8–31
62-11640
b. Checking High Pressure Switch
WARNING
!
Do not use a nitrogen cylinder without a
pressure regulator. Cylinder pressure is
approximately 2350 PSIG (160 bar). Do
not use oxygen in or near a refrigerant
system as an explosion may occur. (See
Figure 8.27 Testing High Pressure Switch
1. Cylinder Valve and Gauge
2. Pressure Regulator
3. Nitrogen Cylinder
4. Pressure Gauge 0 to 500 PSIG (0 to
27.2 bar)
5. Bleed-Off Valve
6. Switch
- - - - -
1. Remove switch as outlined in preceding section.
2. Connect ohmmeter or continuity light across
switch terminals. Ohmmeter will indicate resis-
tance and continuity light will be illuminated if
switch closed after relieving pressure.
3. Connect switch to a cylinder of dry nitrogen.
4. Set nitrogen pressure regulator higher than
open setting for switch being tested. For pres-
sure switch settings refer to
5. Close valve on cylinder and open bleed-off
valve.
6. Open cylinder valve. Slowly close bleed-off
valve and increase pressure until the switch
opens. If light is used, light will go out and if an
ohmmeter is used, the meter will indicate open.
Close cylinder valve. Slowly open bleed-off
valve (to decrease pressure) until switch closes
(light will illuminate or ohmmeter will indicate
open).
8.8.10
Pressure Transducers
The compressor discharge pressure transducer (CDP)
has a range of 0 to 500 PSIG (0 to 34.0 bar) while the
compressor suction pressure transducer (CSP), evapo-
rator outlet pressure transducer (EVOP), and econo-
mizer pressure transducer (ECOP) have a range of -
14.7 to 100 PSIG (-1 to 6.8 bar). When comparing the
transducer reading in Unit Data to the reading on a
manifold gauge, keep in mind the following:
1. The compressor discharge pressure reading in
Unit Data will never read less than 0 bar/psig,
even if it is exposed to a vacuum (such as when
evacuating the system).
2. If the compressor discharge pressure trans-
ducer has lost power or the signal is not return-
ing to the module the reading in Unit Data will
default to 305 to 315 psig (20.75 to 21.43 bar).
Comparisons in this pressure range are not con-
clusive.
3. The compressor suction pressure and evapora-
tor pressure transducers will never read higher
than 100 psig, even if the actual pressure is
higher.
4. If the compressor suction pressure or evapora-
tor pressure transducer has lost power or the
signal is not returning to the module the reading
in Unit Data will default to 55 to 60 psig (3.74 to
4.08 bar). Comparisons in this pressure range
are not conclusive.
Test Transducer Wiring:
1. Verify that the wiring to the transducer is correct.
NOTE
The CDP connector is identified with a red
tape band while the CSP connector is identi-
fied with a blue band.
2. If required, power the transducer circuit by plac-
ing the unit in PC Mode, refer to
Check Voltage to transducer connector. Voltage
reading between connector position 2 (positive)
and position 1 (negative) should be 5.0 VDC.
3. To check the signal wiring, check continuity
between the transducer connector position 3
and the following connector:
CDP = 2MM
−
10, CSP = 2MM
−
9, EVOP =
2MM
−
17
4. If voltage and signal wire are good, replace the
transducer.
Replace a Transducer:
The transducer may be removed by disconnecting the
connector and quickly backing it off the Schrader valve
fitting. Torque replacement transducer 13 to 15 ft/lb
(17.6 to 20.3 Nm).
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......