62-11640
3–26
AUTOFRESH AIR
CLOSED
OPEN
CFM CONTROL
Closed = AutoFresh Air Exchange assembly will be closed.
Open = Assembly will be open if the engine is running and the
setpoint is greater than 28.0°F (-2.22°C).
CFM Control = Assembly will be cycled open and closed over
a 20 minute time period. The length of time the assembly is
opened or closed is based on the Auto Fresh Air Control Func-
tional Parameter. The CFM CONTROL will only be active if the
engine is running and the setpoint is greater than 28.0°F (-
2.22°C).
AUTOFRESH AIR
CONTROL
5 To 50 CFM (in 5 CFM in-
crements)
25 CFM
When CFM Control is selected, this setting is used to set the
amount of air to be exchanged during each 20 minute cycle.
PERISH SENSITIVE
PRODUCT
ON
OFF
OFF = Supply air temperature will be limited to the colder tem-
perature of 32°F (0°C) or set point less the SUPPLY AIR LIMIT
CONFIGURATION VALUE.
ON = Supply air temperature will be limited to set point less the
Supply air Limit Configuration value.
Refer to
for information on Perishable Sensi-
tive Product and Supply Air Configuration interaction.
START-STOP SETTINGS
Time and Temperature values that control Start-Stop Operation are set in this section. The system may be config-
ured so that:
1. the same settings apply to any setpoint = “Together”
or
2. the settings are different, depending on whether the setpoint is in the perishable range or in the frozen
range = “Separate”.
• If “together” is configured, there will be six settings with only the sixth applicable to just frozen range.
• If “Separate” is configured there will be eleven settings five labeled perishable and six labeled frozen.
MIN RUN TIME:
4MINS
TO
60MINS (in 1 minute in-
crements)
This determines the minimum run time for perishable/frozen
setpoints in Start-Stop Operation
MIN OFF TIME:
10 to 90MINS (in 1 minute
increments)
30 MINS
This determines the minimum off time for perishable/frozen
setpoints in Start-Stop Operation.
RESTART TEMP:
0.5 to 18°F (.28 to 10°C)
(in 0.5° increments)
5.5°F (3°C)
Following the Minimum Off Time, should a compartment tem-
perature drift this far above or below setpoint in the Perishable
Range or above setpoint in the Frozen Range, the unit will re-
start.
OVERRIDE TEMP:
3.6 to 18°F (2 to 10°C) (in
0.5 degree increments)
12.0°F (6.7°C)
This selects the override temperature for the Minimum Off
Time portion of the Auto Start-Stop Off Cycle. During the Min-
imum Off Time, should the refrigerated compartment tempera-
ture drift this far above or below setpoint in the Perishable
Range, or above setpoint in the Frozen Range, the unit will
override the Minimum Off Time, and restart.
Table 3–2 Functional Parameters
FUNCTION
PARAMETER
SELECTIONS
DESCRIPTION
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......