T-372
4–36
Cd65 TripWise
If the function is off, display "OFF". If the function is on, display "ON".
“-----” will be displayed if the TripWise option is not active for the current
configuration.
Press the ENTER key. The existing entry will flash. Use the Arrow keys to
alternate between OFF and ON. Press ENTER again to set the Expiration
Interval.
Left display: “dAyS”
Right display: Expiration Interval 2 through 365 in 1 day increments.
Default value is 30.
Cd66 Instantaneous Power
(kW)
Real power in kW currently being used by the system.
Value is “-----“,“ nnn.n
Display “-----“ if not configured else nnn.n
Cd67 Total Power (kW-hr)
Energy used by the system, in kW-hrs, since last Trip Start.
Value is “-----“,“ nnnnn
Display “-----“ if not configured else nnnnn
Cd70 Temp Setpoint Lock
Cd70 locks out setpoint selection, requiring the user to manually turn the lock off,
prior to making a setpoint change. If the setpoint lock is “ON”, and the user
attempts to enter a new setpoint, a message “SPLK” (Setpoint Lock) is in the left
display and “ON” in the right display for five seconds.
Press the ENTER key. “SPLK” will display along with the current setting of “ON”
or “OFF”. Use the Arrow keys to change the selection - the new selection will then
flash for five seconds. Press the ENTER key to confirm the new selection.
An event will be recorded in the DataCorder each time the action of turning it
“ON” or “OFF” is taken.
Default setting is “OFF”. Unit will default to “OFF” with the selection of PTI or a
TripStart on the unit.
Cd71 EverFRESH Mode
Cd71 has three selectable modes of operation:
FRESH - All EverFRESH operations are enabled and setpoints for CO
2
and O
2
can be edited.
OFF - All EverFRESH operations are disabled.
PURGE - the operator has the ability to suspend EverFRESH operations while
per-charging gas levels in the container.
Cd74 Controller Diagnostic
Request Test “tESt”, Displayed Test Result “PASS,” “FAIL0,” “FAIL1,” “FAIL2”
After selecting CD70, press the ENTER key while “tESt” is displayed to run the
Controller Self Diagnostic test. While the test is running, “tESt” will flash on the
display. Once the test is complete, the Test Result will be displayed. After 30
seconds, the controller returns to displaying the setpoint.
"PASS" will be the result if all power sources are present and at the correct level,
there are no input faults, and all output tests pass.
"FAIL0" will be the test result if a power source is not available or not at the
correct level.
"FAIL1" will be the test result if all power sources are present and at the correct
level, but there is an input fault.
"FAIL2" will be the test result if all power sources are present and at the correct
level, and there are no input faults, but an output test fails.