ALARMS
00001
LOW FUEL LEVEL WARNING
NOTE
This is an optional alarm which will only occur when a fuel level sensor is present & configured “YES”.
• ACTIVATION: The ENCU circuit is energized (3MM
−
9) and fuel level is 15% or less for more than 30 seconds.
• UNIT CONTROL: Engine Operation: Alarm only.
Electric Operation: Will not activate in electric operation.
• RESET CONDITION: Auto Reset when the ENCU circuit is energized (3MM
−
9) and fuel level is above 17%
for more than 30 seconds, or alarm may be manually reset using the display mounted keys or by turning
the unit off, then back on again.
NOTE: Follow the Troubleshooting steps until a problem is found. Once a repair or correction is made, the active
alarm should clear itself as described below. Operate the unit through the appropriate modes to see if any active
alarm occurs.
CORRECTIVE ACTIONS:
1.
Check For Low Fuel Level
.
Check fuel level in the fuel tank. Add fuel as needed to the fuel tank.
2.
Check Fuel Level Sensor
.
Refer to procedure for alarm
00126 CHECK FUEL SENSOR CIRCUIT
. Alarm condition must be cor-
rected and the alarm cleared to continue.