Performance data (cont)
ARI RATINGS
UNIT
30
CAPACITY
INPUT
POWER
(kW)
COOLER FLOW
COOLER
PRESSURE DROP
CONDENSER
FLOW
CONDENSER
PRESSURE DROP
EER
IPLV
Tons
kW
Gpm
L/s
Ft of
Water
kPa
Gpm
L/s
Ft of
Water
kPa
HR070
69.4
244.1
60.1
166.3
10.49
8.6
25.7
208.2
13.14
7.0
20.9
13.9
17.5
HR080
77.2
271.5
68.6
185.1
11.68
10.6
31.7
231.6
14.61
10.2
30.5
13.5
17.1
HR090
85.5
300.7
77.4
204.9
12.93
12.9
38.5
256.5
16.18
9.8
29.3
13.3
17.3
HR100
98.0
344.7
85.4
234.8
14.81
9.0
26.9
294.0
18.55
11.5
34.3
13.8
18.4
HR110
105.0
369.3
93.8
251.6
15.87
10.3
30.8
315.0
19.87
10.8
32.2
13.4
18.3
HR120
112.0
393.9
102.3
268.6
16.95
11.7
34.9
336.0
21.20
10.3
30.8
13.1
18.2
HR140
135.0
474.8
126.0
323.7
20.42
9.4
28.1
405.0
25.55
14.4
43.0
12.9
16.3
HR160
149.8
526.8
141.6
359.2
22.66
11.6
34.6
449.4
28.35
10.4
31.1
12.7
16.4
LEGEND
EER — Energy Efficiency Ratio (Capacity
[Btuh]
4
Input Power [W])
IPLV — Integrated Part-Load Value
Rated in accordance with ARI Standard 590-92.
NOTES:
1. Rated in accordance with ARI Standard 590-92 at standard rating
conditions.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving water temperature:
44 F (6.7 C)
Entering water temperature:
54 F (12.2 C)
Condenser Conditions:
Entering water temperature:
85 F (29.4 C)
Flow:
3 gpm per ton (0.054 L/s per kW)
Fouling Factor (Cooler and Condenser):
0.00025 hr-sq ft-F per Btuh
(0.000044 m
2
x C per W)
3. IPLV is a single number part-load efficiency value calculated from
100, 75, 50, and 25% system full-load efficiency values and corrected
for a typical building air-conditioning application.
4. All data in this table is certified in accordance with ARI Standard 590-92
as represented in the Reciprocating Chiller Selection Program (E-
Cat) version 2.13.