4–53
T-372
4.11 Controller Pre-Trip Test Codes
Table 4–9 Controller Pre-Trip Test Codes
NOTE:
“Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu includes P0, P1, P2, P3,
P4, P5, P6, P7, P8, P9, P10 and rSLts. “Auto3” menu includes P0, P1, P2, P3, P4, P5, P6, P7 and P8.
P0-0 Pre-Trip Initiated:
Configuration Display,
Indicator Lamps, LEDs, and
Displays
Container identifier code, Cd18 Software Revision Number, Cd20
Container Unit Model Number, & configuration database identifier
CFMMYYDD are displayed in sequence.
Next the unit will indicate the presence or non-presence of an RMU
according to whether any RMU inquiry messages have been received
since the unit was booted.
Units equipped with Autoslide Enabled (Cnf44) will cause the vent to seek
to its closed position, followed by two sequences of opening to 100% and
returning to the closed position. No other autoslide mode of operation will
be available until the two cycles of opening and closing have completed.
Since the system cannot recognize lights and display failures, there are no
test codes or results associated with this phase of pre-trip. To know if the
test passes the operator must observe that the LCD display elements and
the indicator lights behave as described below.
P1 Tests - Heaters Current Draw:
Heater is turned on, then off. Current draw must fall within specified
range. No other system components will change state during this test.
P1-0 Heaters Turned On
Heater starts in the off condition, current draw is measured, and then the
heater is turned on. After 15 seconds, the current draw is measured again.
The change in current draw is then recorded.
Test passes if the change in current draw test is in the range specified.
P1-1 Heaters Turned Off
Heater starts in the off condition, current draw is measured, and then the
heater is turned on. After 15 seconds, the current draw is measured again.
The change in current draw is then recorded.
Test passes if the change in current draw test is in the range specified.
P2 Tests - Condenser Fan Current Draw:
Condenser fan is turned on, then off. Current draw must fall
within specified range. No other system components will change state during this test. If the Water Pres
-
sure Switch is open this test will be skipped.
P2-0 Condenser Fan On
Condenser fan starts in the off condition, current draw is measured, and
condenser fan is then turned on. After 15 seconds the current draw is
measured again. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P2-1 Condenser Fan Off
Condenser fan is then turned off. After 10 seconds the current draw is
measured. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P3 Tests - Low Speed Evaporator Fan Current Draw:
The system must be equipped with a low speed
evaporator fan, as determined by CnF02, the Evaporator Fan Speed Select configuration variable. Low
speed evaporator fan is turned on, then off. Current draw must fall within specified range. No other sys
-
tem components will change state during this test.
P3-0 Low Speed Evaporator Fan
Motors On
High speed evaporator fans will be turned on for 20 seconds, the fans will
be turned off for 4 seconds, current draw is measured, and then the low
speed evaporator fans are turned on. After 60 seconds the current draw is
measured again. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P3-1 Low Speed Evaporator Fan
Motors Off
Low speed evaporator fans are then turned off. After 10 seconds the
current draw is measured. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.