4–11
62-11640
Figure 4.2 Range Lock Settings - Non Overlapping
The primary time that it is important to determine which
range is to be Range 1 and which is to be Range 2 is
when the ranges overlap each other.
In example 2 (see
), the ranges have been
set to lock all setpoints into Start-Stop, except for a
small range b32° and +42°F (0° and 5.6°C)
where the unit will always operate in Continuous.
Range 1 Minimum Temperature has been set for
+32°F (0°C), and Maximum Temperature of +42°F
(5.6°C). Range 2 has been set for a Minimum Tem-
perature of -22°F (-30°C) and a Maximum Temperature
of +89.6°F (32°C). The unit will switch to Continuous
when the setpoint is b32° and +42°F (0° and
5.6°C) because, when the ranges overlap each other
the Range 1 settings will take priority.
Figure 4.3 Range Lock Settings - Overlapping
Range Lock 1 & 2
Range 2 is set for
0 to -22 F
(-17.8 to -30 C)
Range 1 is set for
28 to 55 F
(-2.2 to +12.8 C)
-30
-23.3
-17.8
-12.2
-6.7
4.4
10.0
15.6
-1.1
21.1
26.7
C
-22
-10
0
10
20
40
50
60
0
7
0
3
80
F
Range 2
Range 1
-30
-23.3
-17.8
-12.2
-6.7
4.4
10.0
15.6
-1.1
21.1
26.7
C
-22
-10
0
10
20
40
50
60
0
7
0
3
80
F
Range 1 always has priority
when Range 1 & 2 overlap
Range 1 is set for 32 to 42 F
(0 to 5.6 C)
Set for Continuous
Range 2 is set for -22 to
89.6 F (-30 to 32 C)
Set for Start-Stop
Range
1
Range 2
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......