8–19
62-11785
Figure 8.8 Economizer Section
1. Liquid Outlet Line (To EVXV)
2. Liquid Inlet Line (From Drier)
3. Economizer Heat Exchanger
4. Economizer Outlet Pressure Transducer (ECOP)
5. Economizer Expansion Valve (ECXV)
6. Economizer Outlet Temperature Sensor (ECOT)
7. Compressor Economizer Connection
8. Liquid Injection Solenoid Valve (LIV)
9. Strainer (Location)
--------------
8.7.6
Stepper Test Harness
A stepper test harness (Carrier Transicold P/N
07
−
00515) is available for testing the compressor suc-
tion modulation valve (CSMV) and evaporator expan-
sion valve (EVXV).
The test harness is installed by disconnecting the
2SVM connector at the SVM module and plugging the
C1 connector, see
, into the module and C2
connector into the unit harness. With the test harness
in place, the A1/A2 test harness connectors may be
used to perform EVXV testing while the B1/B2 connec-
tors may be used to perform CSMV testing.
Figure 8.9 Stepper Test Harness
4
A1
A2
B1
B2
C2
C1
A2
B2
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......