5–17
62-11640
SETPOINT(S) & RANGE LOCK
DECIMAL
DISPLAYED
DISPLAYED = setpoint will be shown with a decimal
and temperatures may be selected to a tenth of a de-
gree.
NOT DISPLAYED
NOT DISPLAYED = setpoint will not be shown with a
decimal. All other temperatures will still be displayed
with a decimal.
MIN SETPOINT
-22°F
TO 90°F (
-30°C
to 32°C) in 0.1°F or °C
increments
Indicates to the main microprocessor the desired
minimum allowable set point.
MAX SETPOINT
-22°F TO
90°F
(-30°C
to
32°C
) in 0.1°F or °C
increments
Indicates to the main microprocessor the desired
maximum allowable setpoint.
RANGE 1 LOCK
OR
RANGE 2 LOCK
OFF
START-STOP
CONTINUOUS
OFF = If both Range Locks are OFF, the unit will op-
erate normally.
If either Range 1 or Range 2 is not OFF, the unit will
operate as selected whenever the setpoint is within
that range
START-STOP = The unit will always operate in Start-
Stop whenever the setpoint is between the minimum
& maximum temperatures for that range (refer to the
following sub-configurations).
CONTINUOUS = The unit will always operate in
Continuous Run whenever the setpoint is between
the minimum & maximum temperatures for that
range (refer to the following sub-configurations).
RANGE 1 (or 2) MINIMUM
TEMPERATURE
-22°F TO
90°F
(-30°C
to
32°C
) in 0.1°F or °C
increments
Select the lowest temperature desired for this Range.
RANGE 1 (or 2) MAXIMUM
TEMPERATURE
-22°F TO
90°F
(-30°C
to
32°C
) in 0.1°F or °C
increments
Select the highest temperature desired for this range.
START-STOP SETTINGS
CURRENT FOR S/S SHUTOFF
7.0A
1A TO 10A (in 0.5A in-
crements)
In Start-Stop Operation the charging current must
drop below this value before the unit is allowed to
shut down.
VOLTAGE FOR S/S RESTART
12.2V
12.0 TO 12.8V
The engine will restart from a Start-Stop Off cycle or
a Sleep Mode Off cycle when the battery drops to this
value.
A lower selection may result in a longer off cycle
(based on battery voltage) and possibly overall short-
er battery life. A higher selection may result in a
shorter off cycle (based on battery voltage) and pos-
sibly overall longer battery life.
ENGINE TEMP FOR S/S RE-
START
10°F (-12.23°C)
10°F to 32°F
(-12.23°C to 0°C)
The engine will restart from a Start-Stop Off cycle or
a Sleep Mode Off cycle when the engine coolant
temperature drops to this value.
Table 5–1 Configuration Settings
(Refer to
Section 5.2.3
for instructions on entering Configuration settings)
Configuration
Selections
Description
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......