29
62-11646
M
ANUAL
D
EFROST
- C
ONTINUED
Defrost may also be initiated automatically at preset intervals by the system
defrost timer or by the defrost air switch.
The defrost mode terminates when the defrost termination temperature
sensor and the supply air temperature sensor both rise higher than 55°F
(12.8°C). If the defrost cycle does not end after a maximum of 45 minutes, the
defrost cycle is terminated automatically. “DEFROST NOT COMPLETE” will
be displayed in the MessageCenter.
If defrost terminates on the 45 minute termination timer, the system will wait
1.5 hours of compressor running time before attempting another automatic
defrost cycle. Pressing the manual defrost key will override this mode and
start a defrost cycle.