7–59
62-11785
00238
CONFIGURATIONS ERROR
• ACTIVATION: There is an error in the Configuration settings that are stored in the main microprocessor
memory.
• UNIT CONTROL: Incorrect Configuration(s) will be automatically set for default value.
• RESET CONDITION: Auto reset when valid Configuration(s) are entered, or alarm may be manually
reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Configurations
- Check Configurations. All must be set for selectable values.
2.
Check Software Version
- Check microprocessor software version. Upgrade to the latest version of soft-
ware. If changes were made using a newer version of TRU-Tech, that version may contain Configura-
tions that were not present in older versions of APX Control System software.
3.
Reconfigure Microprocessor
- Send settings to microprocessor. Using the latest version of TRU-Tech
and a Data Transfer USB Memory Device, write the desired Configuration file to the device, then load the
file into the microprocessor. Allow the microprocessor to reboot itself.
4.
Reset Microprocessor
a. Place the START/RUN-OFF switch in the OFF position. Disconnect positive battery cable, remove
F7 fuse or unplug 1MM connector, wait 20 seconds and reinstall. Place the START/RUN-OFF
back in the START/RUN position. The microprocessor powers up OK and the latest setpoint
appears in the display.
b. Check for valid Configuration settings in Configuration List. Values are set correctly for all
parameters. Alarm is cleared.
c. Disconnect positive battery cable from the battery, wait 30 seconds, then reconnect and place the
START/RUN-OFF switch in the START/RUN position.The microprocessor powers up OK and the
latest setpoint appears in the display.
d. Check for valid Configuration settings in Configuration List. Values are set correctly for all
parameters. Alarm is cleared.
e. Valid Configurations can not be entered and alarm remains active. Download data and replace the
main microprocessor module (MM). Refer to
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......