7–57
62-11785
00232
SETPOINT ERROR
• ACTIVATION: There is an error in the setpoint that is stored in the main microprocessor memory.
• UNIT CONTROL: Shutdown and alarm.
• RESET CONDITION: Auto reset when a valid setpoint is entered, or alarm may be manually reset by
turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Setpoint
a. Check setpoint setting. Must be between -22 and +90° F (-30° and +32°C).
b. Enter new setpoint.
2.
Reset Microprocessor
a. Place the START/RUN-OFF switch in the OFF position. Disconnect positive battery cable, remove
F7 fuse or unplug 1MM connector, wait 20 seconds and reinstall. Then place the START/RUN-OFF
back in the START/RUN position. The microprocessor powers up OK and the latest setpoint appears
in the display.
b. Valid setpoint can not be entered and alarm 00232 remains active. Download data and replace the
main microprocessor module (MM). Refer to
00233
MODEL # ERROR
• ACTIVATION: There is an error in the Model Number that is stored in the main microprocessor memory.
• UNIT CONTROL: Shutdown and alarm.
• RESET CONDITION: Auto reset only when a valid Model number is entered.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Model Number
a. Check Model # in microprocessor. Model Number is on Nameplate.
b. Enter correct Model Number. Select the correct model number in the “MODEL NUMBER”
Configuration. If correct model number is not found, Install (or have Carrier Transicold dealer
install) latest software revision.
2.
Reset Microprocessor
a. Place the START/RUN-OFF switch in the OFF position. Disconnect positive battery cable, remove
F7 fuse or unplug 1MM connector, wait 20 seconds and reinstall. Place the START/RUN-OFF
back in the START/RUN position. The microprocessor powers up OK and the latest setpoint
appears in the display.
b. Check for valid Model number in Unit Data. Valid number is present. Alarm is cleared.
c. Valid model number can not be entered and alarm remains active. Download data and replace the
main microprocessor module (MM). Refer to
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......