62-11640
5–24
UNIT SHUTDOWN BELOW
(ambient air temperature)
OFF
120 to -20°F (49 to -
29°C)
If Door Switch = Unit Shutdown is selected:
OFF = the unit will shutdown at any ambient tem-
perature.
Value = when ambient temperature is below the en-
tered value, shut down will be allowed. (When ambi-
ent temperature is above the entered value, the unit
will not shutdown.)
RUN LOW SPEED BELOW
(ambient air temperature)
OFF
120 to -20°F (49 to -
29°C)
If Door Switch = Low Engine Speed is selected:
OFF = the unit will transition to low speed at any am-
bient temperature.
Value = when ambient temperature is below the en-
tered value, transition to low speed will be allowed.
(When ambient temperature is above the entered
value, the unit will not transition to low speed.)
REMOTE SWITCH 1 or 2
NOT INSTALLED
ON CONTACTS
CLOSED
ON CONTACTS
OPEN
OPEN SWITCH
CLOSED
OPEN SWITCH
OPEN
NOT INSTALLED = There is no remote switch.
ON CONTACTS CLOSED = The remote switch will
be used as a remote control switch. The switch con-
tacts will be CLOSED whenever the switch is in the
ON position.
ON CONTACTS OPEN = The remote switch will be
used as a remote control switch. The switch contacts
will be OPEN whenever the switch is in the ON posi-
tion.
OPEN SWITCH CLOSED = The remote switch will
be used as a door switch. The switch contacts will be
CLOSED whenever the door is OPEN.
OPEN SWITCH OPEN = The remote switch will be
used as a door switch. The switch contacts will be
OPEN whenever the door is OPEN.
REMOTE SWITCH 1 or 2
ALARM ONLY
UNIT SHUTDOWN
LOW ENGINE
SPEED
DATA RECORDER
ONLY
ALARM ONLY = When the switch is activated, a
warning alarm will be displayed in the Message-
Center.
UNIT SHUTDOWN = When the switch is activated, a
warning alarm will be displayed in the Message-
Center, and the unit will shutdown.
LOW ENGINE SPEED = When the switch is activat-
ed, the engine will be forced to low speed.
DATA RECORDER ONLY = The DataLink data re-
corder will record every time the the switch is activat-
ed. There will be no alarms or messages displayed in
the MessageCenter.
OTHER SETTINGS
ENABLE ADVANCED USER
MODE:
YES /
NO
YES = Advanced User Mode is automatically en-
abled when the unit is powered on.
NO = Driver Mode is automatically enabled when the
unit is powered on and Advanced User Mode may be
enabled manually.
Table 5–1 Configuration Settings
(Refer to
Section 5.2.3
for instructions on entering Configuration settings)
Configuration
Selections
Description
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......