataCORDER C...

Page 59: ...r connection of equipment for cali bration and also to download recorded data from the DataCORDER NOTE Downloading using the USDA port inside of the container is not supported by DataLINE 4 7 2 Controller Wireless Communications The ML5 controller offers short range wireless connectivity through wireless 802 11 b g n A mobile device can wirelessly connect to the ML5 controller using the DataLINE C...

Page 60: ... wireless connections 4 Next to Passcode or Token enter the passcode obtained from the Net menu on the display if it is not already shown there See Section 4 7 2 c for reference 5 Select Login 6 When DataLINE connect is connected a message will appear Connected to the WIFI successfully 7 After clicking OK to the message the features of DataLINE Connect are now available Refer to DataLINE Connect u...

Page 61: ...ailed procedures for using DataLINE Connect 4 8 Controller Configuration Variables Table 4 7 Controller Configuration Variables Config Title Default Option CnF02 Evaporator Fan Speed dS Dual SS Single CnF03 Control Temperature Sensors FOUr duAL CnF04 Enable Dehumidification On OFF CnF08 Evaporator Motor Type 1Ph 3Ph CnF09 Refrigerant Type r134a r744 CnF11 Defrost Off Selection noOFF OFF CnF15 Enab...

Page 62: ...ion NOTICE Note If the function is not applicable the display will read Display Only Functions Cd01 through Cd26 are display only functions Cd01 Capacity Modulation Displays the DUV percent closed The right display reads 100 when the valve is fully closed The valve will usually be at 10 on start up of the unit except in very high ambient temperatures Cd03 Compressor Motor Current The current senso...

Page 63: ... the Compressor Motor Hour Meter display The Unit Run Time Hour Meter cannot be reset Cd17 Relative Humidity Humidity sensor reading is displayed This code displays the relative humidity as a percent value Cd18 Software Revision Number The software revision number is displayed Cd19 Battery Check Request backup battery test and display results or scroll to last result After selecting CD19 press the...

Page 64: ... is AUTO See Section 4 3 20 for information on Defrost Interval CnF11 determines whether the operator will be allowed to chose OFF as a defrost interval option After a new Defrost Interval is selected the previously selected Interval is used until the next defrost termination the next time the DTT contacts are OPEN or the next time power to the control is interrupted If the previous value or the n...

Page 65: ... is also reduced The five values for 460 VAC operation are 15 17 19 21 or 23 amperes The factory default setting is 21 amperes Cd33 Humidity Setpoint This is the value in percent to which the system will dehumidify There are configuration variables that determine whether dehumidification capabilities are installed In the Test Mode the setpoint will be temporarily set to 1 allowing the test of dehu...

Page 66: ...ay the return recorder sensor reading Cd40 Container Identification Number If a valid container id exists the default display for Cd40 will be cd40_XXXXX where XXXXX is the 5th character through the 9th character of the container id Press the Enter key while on Cd40 to display id_YYYYYYY where YYYYYYY is the 5th character to the 11th character of the container id If no valid container id exists or...

Page 67: ...t position in units of 5 CMH units displayed as CM or CFM units displayed as CF depending on the selection of Cd46 Airflow display units Cd28 Metric Imperial or the pressing of the deg C F key Cd45 will display whenever the control detects movement via the sensor unless AL50 is active Cd45 will display for 30 seconds then time out and return to the normal display mode Cd46 Airflow Display Units Se...

Page 68: ...rol Cnf57 Out Evaporator speed select goes to Hi for units with PWM Compressor Control Cnf57 In DTT setting goes to 25 6_C or 18 0_C depending on Cnf41 Whenever dehumidification mode is set to bUlb DTT setting goes to 18 0 C if it had been set higher Whenever dehumidification mode is set to dEhUM DTT setting goes to 25 6 C or 18 0 C depending on Cnf41 For units without PWM Compressor Control Cnf57...

Page 69: ... Press the ENTER key to take the interface down into a hierarchy of parameter selection menus act treat days probe and spnew setting Press the ENTER key in any of the parameter selection menus to commit selection of the currently displayed parameter and cause the interface to descend into the next parameter selection menu All parameter selection menus alternate between a blank display and the curr...

Page 70: ...lay and the current selection menu is cancelled but any previously committed changes are retained Available parameters and parameter ranges are a function of configuration options and previously selected parameters as indicated above Parameter with the exception of ASC may not be altered if Cd53 is re entered if ASC is On When ASC has completed including reaching the last setpoint done on the left...

Page 71: ...e display will flash between STArT PdN and PrESS EnTEr Upon entering Cd59 the operator will be required to acknowledge that they want to initiate the pump down control The display will flash between STArT PdN and PrESS EnTEr Once the decision to continue is confirmed pump down logic will begin and will take complete control of the unit until pump down either succeeds or fails This operation can no...

Page 72: ...event will be recorded in the DataCorder each time the action of turning it ON or OFF is taken Default setting is OFF Unit will default to OFF with the selection of PTI or a TripStart on the unit Cd71 EverFRESH Mode Cd71 has three selectable modes of operation FRESH All EverFRESH operations are enabled and setpoints for CO2 and O2 can be edited OFF All EverFRESH operations are disabled PURGE the o...

Page 73: ...ans operating properly Corrective Action Replace fan s if defective See Evaporator Fan Motor Assembly Section 7 17 AL017 Compressor Pressure Delta Failure Cause Compressor has attempted to start in both directions and fails to generate sufficient pressure differential between Suction Pressure Transducer SPT and Discharge Pressure Transducer DPT Component N A Troubleshooting Controller will attempt...

Page 74: ...or short to ground Corrective Action Replace defective sensor s Component Wiring Troubleshooting Check wiring for short to ground Corrective Action Repair as needed Component Controller Troubleshooting Controller may have an internal short Corrective Action Replace controller See Controller Service Section 7 27 AL022 Evaporator IP Open Cause Evaporator motor internal protector IP is open Component...

Page 75: ... motor IP at plug connection pins 4 6 Corrective Action Replace defective condenser fan motor See Condenser Fan Motor Assembly Service Section 7 12 AL026 All Supply Return Probes Failure Cause Sensors out of range Component All sensors detected as out of range Troubleshooting Perform pre trip P5 Corrective Action If P5 passes no further action is required If P5 fails replace the defective sensor a...

Page 76: ...rrective Action Resetting the unit may correct problem monitor the unit If the alarm reappears replace the keypad and harness AL207 Fresh Air Vent Open with Frozen Setpoint Cause Unit has a frozen setpoint and Vent Position Sensor VPS is indicating that the fresh air vent is open Component Vent Position Sensor VPS Troubleshooting Manually reposition vent to 0 and confirm using Cd45 If Cd45 is not ...

Page 77: ...id line service valve is fully open Corrective Action Open liquid line service valve as needed Component Filter Drier Troubleshooting Check the filter drier If it is iced up or very cold it indicates that the filter drier needs replacement Corrective Action Replace the filter drier if needed See Filter Drier Service Section 7 14 Component Condenser Fan Troubleshooting Check condenser fan for prope...

Page 78: ...ay indicate a failing compressor replace the compressor See Compressor Service Section 7 9 AL250 Air Vent Position Sensor Fault Cause Vent Position Sensor VPS out of range Component Vent Position Sensor VPS Troubleshooting Make sure VPS is secure Corrective Action Manually tighten panel Troubleshooting If the alarm persists replace the sensor or the assembly Corrective Action Replace VPS AL251 Dat...

Page 79: ...re Sensor RTS Fault Cause Invalid Return Temperature Sensor RTS reading Component Return Temperature Sensor RTS Troubleshooting Perform pre trip P5 Corrective Action If P5 passes no further action is required If P5 fails replace the defective sensor as determined by P5 See Temperature Sensor Service Section 7 28 AL257 Ambient Sensor AMBS Fault Cause Invalid Ambient Temperature Sensor AMBS reading ...

Page 80: ...ive Action Replace heater s if defective See Evaporator Heater Removal and Replacement Section 7 16 Component Contactor Troubleshooting Check voltage at heater contactor on the heater side Corrective Action If no voltage present replace heater contactor if defective AL263 Exceed Current Limit Setting Cause Unit operating above current limit Component Refrigeration System Troubleshooting Check unit...

Page 81: ...tive Troubleshooting Monitor Corrective Action If the alarm persists it may indicate a failing compressor See Compressor Service Section 7 9 AL267 Humidity Sensor HS Fault Cause Humidity Sensor HS reading out of range Component Humidity Sensor HS Troubleshooting Make sure the HS is properly connected in the socket Make sure the HS wires have not been damaged Corrective Action Monitor replace HS if...

Page 82: ...e sensor values by following the Sensor checkout procedure See Section 7 28 Corrective Action If the sensor is bad replace If not verify the harness wiring and connections to the controller AL274 USDA Temp 3 Out of Range Cause USDA Temp 3 Sensor is out of range Component Sensor Troubleshooting Validate sensor values by following the Sensor checkout procedure See Section 7 28 Corrective Action If t...

Page 83: ... of the panel See Section 7 29 for Vent Position Sensor service procedures Corrective Action If unable to obtain a zero reading replace the defective VPS If unit is loaded ensure vent is closed Note and replace VPS on next PTI The alarm will not affect the EverFRESH system from operating AL909 Oxygen Sensor O2 Fault Cause Triggered anytime the O2 sensor reading is outside of the normal operation r...

Page 84: ...le Alarm LED Open the fresh air vent and air compressor is enabled Setup Verify all EverFRESH components are functioning properly by checking for EverFRESH alarms and running a P 20 PreTrip Troubleshooting If a component is not functioning properly it will fail the appropriate P 20 sub test Note components in order below Component Membrane Pressure Transducer MPT Troubleshooting Remove the MPT Tur...

Page 85: ...d74 and perform a ML5 self check to verify the controller is functioning properly If it fails replace the controller If it passes self check replace the EN AL962 Oxygen O2 Out of Range Cause This is a notification alarm and does not pose a risk to fresh produce however the benefit of atmosphere control will not be lost O2 level reaches pulldown limit and then O2 exceeds 5 over setpoint for 30 minu...

Page 86: ...o EF Pt Verify that the value is between 5 psig and 5 psig A value indicates a failed sensor or harness Pressure outside of range indicates a bad sensor replace the sensor Component System Plumbing Troubleshooting Inspect plumbing hoses fittings check valve and orifices for signs of leakage Repair as required With the compressor running spray the pressure relief valve with soapy water Replace if l...

Page 87: ... test fails replace the valve If the mechanical test fails check for obstructions blocking system flow Remove obstructions If it still fails replace the valve Component ML5 Controller Troubleshooting Access function code Cd74 to perform an ML5 self diagnostic test AL982 CO2 Injection Failure Cause If unit is configured with the CO2 injection option this alarm is triggered when Cd71 is set to On to...

Page 88: ...icroprocessor Failure Cause The controller performs self check routines If an internal failure occurs an ERR alarm will appear on the display This is an indication the controller needs to be replaced Error Description ERR 0 RAM failure Indicates that the controller working memory has failed ERR 1 Program Memory Failure Indicates a problem with the controller program ERR 2 Watchdog time out The con...

Page 89: ...ent draw is measured and then the heater is turned on After 15 seconds the current draw is measured again The change in current draw is then recorded Test passes if the change in current draw test is in the range specified P2 Tests Condenser Fan Current Draw Condenser fan is turned on then off Current draw must fall within specified range No other system components will change state during this te...

Page 90: ...alidity of the Air Stream Temperature Sensors P5 0 Supply Return Probe Test The High Speed Evaporator Fan is turned on and run for eight minutes with all other outputs de energized A temperature comparison is made between the return and supply probes Test passes if temperature comparison falls within the specified range NOTE If this test fails P5 0 and FAIL will be displayed If both Probe tests th...

Page 91: ... Test is skipped if the controller configuration has the humidity sensor out and Vout is less than 0 20 Volts Test P5 9 must pass before this test is run P5 11 Humidity Sensor Installation Verification Test This is a Pass Fail test of humidity sensor installation sensor is present Test passes if Vout is greater than 0 20 Volts for the humidity sensor Test fails if Vout is less than 0 20 Volts for ...

Page 92: ... equipped Test passes if change of suction pressure is greater than 4 psia when the valve opens for 10 seconds Otherwise it fails P6 10 Electronic Expansion Valve Test The test records the suction pressure during the open valve position and passes if the suction pressure increase is above 3 psi when the valve opens for 10 seconds NOTE P7 0 P8 are included with Auto 2 Auto 3 only P9 0 through P10 a...

Page 93: ...he CO2 Sensor Status indicates that a CO2 sensor is present calibration of the CO2 sensor will be attempted during P8 1 Once P8 1 begins calibration will be attempted when the supply temperature goes below 5 C If the CO2 sensor voltage reads within the 0 95 1 15Vdc range before the end of P8 1 the sensor will be calibrated by holding the CO2 zero line low for 4 seconds Once calibration is performe...

Page 94: ...splay The test fails if the 180 Minute timer expires before the control temperature reaches setpoint 0 3 C If the test fails it will not auto repeat There is no pass display for this test Once the control temperature reaches setpoint the test proceeds to test 10 1 P10 1 Frozen Mode Pulldown Test Control temperature must be at least 7 2 C 45 F The setpoint is changed to 17 8 C The system will then ...

Page 95: ...robe SRS Test Pass Fail Skip 5 2 Secondary Return Probe RRS Test Pass Fail Skip 5 3 Evaporator Fan Direction Test Pass Fail Skip 5 7 Primary vs Secondary Evaporator Temperature Sensor Test Pass Fail Skip 5 8 Future Expansion 5 9 Primary vs Secondary Evaporator Pressure Transducer Test Pass Fail Skip 5 10 Humidity Sensor Controller Configuration Verification Test Pass Fail Skip 5 11 Humidity Sensor...

Page 96: ... Skip Result Averaged DataCORDER supply temperature SRS over last recording interval 9 0 Defrost Test Pass Fail Skip Result DTS reading at end of test line voltage line frequency time in defrost 10 0 Frozen Mode Heat Test Pass Fail Skip Result STS time unit is in heat 10 1 Frozen Mode Pulldown Test Pass Fail Skip Result STS time to pull down unit to 17 8 C 0 F 10 2 Frozen Mode Maintain Test Pass F...

Page 97: ... to Section 7 11 3 Open the control box door Check for loose electrical connections or hardware 4 Check color of moisture liquid indicator 5 2 Connect Power WARNING Do not attempt to remove power plug s before turning OFF the Start Stop switch ST unit cir cuit breaker s and external power source WARNING Make sure the power plugs are clean and dry before connecting to power receptacle 5 2 1 Connect...

Page 98: ...uire fresh air circulation The vent must be closed when transporting frozen foods Air exchange depends on static pressure differential which will vary depending on the container and how the con tainer is loaded Units may be equipped with a vent position sensor VPS The VPS determines the position of the upper fresh air vent as equipped and sends data to the controller display 5 3 1 Upper Fresh Air ...

Page 99: ... min utes On completion of the first four minutes the vent is required to remain stable for the next four min utes If vent position changes are detected during the four minute stability period AL250 will be generated This provides the user with the ability to change the vent setting without generating multiple events in the DataCORDER 5 4 EverFRESH Operation Procedures and technical information re...

Page 100: ...To shift to air cooled condenser operation stop the unit set the CFS switch to position I and restart the unit Disconnect the water lines to the water cooled condenser 5 6 Starting and Stopping Instructions WARNING Make sure that the unit circuit breaker s CB 1 CB 2 and the Start Stop switch ST are in the O OFF position before connecting to any electrical power source NOTE The electronic phase det...

Page 101: ... a pre trip selection menu The user may have the option of selecting one of two automatic tests These tests will automatically perform a series of individual pre trip tests The user may also scroll down to select any of the individual tests When only the short sequence is configured it will appear as AUtO in the display Otherwise AUtO1 will indicate the short sequence and AUtO2 will indicate the l...

Page 102: ... on the right display with the corresponding test number to the left The user may then press the Down Arrow key to repeat the test the Up Arrow key to skip to the next test or the PRE TRIP key to terminate testing The unit will wait indefinitely or until the user manually enters a command CAUTION When a failure occurs during automatic testing the unit will suspend operation awaiting oper ator inte...

Page 103: ...d or a difference of 2 0 C 3 6 F between the return air sensors Probe disagreement found in either pair can trigger a defrost probe check In Frozen Mode only the controlling probes are considered Disagreement of the controlling probes can trigger a defrost probe check which will occur when the difference between the sensors is greater than 2 0 C 3 6 F Nor mally the controlling probes are the retur...

Page 104: ... not meet the pass fail requirements It is recom mended to pre trip the unit following customer specific guidelines prior to the unit s next trip Pressing the ENTER key while SELCt PrtrP is displayed will enter into the Pre trip test menu Pressing the Arrow keys will navigate through the standard PTI test selections menu 5 10 2 Enabling or Disabling TripWise Option 1 Press the CODE SELECT key on t...

Page 105: ...the current DataLINE software release the event will show the status of the unit Figure 5 3 TripWise Status in DataCORDER In DataLINE perform an all data download by selecting from the drop down menu TripWise Summary and then select a date in User Logged Events as shown in the Figure below Figure 5 4 Generating TripWise Summary Report ...

Page 106: ...T 372 5 10 This will generate the status results in a DataLINE TripWise Summary Report as shown in the Figure below Figure 5 5 TripWise Summary Report Status Results ...

Page 107: ...display and the right will display Off Use the Arrow keys to bring up On in the right display and press the ENTER key 5 trEAt is now displayed in the left display and the right will be flashing the last setting shown as XX X C Use the Arrow keys to select the desired cold treatment setpoint and press the ENTER key NOTE trEAt is the maximum value that the USDA probes need to remain below to pass th...

Page 108: ...ht hand display will alternate between trEAt and the cargo temperature Once the treatment time has been completed the setpoint temperature will increase to the SPnEW setting chosen in step 8 12 When the cold treatment process is complete the SPnEW setpoint will be displayed in the left hand dis play and cargo temperature in the right hand display alternating with COLd Done COLd Done will continue ...

Page 109: ...t a final setpoint SP x With SP x in the left display select by scrolling to the desired flashing set point in the right display and press ENTER While the unit is operating in ASC mode the left hand display will alternate between current unit setpoint and ASC The right hand display will alternate between current control temperature and ACtvE The user can deter mine the amount of time left at the c...

Page 110: ......

Page 111: ...lfunction of current sensor Replace Compressor hums but does not start Low line voltage Check Single phasing Check Shorted or grounded motor windings Section 7 9 Compressor seized Section 7 9 6 2 Unit Operates Long or Continuously in Cooling Container Hot load Normal Defective box insulation or air leak Repair Refrigeration system Shortage of refrigerant Section 7 3 Evaporator coil covered with ic...

Page 112: ...elay defective Check Heater termination thermostat open Section 7 15 Unit will not heat or has insufficient heat Heater s defective Section 7 15 Heater contactor or coil defective Replace Evaporator fan motor s defective or rotating back wards Section 7 15 Section 7 17 Evaporator fan motor contactor defective Replace Controller malfunction Section 6 9 Defective wiring Replace Loose terminal connec...

Page 113: ...on service valve partially closed Open Filter drier partially plugged Section 7 14 Low refrigerant charge Section 7 3 No evaporator air flow or restricted air flow Section 7 15 Excessive frost on evaporator coil Section 6 6 Evaporator fan s rotating backwards Section 7 17 3 EEV control malfunction Replace Failed digital unloader valve DUV Replace Suction and discharge pressures tend to equalize wh...

Page 114: ...lly plugged Section 7 14 Low refrigerant charge Section 7 3 No evaporator air flow or restricted air flow Section 7 15 Excessive frost on evaporator coil Section 6 6 Evaporator fan s rotating backwards Section 7 17 3 EEV control malfunction Section 7 19 Failed digital unloader valve DUV Replace Loose or insufficiently clamped sensor Replace High suction pressure with low superheat Foreign material...

Page 115: ... Incorrect wiring of current sensor 6 15 Abnormal Temperatures High discharge temperature Condenser coil dirty Section 7 11 2 Condenser fan rotating backwards Section 7 12 Condenser fan inoperative Section 7 12 1 Refrigerant overcharge or non condensibles Section 7 3 Discharge service valve partially closed Open Electronic expansion valve EEV control malfunction Replace Failed suction pressure tra...

Page 116: ......

Page 117: ...Container Units Operation 7 1 Section Layout Service procedures are provided in this section beginning with refrigeration system service then refrigeration sys tem component service electrical system service temperature recorder service and general service Refer to the Table of Contents to locate specific topics 7 2 Manifold Gauge Set The manifold gauge set see Figure 7 1 is used to determine syst...

Page 118: ...ylinder 3 Evacuate to 10 inches of vacuum and then charge with refrigerant to a slightly positive pressure of 0 1 kg cm2 1 0 psig 4 Frontseat both manifold gauge set valves and disconnect from cylinder The gauge set is now ready for use Figure 7 2 Manifold Gauge Hose Set 1 RED Refrigeration and or Evacuation Hose SAE J2196 R 134a 2 Hose Fitting 0 5 16 Acme 3 YELLOW Refrigeration and or Evacuation ...

Page 119: ...field service coupling see Figure 7 2 to the access valve 4 Turn the field service coupling knob clockwise to open the system to the gauge set 5 Slightly midseat the service valve to read system pressures 6 Repeat the procedure to connect the other side of the gauge set CAUTION To prevent trapping liquid refrigerant in the manifold gauge set make sure set is brought to suction pressure before disc...

Page 120: ...rant system certain parts may frost Allow the part to warm to ambient temperature before dismantling This avoids internal condensation which puts moisture in the system 8 After repairs have been made make sure to perform a refrigerant leak check see Section 7 5 and evacuate and dehydrate the low side see Section 7 6 9 Check refrigerant charge See Section 7 7 1 7 5 Refrigerant Leak Checking WARNING...

Page 121: ...re If the ambient temperature is lower than 15 6 C 60 F ice might form before moisture removal is complete Heat lamps or alternate sources of heat may be used to raise the system temperature 4 Additional time may be saved during a complete system pump down by replacing the filter drier with a section of copper tubing and the appropriate fittings Installation of a new drier may be performed during ...

Page 122: ...If nitrogen was used relieve the pressure 9 Repeat steps 6 and 7 one time 10 Remove the copper tubing and change the filter drier Evacuate unit to 500 microns Close the electronic vacuum gauge and vacuum pump valves Shut off the vacuum pump Wait five minutes to see if vacuum holds This procedure checks for residual moisture and or leaks 11 With a vacuum still in the unit the refrigerant charge may...

Page 123: ...r approximately 10 minutes and check the refrigerant charge 7 7 3 Adding Refrigerant to System Partial Charge 1 Examine the refrigerant system for any evidence of leaks and repair as necessary See Section 7 5 2 Maintain the conditions outlined in the beginning of this section Section 7 7 1 3 Fully backseat the suction service valve and remove the service port cap 4 Connect the charging line betwee...

Page 124: ...emoval and Replacement of Compressor 1 Turn the unit ON and run it in full cool mode for 10 minutes NOTE If the compressor is not operational frontseat the suction and discharge service valves and go to step 5 below 2 Frontseat the manual liquid line valve and allow the unit to pull down to 0 1 kg cm2 1 psig 3 Place the Start Stop switch ST to 0 turn the unit circuit breaker CB 1 OFF and disconnec...

Page 125: ... as shown in Figure 7 5 Install the four base mounting bolts loosely 15 Place the new Teflon seals at the compressor suction and discharge ports as well as the O rings at the unloader and economizer line connection ports Hand tighten all four connections 16 Torque the four base mounting screws to 6 2 mkg 45 ft lbs 17 Torque the compressor ports connections 18 Connect butt splice and heat shrink th...

Page 126: ... High Pressure Switch 7 10 1 Checking High Pressure Switch WARNING Do not use a nitrogen cylinder without a pressure regulator NOTE The high pressure switch is non adjustable 1 Remove switch as outlined in Figure 7 10 2 2 Connect ohmmeter or continuity light across switch terminals Ohm meter will indicate no resistance or continuity light will be illuminated if the switch closed after relieving co...

Page 127: ...cted 2 Remove the condenser fan grille 3 Starting from the top of the coil use a water hose with a nozzle to wash the coil from the inside out 4 Systematically wash across the inside top face of the coil until the water runs clean 5 Wash down the center section and then through the bottom of the coil Continue washing until the water runs clear 6 After the coil is clean rinse the condenser fan to r...

Page 128: ...pported 2 Secure the condenser coil into the unit using the retained hardware refit the mylar and fender washers a Refit the side support bracket bolts b Refit the top support bracket bolts as well as the top grille extension support c Refit the bottom support bracket bolts 3 Braze the condenser coil inlet connection 4 Insert the receiver pipe work onto the coil outlet and loosely secure the recei...

Page 129: ...er Fan Motor Remove and Replace WARNING Do not remove the condenser fan grille before turning power OFF and disconnecting the power plug 1 Remove the condenser fan grille Retain all bolts and washers for reuse 2 Remove the condenser fan by loosening the two set screws 3 Disconnect the condenser fan motor wiring CAUTION Take necessary steps place plywood over coil or use sling on motor to prevent m...

Page 130: ...and actual condensing temperature coupled with a small difference in temperature of entering and leaving condensing water is an indication of a dirty condensing coil If the water cooled condenser is dirty it may be cleaned and de scaled 7 13 1 Cleaning Supplies Needed Oakite Aluminum Cleaner 164 available as a powder in 20 kg 44 lb pails and 205 kg 450 lb drums Oakite Composition No 32 available a...

Page 131: ...diluting Oakite Compound No 32 with water This is accomplished by slowly adding 0 47 liter 1 U S pint of the acid Oakite No 32 to 2 8 liters 3 U S quarts of water WARNING Oakite No 32 is an acid Be sure that the acid is slowly added to the water DO NOT PUT WATER INTO THE ACID this will cause spattering and excessive heat WARNING Wear rubber gloves and wash the solution from the skin immediately if...

Page 132: ...ing water or is not re circulated in a closed or tower system neutralizing is not necessary 9 Following the water flush circulate a 56 7 gram 2 ounce per 3 785 liter 1 U S gallon solution of Oakite Aluminum Cleaner 164 through the tubes to neutralize Drain this solution 10 Flush the tubes thoroughly with fresh water 11 Put the unit back in service and operate under normal load Check the head press...

Page 133: ...7 15 1 Evaporator Coil Replacement 1 Pump unit down See Section 7 4 WARNING Always turn OFF the unit circuit breakers CB 1 CB 2 and disconnect main power supply before working on moving parts 2 With power OFF and power plug removed remove the screws securing the panel covering the evaporator section upper panel 3 Disconnect the defrost heater wiring 4 Remove the mounting hardware from the coil 5 U...

Page 134: ...from the insulation tester to a fixed ground point preferably the ground plate in the control box e At the load side of the heater contactor check the insulation resistance to ground If readings are 1 Mohm then the heaters are operating properly and no action is needed If readings are 1 Mohm then the faulty heater needs to be identified Proceed to step 3 for units with a heater access panel or ste...

Page 135: ...remove h To install heater reverse steps i Reconnect all wiring using new splices and heat shrink where needed The heat shrink MUST have a melt able liner to ensure that the connections are properly sealed when shrunk This can be seen as a Ring of melt liner pushed from under the heat shrink at each end of the shrink tube NOTE Failure to use melt liner heat shrink allows moisture to wick up under ...

Page 136: ...e blade is not damaged In the past it was a common practice to insert a screwdriver between the fan blades to keep it from turning This practice can no longer be used as the blade is made up of a material that will be damaged It is recommended that an impact wrench be used when removing the blade Do not use the impact wrench when reinstalling as galling of the stainless steel shaft can occur 2 App...

Page 137: ...ample Fumigation is the process by which a chemical is released into an enclosed area to eliminate infesta tions of insects termites rodents weeds and soil born disease Typically any aluminum oxide that becomes detached from evaporator fan stators will be blown into the wet evapo rator coil where it will be caught and then flushed out of the unit during routine defrost cycles However it is still h...

Page 138: ...7 19 1 Removing an EEV WARNING Always turn OFF the unit circuit breakers CB 1 CB 2 and disconnect main power supply before working on moving parts 1 Pump down the compressor see Section 7 4 and frontseat both suction and discharge valves 2 Turn unit power off and remove power from the unit 3 Remove the coil 4 Remove the valve The preferred method of removing the valve is to cut the connection betw...

Page 139: ...e 1 4 socket wrench or nut driver One clean clear water bottle with a minimum 6 cm 2 5 in opening and capacity to hold 500 ml 16 9 oz 100 ml 3 4 oz of fresh water distilled if available 50 gm of Salt NaCl Procedure 1 Remove the left Upper Fresh Air Makeup Vent panel 2 Remove the humidity sensor from the mounting hardware and bring to the front of the access panel 3 Disconnect the humidity sensor f...

Page 140: ...the reefer unit on 12 Press the CODE SELECT key on the keypad 13 Use the Arrow keys until Cd17 is displayed then press the ENTER key 14 This displays the humidity sensor reading Verify the reading is between 60 and 85 relative humidity 15 If the humidity sensor display is outside of this range reconfirm the salt mixture and retest If not in range replace the sensor at the next opportunity 16 Wipe ...

Page 141: ... discharge valves 2 Remove the valve The preferred method of removing the solenoid valve is to cut the connection between the brazed section and the valve using a small tube cutter Remove valve Alternatively heat inlet and outlet connections to valve body and remove valve 3 Clean the valve stem with mild cleaner if necessary 7 21 3 Installing the Solenoid Valve 1 Fit the new solenoid valve into po...

Page 142: ...the connection between the brazed section and the valve using a small tube cutter Remove valve Alternatively use a wet rag to keep valve cool Heat inlet and outlet connections to valve body and remove valve 7 Clean the valve stem with a mild cleaner if necessary 7 22 2 Installing the Economizer Expansion Valve 1 The economizer expansion valve should be wrapped in a soaked cloth for brazing 2 Braze...

Page 143: ...le a jumper procedure can be used as follows 1 Remove all four controller fuses F1 F2 F3a F3b 2 Remove the KA6 wire from the KA controller connector on the front of the controller 3 Disconnect the X1 wire from the 24VAC side of the transformer black wire and locate it away from the transformer 4 Jumper between the black transformer wires to the KA6 wire removed from the connector 5 Connect power t...

Page 144: ...n 4 Reinstall and tighten the brackets that secure the valve body to the discharge line 5 Torque the o ring face seal connections to 18 to 20 ft lbs 6 Install the coil onto the valve body and tighten the attachment bolt NOTE Confirm that the small spacer tube is inserted into the coil prior to attaching it to the valve body The valve will not function correctly without it 7 Leak check and evacuate...

Page 145: ...26 Autotransformer If the unit does not start check the following 1 Verify the 460 VAC yellow power cable is plugged into the receptacle see Figure 7 20 and locked in place 2 Verify that circuit breakers CB 1 and CB 2 are in the ON position If the circuit breakers do not hold in check voltage supply 3 Using a voltmeter and with the primary supply circuit ON check the primary input voltage 460 VAC ...

Page 146: ...en it is placed on the mat 7 27 2 Controller Troubleshooting For reference of the controller location in the control box see Section 3 1 7 For a description of the controller software see Section 4 2 See function code Cd74 see Section 4 9 for controller self diagnostic test 7 27 3 Loading Controller Operational Software from a USB Drive 1 Place the Start Stop switch ST to I to turn the unit On Wai...

Page 147: ...unction code Cd20 and confirm that the correct model configuration is displayed The model displayed in Cd20 should match what is shown on the unit nameplate 7 27 5 Downloading DataCORDER Data to a USB Drive 1 Place the Start Stop switch ST to I to turn the unit On Wait for controller information to be displayed 2 Insert the designated USB flash drive into the controller micro USB port 3 Press the ...

Page 148: ...tainer ID This procedure explains how to set the Container ID which can be found in Function Code Cd40 See Section 4 9 The characters will be preset to the container ID of the box that the refrigeration unit was originally commis sioned in If no ID has been loaded Cd40 will show dashes as the ID will be invalid 1 Place the Start Stop switch ST to I to turn the unit On Wait for controller informati...

Page 149: ...rque value for the connectors is 0 12 mkg 10 inch pounds 7 27 9 Battery Replacement The Carrier rechargeable battery pack part is 79 04262 01 1 Turn unit power Off and disconnect the power supply 2 Open the control box door and remove both the high voltage shield and clear plastic rain shield if installed 3 Disconnect the battery connection at the BA connector and carefully remove wire ties along ...

Page 150: ...tub open to atmosphere and large enough to contain crushed ice and water should be used The tub should be large enough to contain the unit s sensor and the reference thermometer Enough distilled water should be available to make ice cubes and to set up a proper and stable ice water tri ple point mixture Prepare ice using distilled water Pre cool distilled water for testing Procedure 1 Prepare a mi...

Page 151: ... adapter The carrier harness adapter part numbers are 22 50485 00 CA connector 22 50486 00 CC connector and 22 50487 00 ME connector All readings from the adapter will be resistance readings with power removed and the harness disconnected from the ML5 controller 5 Locate the proper wires to be ohmed on the system schematic and check against the temperature resistance chart provided in Table 7 2 an...

Page 152: ... 23 9 4 115 702 23 73 4 10 923 22 7 6 109 063 24 75 2 10 450 21 5 8 102 846 25 77 10 000 20 4 97 022 26 78 8 9 572 19 2 2 91 563 27 80 6 9 164 18 0 4 86 445 28 82 4 8 777 17 1 4 81 644 29 84 2 8 407 16 3 2 77 139 30 86 8 055 15 5 72 910 31 87 8 7 720 14 6 8 68 938 32 89 6 7 401 13 8 6 65 206 33 91 4 7 096 12 10 4 61 699 34 93 2 6 806 11 12 2 58 401 35 95 6 529 10 14 55 330 36 96 8 6 265 9 15 8 52 ...

Page 153: ...energized It is important that all dismantling work is done and tools and personnel are away from the unit before powering on the unit for calibration Table 7 3 Sensor Resistance PrimeLINE CPDS C F OHMS C F OHMS 40 40 2 889 600 18 64 4 117 656 38 36 4 2 532 872 20 68 0 107 439 36 32 8 2 225 078 22 71 6 98 194 34 29 2 1 957 446 24 75 2 89 916 32 25 6 1 724 386 25 77 86 113 30 22 0 1 522 200 26 78 8...

Page 154: ...he sensor values If the test fails identify and correct the faulty sensor and rerun the test Tools Required Socket screwdrivers set Phillips screwdriver Standard hand tools Interrogator cable Laptop with DataLINE 3 1 or above installed Clean insulated container for distilled water and ice A regularly calibrated reference thermometer recommended to be of accuracy up to 2 decimal places GDP Calibrat...

Page 155: ...Figure 7 22 Save all hardware for re installation Figure 7 22 Removing Front Access Panels 2 On the right side disconnect the fan motor wiring loosen the fastener and remove slide the evaporator motor from the unit see Figure 7 23 Figure 7 23 Removing Evaporator Motor 3 Loosen the fastener on the sensor bracket see Figure 7 24 Figure 7 24 Return Sensors Bracket ...

Page 156: ...Before powering on the unit it is important to ensure that all dismantling work is done and tools are away and service personnel are not working on the unit at the time of power on 2 Open DataLINE version 3 1 or above From the DataLINE launch pad click on the Probe Calibration button see Figure 7 26 to go to the Probe Calibration screen A pop up window will appear reminding the user to ensure prop...

Page 157: ...being performed Then click the Save button A pop up window will appear reminding the user to ensure proper ice bath temperature Click OK to acknowledge and remember to maintain the Ice bath at 0 C 32 F Figure 7 28 DataLINE Enter Service Center Information 5 Prepare the ice bath Refer to the Ice bath preparation procedure Ensure that the set up i e ice bath sensors reference thermometer has reached...

Page 158: ...mometer Confirm that the sensor readings have stabilized and the sensors are within 0 3 C 0 5 F The readings can be taken from the Uncal column in the Current Probe Offset Temperatures table 9 Then after confirming the sensor readings have stabilized click on the Start Cal button see Figure 7 30 After clicking Start Cal the process begins automatically and will complete in less than 5 minutes Figu...

Page 159: ...ended sensors in calibration have passed 13 After the completion of the calibration restore the unit to its original state 7 28 4 Sensor Replacement WARNING Always turn OFF the unit circuit breaker CB 1 and disconnect main power supply before removing electrical parts 1 Place the Start Stop switch ST to 0 to turn the unit Off Disconnect the power supply NOTE Include white date code label when cutt...

Page 160: ...res keeping wire colors together Make sure wires are pushed into crimp fittings as far as possible and crimp with crimping tool 9 Solder spliced wires with a 60 tin and 40 lead Rosincore solder 10 Slide heat shrink tubing over each splice so that ends of tubing cover both ends of crimp as shown in Figure 7 33 11 Heat tubing to shrink over splice Make sure all seams are sealed tightly against the w...

Page 161: ...oning will give the sensor the optimum amount of expo sure to the supply air stream and will allow the Controller to operate correctly Insufficient probe insertion into the probe holder will result in poor temperature control due to the lack of air flow over the sensor It is also necessary to ensure that the probe tip does not contact the back panel The design minimum clearance of 6 mm 1 4 inch sh...

Page 162: ...plying thermal grease Insulating material must completely cover the sensor to ensure the correct temperature is sensed Figure 7 36 Evaporator Temperature Sensor Positioning 1 Insulation 2 ETS Tube Holder 3 ETS1 and ETS2 4 Wire Tie 7 28 9 Sensor CPDS Reinstallation To replace the Compressor Discharge Temperature Sensor see Figure 7 37 1 Ensure the unit is disconnected from the power source 2 Verify...

Page 163: ...In order to replace the Upper VPS the panel must be removed and replaced with another upper fresh air panel equipped with VPS Upon installation a new VPS assembly requires calibration 1 Rotate the vent to the 0 CMH CFM position Cd45 will automatically display 2 Press and hold the ENTER key for five seconds 3 After the ENTER key has been pressed the display will read CAL for calibration 4 Press and...

Page 164: ...25 6 0 3 27 16 6 0 03 12 24 4 1 1 26 14 8 0 02 10 23 3 1 9 25 13 0 0 06 8 22 2 2 8 24 11 2 0 11 6 21 1 3 6 23 9 4 0 16 4 20 0 4 6 22 7 6 0 22 2 18 9 5 5 21 5 8 0 27 0 17 8 6 5 20 4 0 0 33 2 16 7 7 5 19 2 2 0 39 4 15 6 8 5 18 0 4 0 45 6 14 4 9 6 17 1 4 0 51 8 13 3 10 8 16 3 2 0 57 10 12 2 11 9 15 5 0 0 64 12 11 1 13 1 14 6 8 0 71 14 10 0 14 4 13 8 6 0 78 16 8 9 15 7 12 10 4 0 85 18 7 8 17 0 11 12 2...

Page 165: ... 90 0 21 69 8 4 90 84 28 9 93 5 22 71 6 5 08 86 30 0 97 0 23 73 4 5 27 88 31 1 100 6 24 75 2 5 46 90 32 2 104 3 25 77 0 5 65 92 33 3 108 1 26 78 8 5 85 94 34 4 112 0 27 80 6 6 06 96 35 6 115 9 28 82 4 6 27 98 36 7 120 0 29 84 2 6 48 100 37 8 124 2 30 86 0 6 70 102 38 9 128 4 31 87 8 6 93 104 40 0 132 7 32 89 6 7 15 106 41 1 137 2 33 91 4 7 39 108 42 2 141 7 34 93 2 7 63 110 43 3 146 4 35 95 0 7 87...

Page 166: ... 0 12 18 142 61 1 235 7 51 123 8 12 51 144 62 2 242 3 52 125 6 12 85 146 63 3 249 0 53 127 4 13 20 148 64 4 255 9 54 129 2 13 56 150 65 6 262 9 55 131 0 13 92 56 132 8 14 28 57 134 6 14 66 58 136 4 15 04 59 138 2 15 42 60 140 0 15 82 61 141 8 16 22 62 143 6 16 63 63 145 4 17 04 64 147 2 17 47 65 149 0 17 90 Table 7 4 R 134a Refrigerant Pressure Temperature Chart Note Underline figures are inches o...

Page 167: ...4 6 27 16 6 0 25 12 24 4 5 5 26 14 8 0 30 10 23 3 6 5 25 13 0 0 36 8 22 2 7 5 24 11 2 0 42 6 21 1 8 5 23 9 4 0 48 4 20 0 9 6 22 7 6 0 54 2 18 9 10 7 21 5 8 0 61 0 17 8 11 9 20 4 0 0 67 2 16 7 13 1 19 2 2 0 74 4 15 6 14 3 18 0 4 0 81 6 14 4 15 6 17 1 4 0 89 8 13 3 16 9 16 3 2 0 96 10 12 2 18 3 15 5 0 1 04 12 11 1 19 7 14 6 8 1 12 14 10 0 21 1 13 8 6 1 21 16 8 9 22 6 12 10 4 1 29 18 7 8 24 2 11 12 2...

Page 168: ...5 7 21 69 8 5 85 84 28 9 109 5 22 71 6 6 05 86 30 0 113 3 23 73 4 6 26 88 31 1 117 3 24 75 2 6 47 90 32 2 121 3 25 77 0 6 68 92 33 3 125 4 26 78 8 6 90 94 34 4 129 6 27 80 6 7 13 96 35 6 133 9 28 82 4 7 36 98 36 7 138 3 29 84 2 7 59 100 37 8 142 8 30 86 0 7 83 102 38 9 147 4 31 87 8 8 07 104 40 0 152 0 32 89 6 8 32 106 41 1 156 8 33 91 4 8 57 108 42 2 161 7 34 93 2 8 83 110 43 3 166 7 35 95 0 9 10...

Page 169: ...0 122 0 13 73 142 61 1 261 9 51 123 8 14 09 144 62 2 268 9 52 125 6 14 45 146 63 3 276 1 53 127 4 14 82 148 64 4 283 3 54 129 2 15 20 150 65 6 290 8 55 131 0 15 58 56 132 8 15 97 57 134 6 16 37 58 136 4 16 77 59 138 2 17 18 60 140 0 17 60 61 141 8 18 03 62 143 6 18 46 63 145 4 18 90 64 147 2 19 35 65 149 0 19 80 Table 7 5 R 513A Refrigerant Pressure Temperature Chart Note Underline figures are inc...

Page 170: ...7 2 3 10 24 23 1 9 2 6 1 4 20 75 6 3 8 5 5 16 18 132 11 14 9 3 8 16 240 20 27 1 7 16 14 372 31 42 1 2 13 516 43 58 3 9 16 12 684 57 77 3 5 8 11 1104 92 124 7 3 4 10 1488 124 168 1 Non Free Spinning Locknuts etc 1 4 20 82 5 6 9 9 3 5 16 18 145 2 12 1 16 4 3 8 16 264 22 0 29 8 7 16 14 409 2 34 1 46 2 1 2 13 567 6 47 3 64 1 9 16 12 752 4 62 7 85 5 8 11 1214 4 101 2 137 2 3 4 10 1636 8 136 4 184 9 ...

Page 171: ...8 1 T 372 SECTION 8 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 1 Legend Standard Unit Configuration ...

Page 172: ...T 372 8 2 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 2 Schematic Diagram Based on Drawing 62 11957 ...

Page 173: ...8 3 T 372 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 3 Unit Wiring Diagram Sheet 1 of 2 Based on Drawing 62 11957 ...

Page 174: ...T 372 8 4 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 4 Unit Wiring Diagram Sheet 2 of 2 Based on Drawing 62 11957 ...

Page 175: ...as determined to be no higher than PED Category I and is covered by the Machinery Directive 2006 42 EC The following Harmonized Standards were applied for this equipment The following Technical Standards were applied for this equipment ISO 1496 2 2008 Person established in Europe authorized to compile a copy of the Technical File Shaun Bretherton Service Engineering Manager of CTL Rotterdam Pittsb...

Page 176: ......

Page 177: ... est soumis aux deux conditions suivantes 1 Cet appareil ne doit pas causer d interférences 2 Cet appareil doit accepter toutes les interférences y compris celles susceptibles de provoquer un fonctionnement indésirable de l appareil This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this dev...

Page 178: ......

Page 179: ...热部件 O O O O O O 马达 压缩机与风扇组件 O O O O O O 温度控制微处理器系统 X O O O O O 断路器与接触器 O O O O O O 变压器 O O O O O O 传感器 X O O O O O 通讯组件 O O O O O O 阀组件 X O O O O O 电缆线 电源 O O O O O O 电池 O O X O O O 标签与绝缘材料 O O O O O O 玻璃部件 X O O O O O 本表格依据 SJ T 11364 的规定编制 O 表示该有害物质在该部件所有均质材料中的含量均在 GB T 26572 规定的限量要求以下 X 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB T 26572 规定的限量要求 62 66122 00 Rev A ...

Page 180: ......

Page 181: ...r Fan Motor Remove Replace 7 13 Condenser Grille 2 3 Condenser Grille and Venturi Assembly Location 3 3 Configuration Identification 2 1 Configuration Software CnF Variables 4 3 Container Unit Description Front Section 3 1 Control Box 2 1 Control Box Component Location 3 6 Control Box Section 3 6 Control Panel Location 3 1 Controller 2 3 7 30 Controller Alarm Indications 4 37 Controller Modules Ha...

Page 182: ... Evaporator Temperature Sensors ETS1 ETS2 Loca tion 3 2 F Failure Action 4 12 Filter Drier Location 3 3 Filter Drier Replace 7 17 Filter Drier Service 7 16 First Aid 1 1 Fork Lift Pockets Location 3 1 Fresh Air Makeup Vent 2 3 3 2 Fresh Air Makeup Vent Adjustment 5 2 Frozen Heat Mode 4 9 Frozen Economy Mode 4 9 Frozen Idle Mode 4 9 Frozen Mode Temperature Control 4 8 Frozen Mode Cooling Sequence o...

Page 183: ...ements 1 1 Standard Mode 4 17 Standard Operation Description 3 10 Start Temperature Recorder 5 5 Start Up Compressor Bump Start 4 4 Start Up Compressor Phase Sequence 4 3 Starting and Stopping Instructions 5 4 Starting the Unit 5 4 Start Stop Switch ST Location 3 1 Start Up Inspection 5 4 Stopping the Unit 5 4 Suction Connection Location 3 3 Suction Pressure Transducer SPT Location 3 3 Suction Ser...

Page 184: ......

Page 185: ......

Page 186: ...Carrier Transicold Division Carrier Corporation P O Box 4805 Syracuse NY 13221 USA www carrier com container refrigeration ...

Reviews: