Exhibit F Remote setting of Chilled water outlet temp.
Control panel of Chiller
E
732 733
Terminal strips in the control panel
+
-
Input current :
DC 4-20mA
Cooling mode :
+0 to +5
o
C(+9
o
F)
Heating mode :
-0 to -10
o
C(-18
o
F)
(TSA-16DJ only)
Remote setting of chilled water outlet temperature
Ste point of chilled(/hot) water outlet temperature is offset by remote control panel
such as central monitoring panel.
Setting mode
Cooling mode : Set point + Offset dt (below the maximum set point)
Heating mode : Set point - Offset dt (above the minimum set point) (TSA-16DJ only)
1) Should be work the electric wiring connection by license holder.
2) Use steel conduit for electric wiring between field electric supply and chiller control panel.
DC 4 - 20 mA
(Field supply)
+5
+4
Heating mode
(TSA-16DJ only)
-8
0
o
C
-4
-6
-14.4
20mA
Input current
Offset dt
-10
4mA
8mA
12mA
-2
Cooling mode
0
o
F
+9
16mA
+3
+2
+1
-18
+7.2
+5.4
+3.6
+1.8
-3.6
-7.2
-10.8