ALARMS
00013
HIGH DISCHARGE PRESSURE
• ACTIVATION: Compressor discharge pressure switch (HPS) contacts are open. HPS contacts open
when the discharge pressure rises. Refer to
• UNIT CONTROL: Refrigeration system shutdown and alarm with PSCON still energized. CSMV at 50%
and EVXV controls superheat.
• RESET CONDITION: Auto reset after 15 minutes if the compressor discharge pressure falls below limit,
or alarm may be manually reset using the display mounted keys or by turning the unit off, then back on
again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check
System Pressures -
Install manifold gauge set and check and compare compressor discharge &
suction pressures with those shown in Unit Data. Refer to
for instruction on comparison. If
discharge pressure is in normal range, proceed to step 5.
2.
Check
Airflow Through Condenser Coil
a. Inspect condenser. Ninety percent or more of the coil surface must be undamaged. Condenser/
Radiator coil must be clean.
b. Check airflow (with unit running). Verify even airflow through the entire coil, and no “dead” spots.
c. Check condenser fan rotation/operation. Fans should operate correctly. Air should be directed in
through the grill.
3.
Perform
Pretrip -
Check CSMV & ECXV tests. Refer to
. Pass Test.
4.
Check Refrigerant
Charge -
Refer to
. Charge must be correct.
5.
Check HPS Power And
Wiring
a. Inspect switch, connector pins & terminals. Verify that there is no physical damage to the switch.
Check the connections for damage and corrosion.
b. Check for power at the 2MM35 or J1A. If a minimum of 11 VDC is not present, check connectors
and wiring between terminals for damage, moisture or corrosion.
c. Check continuity from the switch connector B position to 3MM16 2MM35. Inspect SP-23 and SP-
24 connections. If they are OK replace HPS. If good continuity is not present, check connectors
and wiring between terminals for damage, moisture or corrosion.
6.
Check
HPS
a. With discharge pressure below the switch closing pressure (refer to
). Check continuity
from the switch connector B position to 2MM35. Switch closed.
b. Check switch operation. Test switch. Refer to
7.
Refer to Refrigeration
Troubleshooting -
Refer to
. Discharge must be in range for the cur-
rent ambient and refrigerated compartment conditions.
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......