62-11785
7–62
00255
MICROPROCESSOR ERROR
• ACTIVATION: If alarm
21100 NO COMM FROM ANY BOARD TO MAIN MICRO
is not active and main
microprocessor input and/or output board configuration is incorrect.
• UNIT CONTROL: Shutdown and alarm.
• RESET CONDITION: Auto reset when board communications are valid, or alarm may be manually reset
by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 in
Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Software Revision
- Check microprocessor software. Unit should have the software upgraded to
the latest version, provided for Carrier Transicold dealers on the TransCentral site.
2.
Reset Microprocessor
a. Place the START/RUN-OFF switch in the OFF position. Disconnect positive battery cable, remove
F7 fuse or unplug 1MM connector, wait 20 seconds and reinstall. Place the START/RUN-OFF
back in the START/RUN position. The microprocessor powers up OK and the latest setpoint
appears in the display.
b. Alarm 00255 remains active. Download data and replace the main microprocessor module (MM).
Refer to
02000
UPDATE SOFTWARE
• ACTIVATION: The software version in one or more of the modules is not compatible with the remainder of
the APX Control System.
• UNIT CONTROL: Shutdown and alarm.
• RESET CONDITION: Auto reset when all module software versions are compatible. Or alarm may be
manually reset using the display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
Software
- Reload software. Unit should have the software upgraded to the latest version, provided for
Carrier Transicold dealers on the TransCentral site.
02001
REAR PANEL SHUTDOWN
• ACTIVATION: 'UNIT OFF' soft key is pressed from Remote Panel.
• UNIT CONTROL: Shutdown and alarm.
• RESET CONDITION: Auto reset when all module software versions are compatible. Or alarm may be
manually reset using the display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
Verify Unit should be shut down.
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......