7–89
62-11785
25201
OVER CURRENT STP2
• ACTIVATION: The stepper current is reported to be too high by stepper board 2 (Indicated by Stepper
Output Voltage < 5V) for 3 seconds as timed at stepper board.
• UNIT CONTROL: Alarm condition. Steppers on board with problem disabled (Powered OFF) until good
power reported from Stepper Board at which point they are re-enabled.
• RESET CONDITION: 10 seconds of good current range reported from all steppers.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 in
Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check power
- Verify power at 3SVM-11 and 3SVM-22.
2.
Check wiring
- Check wiring to ECXV to SVM2. Verify there is no physical damage to harness, and no
damage, moisture, or corrosion in connectors.
25202
CHECK INPUT VOLTAGE STP2
• ACTIVATION: The stepper input voltage is reported out of valid range (9V to 17V) by stepper board 2 for
3 seconds as times at stepper board.
• UNIT CONTROL: Alarm only. Steppers on board with problem disabled (Powered OFF) until good power
reported from Stepper Board at which point they are re-enabled.
• RESET CONDITION: 10 seconds of good voltage reported from all steppers.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 in
Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check power
- Verify power at 3SVM-11 and 3SVM -22.
2.
Check wiring
- Check wiring to ECXV to SVM-2. Verify there is no physical damage to harness, and no
damage, moisture, or corrosion in connectors.
27200
NO COMM FROM MICRO TO OPTIONAL COMM MODULE
• ACTIVATION: Alarm
21100 NO COMM FROM ANY BOARD TO MAIN MICRO
is not active, number of
Comm Modules Configuration is set to 1, and no sync responses have been received from the Comm
Module for 10 seconds.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Sync response received from the Comm Module in the past 10 seconds, alarm
reset or alarm may be manually reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 in
Section.) Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check for other CAN bus alarms
- This alarm may accompany other alarms, complete the trouble-
shooting steps for alarms found. If repairs have been made and the other alarms have cleared, further
troubleshooting may not be required.
2.
Replace Comm Module
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......