SETPOINT ERROR
• ACTIVATION: There is an error in the setpoint that is stored in the main microprocessor memory.
• UNIT CONTROL: Engine and Electric Operation: Shutdown and alarm.
• RESET CONDITION: Auto reset when a valid setpoint is entered, or alarm may be manually reset by
turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Setpoint
a. Check setpoint setting. Must be between -22 and +90° F (-30° and +32°C)
b. Enter new setpoint.
2.
Reset Microprocessor
a. Place the START/RUN-OFF switch in the OFF position. Disconnect positive battery cable, remove
the F7 fuse or unplug 1MM connector, wait 20 seconds and reinstall. Then place the START/RUN-
OFF back in the START/RUN position. The microprocessor powers up OK and the latest setpoint
appears in the display.
b. Valid setpoint can not be entered and alarm 00232 remains active. Download data and replace the
main microprocessor module (MM). Refer to
00233
MODEL # ERROR
• ACTIVATION: There is an error in the Model Number that is stored in the main microprocessor memory
• UNIT CONTROL: Engine and Electric Operation: Shutdown and alarm.
• RESET CONDITION: Auto reset only when a valid Model number is entered.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Model Number
a. Check Model # in microprocessor.
b. Enter correct Model Number. Check Model Number on Nameplate. Select the correct model num-
ber in the “MODEL NUMBER” Configuration. If correct model number is not found, Install (or have
Carrier Transicold dealer install) latest software revision.
2.
Reset Microprocessor
a. Place the START/RUN-OFF switch in the OFF position. Disconnect positive battery cable, remove
F7 fuse or unplug 1MM connector, wait 20 seconds and reinstall. Then place the START/RUN-
OFF back in the START/RUN position. The microprocessor powers up OK and the latest setpoint
appears in the display.
b. Check for valid Model number in Unit Data. Valid number is present. Alarm is cleared.
c. Valid model number can not be entered and alarm remains active. Download data and replace the
main microprocessor module (MM). Refer to
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......