62-11785
7–76
07001
ECONOMIZER PRESS SENSOR
• ACTIVATION: Economizer Pressure (ECOP) sensor is out of range.
• UNIT CONTROL: Alarm only. Economizer forced to STANDARD mode when alarm is active.
• RESET CONDITION: Economizer Pressure sensor is in range or alarm may be manually reset using the
display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 in
Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check System Pressures
a. Check Unit Data. Refer to
. Compare the pressure readings for the ECOP, the CSP
and the CDP. The ECOP should read between the CSP and the CDP, if not it indicates the ECOP
has failed. Refer to
for instruction on comparison. If discharge pressure is in
normal range, proceed to next step.
b. Place the Unit in Service Mode. Refer to
. After the unit has equalized, compare the
pressure readings for the ECOP, the CSP and the CDP. The ECOP the CSP and the CDP should
all read within 5 psi, if not it indicates the ECOP has failed. Refer to
for instruction
on comparison.
2.
Check Economizer Pressure Sensor
- Inspect sensor & connectors. Verify there is no damage to sen-
sor, and no damage, moisture, or corrosion in connectors.
07006
SUCTION PRESSURE SENSOR
• ACTIVATION: Suction pressure sensor is out of range. If Economizer pressure < or = (Suction pressure -10)
for 10 seconds and suction pressure is > than 40 psig and < than 60 psig with the compressor running.
• UNIT CONTROL: Alarm only. Economizer forced to STANDARD mode when alarm is active.
• RESET CONDITION: Auto reset when Suction Pressure Sensor is in range or, alarm may be manually
reset using the display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check System Pressures
a. Check Unit Data. Refer to
. Compare the pressure readings for the ECOP, the CSP
and the CDP. The ECOP should read between the CSP and the CDP. Refer to
instruction on comparison. If pressures are in normal range, proceed to next step.
b. Place the Unit in Service Mode. Refer to
. After the unit has equalized, compare the
pressure readings for the ECOP, the CSP and the CDP. The ECOP the CSP and the CDP should
all read within 5 psi, if not it indicates a failed sensor. Refer to
for instruction on
comparison.
2.
Check Pressure Sensor
- Inspect sensor & connectors. Verify there is no damage to sensor, and no
damage, moisture, or corrosion in connectors.
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......