Physical data — English (cont)
COOLER
30HR,HS SIZE
070,080,090
100,110,120
140,160
COOLER PART NO. 10HA401---
664
684
704
DIMENSIONS
OD (ft-in.)
1-
3
⁄
4
1- 4
1-4
Length (ft-in.)*
6-9
6-11
9-0
NET FLUID VOLUME (gal.)†
21.7
40.4
52.4
REFRIGERANT CIRCUITS
2
2
2
MAXIMUM DESIGN WORKING
PRESSURE (psig)
Refrigerant Side
235
235
235
Fluid (Shell) Side
300
300
300
FLUID CONN. (in.)
Inlet and Outlet
4**
5**
6**
Drain
3
⁄
4
FPT
3
⁄
4
MPT
3
⁄
4
MPT
*Between tube sheets.
†Includes nozzles.
**Victaulic-type water connections.
CONDENSER
CONDENSER PART NO. 09RP---
033
043
054
070
084
DIMENSIONS
OD (in.)
10
3
⁄
4
12
3
⁄
4
12
3
⁄
4
12
3
⁄
4
14
Length (in.)*
67
1
⁄
2
77
83
3
⁄
8
95
1
⁄
4
83
NET FLUID VOLUME (gal.)
5.7
8.5
9.9
11.4
13.7
FLUID CONN. — in. diameter†
Inlet IPS**
2
1
⁄
2
3
3
3
2
1
⁄
2
††
Outlet IPS**
2
1
⁄
2
3
3
3
4
FLUID PASSES
3
3
3
3
3 or 6
MAXIMUM DESIGN WORKING
Refrigerant Side — 385
PRESSURE (psig)
Fluid Side — 250
LEGEND
IPS — Iron Pipe Size
OD — Outside Diameter
*Between tube sheets.
†On part no. 084 condensers, data is for 3-pass only. For 6-pass, inlet and outlet connections are 2
1
⁄
2
inches.
**Field welded (flange with weld stub provided for all connections).
††The 09RP084 has 2 inlet connections.
NOTES:
1. The 2
1
⁄
2
-in. and 3-in. condenser connections are equipped with slip-on flanges bolted to the condensers and
designed for field welding of field-supplied 2
1
⁄
2
-in. and 3-in. schedule 40 pipe.
The 4-in. condenser connections are equipped with welding neck flanges bolted to the condensers and designed
for field welding of field-supplied 4-in. schedule 40 pipe.
2. Standard 30HR,HS160 unit is supplied with 3-pass condensers. To convert from 3 to 6 pass, proceed as follows:
a. Remove 4-in. outlet flanges.
b. Cover 4-in. (09RP084) 3-pass condenser water outlets with blind flanges (field supplied).
3. Water outlet and inlet connections are rated according to ANSI/ASME B 16.5 (American National Standards
Institute/American Society of Mechanical Engineers) latest revision.
6