T-372
4–50
AL977
Membrane Pressure Transducer (MPT) Fault
Cause:
When the EverFRESH Air Compressor (EAC) is running and pressure is not between -5 psig and
200 psig or the EAC has been OFF for five minutes and pressure is not within the range of -5 psig
and 5 psig.
Component
Membrane Pressure Transducer (MPT)
Troubleshooting
With the EverFRESH system off for 15 minutes, bring up function code
Cd44 and scroll to "EF Pt". Verify that the value is between -5 psig and 5
psig. A "- - - - " value indicates a failed sensor or harness. Pressure outside
of range indicates a bad sensor, replace the sensor.
Component
ML5 Controller
Troubleshooting
Access function code Cd74 to perform an ML5 self-diagnostic test.
AL978
Air Compressor Pressure Low
Cause:
EverFRESH Air Compressor (EAC) engaged and Fresh Air Vent (FAV) and Water Drain Valve
(WDV) are closed and compressor has been running for longer than 20 seconds and Membrane
Pressure Transducer (MPT) Pressure < 75 psig.
Component
Membrane Pressure Transducer (MPT)
Troubleshooting
With the EverFRESH system off for 15 minutes, bring up function code
Cd44 and scroll to "EF Pt". Verify that the value is between -5 psig and 5
psig. A "- - - - " value indicates a failed sensor or harness. Pressure outside
of range indicates a bad sensor, replace the sensor.
Component
System Plumbing
Troubleshooting
Inspect plumbing, hoses, fittings, check valve, and orifices for signs of
leakage. Repair as required.
With the compressor running, spray the pressure relief valve with soapy
water. Replace if leaking. If a spare pressure relief valve is not available,
try opening and closing the valve with an O-Ring on the valve to try and
re-seat.
See the condition for Membrane Pressure Transducer (MPT) Reading
Low in the EverFRESH manual.
AL979
Air Compressor Pressure High
Cause:
EverFRESH Air Compressor (EAC) engaged and Pressure > 135 psig.
Component
Membrane Pressure Transducer (MPT)
Troubleshooting
With the EverFRESH system off for 15 minutes, bring up function code
Cd44 and scroll to "EF Pt". Verify that the value is between -5 psig and 5
psig. A "- - - - " value indicates a failed sensor or harness. Pressure outside
of range indicates a bad sensor, replace the sensor.
Component
System Plumbing
Troubleshooting
Inspect plumbing, hoses, fittings, check valve, and orifices for signs of
blockage. Repair as required.
See the condition for Membrane Pressure Transducer (MPT) Reading
High in the EverFRESH manual.