62-11785
7–90
28002
NO COMM FROM DOOR SWITCH
• ACTIVATION: The door switch configuration is configured as 3rd Party and no communications have
been received for 15 minutes
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Communications have been received from the door switch.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check for proper APX Control System Configuration -
2. Make sure that all third party configurations are correct and software is current.
Check Switch and Wiring
- Inspect switch, connector pins & terminals. No physical damage to sen-
sor. No damaged or corrosion in connections.
28003
INVALID DOOR SWITCH
• ACTIVATION: The Door Switch configuration is configured as 3rd Party and data received from the switch
is invalid.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Valid data received from door switch.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check for proper APX Control System Configuration -
2. Make sure that all third party configurations are correct and software is current.
Check Switch and Wiring
- Inspect switch, connector pins & terminals. No physical damage to sen-
sor. No damaged or corrosion in connections.
28004
INVALID REMS1
28005
INVALID REMS2
• ACTIVATION: The Remote Switch configuration is configured as 3rd Party and data received from the
switch is invalid.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Valid data received from remote switch.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1. Check for proper APX Control System Configuration -
2. Make sure that all third party configurations are correct and software is current.
Check Switch and Wiring
- Inspect switch, connector pins & terminals. No physical damage to sen-
sor. No damaged or corrosion in connections.
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......