62-11785
7–30
00094
CHECK COMP CONTACTOR 1
• ACTIVATION: Compressor motor contactor (CCON) circuit is shorted or open.
• UNIT CONTROL: Shutdown and alarm.
• RESET CONDITION: Auto Reset or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check CCON
a. Inspect compressor contactor coil and connector. Verify there is no damage to coil, and no
damage, moisture, or corrosion in connector.
b. Check contactor coil resistance. Refer to
for contactor coil resistance values. Cannot
be open (infinite ohms), shorted (Zero Ohms) or shorted to ground.
2.
Check CCON Using Component Test Mode
a. Use Component Test Mode to energize CCON. (Refer to
). Verify Current Draw on
Component Test Mode Screen. Refer to
for correct electrical values.
b. Check coil voltage between A1 and A2. Verify 12 VDC between A1 & A2.
c. Check resistance at contacts. Verify contacts are closed at L1-T1, L2-T2, L3-T3.
3.
Check CCON Wiring
- Inspect harness & control box connector pins & terminals. (See wiring schematic
). Verify there is no physical damage to harness, and no damage, moisture, or corrosion in
connectors.
00095
CHECK CDCON1 COIL
• ACTIVATION: Condenser fan motor contactor (CDCON) circuit is shorted or open.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Auto Reset or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check CDCON
a. Inspect contactor coil and connector. Verify there is no damage to coil, and no damage, moisture,
or corrosion in connector.
b. Check contactor coil resistance. Refer to
for contactor coil resistance values. Cannot
be opened (infinite ohms), shorted (Zero Ohms), or shorted to ground.
2.
Check CDCON Using Component Test Mode
a. Use Component Test Mode to energize CDCON. (Refer to
.) Verify Current Draw on
Component Test Mode Screen. Refer to
for correct electrical values.
b. Check coil voltage between A1 and A2. Verify 12 VDC between A1 & A2.
c. Check resistance at contacts. Verify contacts are closed at L1-T1, L2-T2, L3-T3.
3.
Check CDCON Wiring
- Inspect harness & control box connector pins & terminals. (See wiring sche-
matic
.) Verify there is no physical damage to harness, and no damage, moisture, or corro-
sion in connectors.
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......