background image

30

12 - OPTIONS 

Options

No.

Description

Advantages

Use for 30XW 

range

Medium-temperature brine 

solution

5

Implementation of new control algorithms and redesigned 

evaporator to allow chilled brine solution production down to -6°C 

when ethylene glycol is used (-3°C with propylene glycol)

Covers specific applications such as ice storage and 

industrial processes

Only sizes 

512/562/1012/1154

Low-temperature brine solution

6

Implementation of new control algorithms and redesigned 

evaporator to allow chilled brine solution production down to -12°C 

when ethylene glycol is used (-8°C with propylene glycol)

Covers specific applications such as ice storage and 

industrial processes

Only sizes 

512/562/1012/1154

Light-brine solution, down to 

-3°C

8

Implementation of new control algorithms and redesigned 

evaporator to allow chilled brine solution production down to -3°C 

when ethylene glycol is used (0°C with propylene glycol)

Matches with most application requirements for 

ground-sourced heat pumps and fits with many 

industrial processes requirements

254-1762

Unit supplied in two assembled 

parts

51

The unit is equipped with flanges that allow disassembly of the unit 

on site

Facilitates installation in plant rooms with limited access Only sizes 

1612/1652/1702/1762

Master/slave operation

58

Unit equipped with supplementary water outlet temperature sensor 

kit (to be field installed) allowing master/slave operation of two 

units connected in parallel

Optimised operation of two units connected in parrallel 

operation with operating time equalisation

254-1762

Single power connection point

81

Unit power connection via one main supply connection

Quick and easy installation

1002-1762

No disconnect switch 

82A

Unit without disconnect switch, but with short-circuit protection 

device

Permits an external electrical disconnect system for the 

unit (field-supplied), while ensuring unit short circuit 

protection

254-1762

Evap. single pump power/control 

circuit

84

Unit equipped with an electrical power and control circuit for one 

pump evaporator side

Quick and easy installation: the control of fixed speed 

pumps is embedded in the unit control 

254-1252, 1314

Evap. dual pumps power/control 

circuit

84D

Unit equipped with an electrical power and control circuit for two 

pumps evaporator side

Quick and easy installation: the control of fixed speed 

pumps is embedded in the unit control 

254-1252, 1314

Cond. single pump power/control 

circuit

84R

Unit equipped with an electrical power and control circuit for one 

pump condenser side

Quick and easy installation: the control of fixed speed 

pumps is embedded in the unit control 

254-1252, 1314

Condenser insulation

86

Thermal condenser insulation

Minimizes thermal dispersions condenser side (key 

option for heat pump or heat recovery applications)

254-1762

Service valve set

92

Liquid line valve (evaporator inlet) and compressor suction line 

valve

Allow isolation of various refrigerant circuit components 

for simplified service and maintenance

254-1762

Evaporator with one pass less

100C

Evaporator with one pass on the water side. Evaporator inlet and 

outlet on opposite sides. 

Easy to install, depending on site. Reduced pressure 

drops

254-1762

Condenser with one pass less

102C

Condenser with one pass on the water side. Condenser inlet and 

outlet on opposite sides. 

Easy to install, depending on site. Reduced pressure 

drops

254-1762

21 bar evaporator

104

Reinforced evaporator for extension of the maximum water-side 

service pressure to 21 bar (standard 10 bar)

Covers applications with a high water column evaporator 

side (typically high buildings)

254-1762

21 bar condenser

104A Reinforced condenser for extension of the maximum water-side 

service pressure to 21 bar (standard 10 bar)

Covers applications with a high water column condenser 

side (typically high buildings)

254-1762

Reversed evaporator water 

connections

107

Evaporator with reversed water inlet/outlet

Easy installation on sites with specific requirements

254-1762

Reversed condenser water 

connections

107A

Condenser with reversed water inlet/outlet

Easy installation on sites with specific requirements

254-1762

J-Bus gateway

148B

Bi-directional communication board complying with JBus protocol Connects the unit by communication bus to a building 

management system 

254-1762

Lon gateway

148D

Bi-directional communication board complying with Lon Talk 

protocol

Connects the unit by communication bus to a building 

management system 

254-1762

Bacnet over IP

149

Bi-directional high-speed communication using BACnet protocol 

over Ethernet network (IP)

Easy and high-speed connection by ethernet line to a 

building management system. Allows access to multiple 

unit parameters

254-1762

High condensing temperature

150

Optimized compressor for operation at high condensing 

temperature

Increased condenser leaving water temperature up to 

63°C. Allows applications with high condensing 

temperature (heat pumps, installations with not 

generously sized dry-coolers or more generally, 

installations with dry-coolers in hot climate). NOTE: to 

ensure control of the condenser leaving water 

temperature, this option must be fitted on the units. 

30XWH- / XW-P / 

XWHP 254-1762 & 

30XW--0254/0304/354

Condensing temperature 

limitation

150B Limitation of the maximum condenser leaving water temperature to 

45°C

Reduced maximum power input and current absorption: 

power cables and protection elements can therefore be 

downsized

254-1762

Control for low cond. 

temperature

152

Output signal (0-10 V) to control the condenser water inlet valve

Simple installation: for applications with cold water at 

condenser inlet (ex. ground-source, groundwater-

source, superficial water-source applications) the signal 

permits to control a 2 or 3-way valve to maintain 

condenser water temperature (and so condensing 

pressure) at acceptable values  

254-1762

Energy Management Module 

156

EMM Control board with additional inputs/outputs. See Energy 

Management Module option chapter

Extended remote control capabilities (Set-point reset, 

ice storage end, demand limits, boiler on/off 

command...)

254-1762

 7" user interface 

158A Control supplied with a 7 inch colour touch screen user interface

Enhanced ease of use.

254-1762

Input contact for Refrigerant leak 

detection 

159

0-10 V signal to report any refrigerant leakage in the unit directly on 

the controlller (the leak detector itself must be supplied by the 

customer)

Immediate customer notification of refrigerant losses to 

the atmosphere, allowing timely corrective actions

254-1762

Compliance with Swiss 

regulations

197

Additional tests on the water heat exchangers: supply (additional 

of PED documents) supplementary certificates and test 

certifications

Conformance with Swiss regulations

254-1762

Compliance with Australian 

regulations

200

Unit approved to Australian code

Conformance with Australian regulations

254-1762

Low noise level

257

Evaporator sound insulation

3 dB(A) quiter than standard unit

254-1762

Welded evaporator connection 

kit

266

Victaulic piping connections with welded joints

Easy installation

254-1762

Welded condenser water 

connection kit

267

Victaulic piping connections with welded joints

Easy installation

254-1762

Flanged evaporator water 

connection kit

268

Victaulic piping connections with flanged joints

Easy installation

254-1762

Flanged condenser water 

connection kit

269

Victaulic piping connections with flanged joints

Easy installation

254-1762

Thermal compressor insulation

271

The compressor is covered with a thermal insulation layer

Prevents air humidity to condensate on the compressor 

surface

254-1762

230V electrical plug

284

230V AC power supply source provided with plug socket and 

transformer (180 VA, 0,8 Amps)

Permits connection of a laptop or an electrical device 

during unit commissioning or servicing

254-1762

Carrier Connect link (only 

European distribution 

companies)

298

3G router board NOTE 1: require option 149

 

NOTE 2: when more than one machine is installed on site, only 

one of them shall be equipped with option 298 while all of them 

must be equipped with option 149 NOTE 3: if the Carrier® 

PlantCTRL™  is on site, option 298 shall be integrated in the 

Carrier® PlantCTRL™ while option 149 is still mandatory for each 

single unit. 

Enabler for Carrier Connect service offer

254-1762

Summary of Contents for 30XW

Page 1: ...A N D M A I N T E N A N C E I N S T R U C T I O N S Water Cooled Screw Chillers Water sourced screw heat pumps 30XW 30XW P A 30XWH 30XWHP A Original instructions Nominal cooling capacity 273 1756 kW Nominal heating capacity 317 1989 kW 50 Hz ...

Page 2: ...nect switch 16 5 4 Recommended wire sections 16 5 5 Power cable entry 17 5 6 Field control wiring 17 5 7 24 and 230 V power reserve for the user 18 6 APPLICATION DATA 18 6 1 Operating limits for 30XW units 18 6 2 Minimum chilled water flow 18 6 3 Maximum chilled water flow 18 6 4 Condenser water flow rate 18 6 5 Standard and optional number of water passes 19 6 6 Evaporator and condenser water flo...

Page 3: ... 5 and 6 26 10 2 Electrical data units with options 5 and 6 27 10 3 Dimensions clearances units with option 5 and 6 27 10 4 Operating range units with options 5 and 6 27 10 5 Minimum recommended evaporator flow rate with options 5 and 6 27 10 6 Nominal evaporator pressure drop with options 5 and 6 27 11 MAJOR SYSTEM COMPONENTS AND OPERATION DATA 28 11 1 Direct drive twin screw compressor with vari...

Page 4: ... in the right place and direction on the unit The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings or lifting beams with the correct capacity and always follow the lifting instructions on the certified drawings supplied with the unit Do not tilt the unit more than 15 Safety is only guaranteed if these instructions are carefully followed If...

Page 5: ...ation as accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation or explosions Inhalation of high concentrations of vapour is harmful and may cause heart irregularities unconsciousness or death Vapour is heavier than air and reduces the amount of oxygen available for breathing These products cause eye and skin irritation Decomposition products are hazardous 1 2 ...

Page 6: ...lock the power supply circuit in the open position ahead of the machine If the work is interrupted always ensure that all circuits are still deenergized before resuming the work ATTENTION Even if the unit has been switched off the power circuit remains energized unless the unit or circuit disconnect switch is open Refer to the wiring diagram for further details Attach appropriate safety labels Ope...

Page 7: ...nders to a place designated for their recovery Do not incinerate ATTENTION Only use refrigerant R134a in accordance with 700 AHRI Air conditioning Heating and Refrige ration Institute The use of any other refrigerant may expose users and operators to unexpected risks If the refrigerant circuit remains open for longer than a day after an intervention such as a component replacement the openings mus...

Page 8: ...tion any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not install relief valves in series or backwards ATTENTION No part of the unit must be used as a walk way rack or support Periodically check and repair or if necessary replace any component or piping that shows signs of damage The...

Page 9: ...agrams During the installation test national regulations must be followed If no national regulation exists standard EN 378 can be used as a guide External visual installation checks Ensure that the machine is charged with refrigerant Verify on the unit nameplate that the fluid being transported is R 134a and is not nitrogen Compare the complete installation with the refrigeration system and power ...

Page 10: ...44 3059 168 3 168 3 2800 702 1848 968 1044 3059 168 3 168 3 2800 802 1848 968 1044 3059 168 3 168 3 2800 852 1898 828 1044 2780 219 1 168 3 2600 High efficiency units 30XW P 30XWHP 512 1743 968 936 3059 168 3 168 3 2800 562 1743 968 936 3059 168 3 168 3 2800 712 1950 1083 1065 3290 219 1 219 1 3100 812 1950 1083 1070 3290 219 1 219 1 3100 862 1950 1083 1070 3290 219 1 219 1 3100 Standard efficienc...

Page 11: ...1252 2051 1512 1162 4730 219 1 219 1 4500 1352 2051 1512 1162 4730 219 1 219 1 4500 1452 2051 1512 1162 4730 219 1 219 1 4500 1552 2051 1512 1162 4730 219 1 219 1 4500 High efficiency units 30XW P 30XWHP 1012 1997 1512 1039 4730 219 1 219 1 4500 1162 1997 1512 1039 4730 219 1 219 1 4500 1314 2051 1512 1162 4730 219 1 219 1 4500 1464 2051 1512 1162 4730 219 1 219 1 4500 Standard efficiency units 30...

Page 12: ...for maintenance Recommended space for tube removal Water inlet Water outlet Power supply connection Dimensions in mm A B C D E F G Standard efficiency units 30XW 30XWH 1652 1515 1568 1902 4790 219 1 219 1 4500 1702 1515 1568 1902 4790 219 1 219 1 4500 High efficiency units 30XW P 30XWHP 1612 1562 1591 2129 4832 273 1 273 1 4600 1762 1562 1591 2129 4832 273 1 273 1 4600 Standard efficiency units 30...

Page 13: ...3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Max water side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 High efficiency units 30XW P 30XWHP 512 562 712 812 862 1012 1162 1314 1464 1612 1762 Sound levels standard unit Sound power level 1 dB A 99 99 99 99 99 102 102 102 102 102 102 Sound pressure level at 1 m 2 dB ...

Page 14: ...4 490 556 580 650 615 650 High efficiency units 30XW P 30XWHP 512 562 712 812 862 1012 1162 1314 1464 1612 1762 Power circuit Nominal power supply V ph Hz 400 3 50 Voltage range V 360 440 Control circuit 24 V via the built in transformer Nominal start up current Circuit A A 414 414 587 587 587 414 414 587 587 587 587 Circuit B A 414 414 414 587 587 587 Option 81 A 556 574 747 780 801 819 Maximum s...

Page 15: ...56 224 388 1210 0 81 0 88 06TUA483 162 275 215 300 587 1828 0 85 0 91 06TUA554 171 300 234 330 587 1828 0 85 0 91 06TVA680 210 400 312 419 629 1919 0 85 0 90 06TVA753 230 430 335 455 629 1919 0 86 0 90 06TVA819 250 460 359 476 629 1919 0 87 0 90 Value at standard Eurovent conditions evaporator entering leaving water temperature 12 C 7 C condenser entering leaving water temperature 30 C 35 C Value ...

Page 16: ...switches The control box includes the following standard features One main disconnect switch per circuit Starter and motor protection devices for each compressor Anti short cycle protection devices Control devices Field connections All connections to the system and the electrical installations must be in full accordance with all applicable codes The Carrier 30XW units are designed and built to ens...

Page 17: ...5 200 200 XLPE Cu 1 x 240 1 x 240 400 400 PVC Cu 1012 2 x 240 2 x 240 1 x 120 1 x 95 230 200 XLPE Cu 1 x 240 1 x 240 400 401 PVC Cu 1052 1154 1162 2 x 240 2 x 240 1 x 120 1 x 120 220 220 XLPE Cu 2 x 120 2 x 120 375 375 PVC Cu 1252 1314 2 x 240 2 x 240 1 x 150 1 x 120 220 220 XLPE Cu 2 x 185 2 x 120 410 375 PVC Cu 1352 1464 2 x 240 2 x 240 1 x 150 1 x 150 220 220 XLPE Cu 2 x 185 2 x 185 410 410 PVC...

Page 18: ...ld control wiring Unit without option 084 2 A 24 V a c or 48 VA Unit with option 084 1 3 A 24 V a c or 30 VA 084 or 084R or 084D As an option a the 230 V 50 Hz circuit allows the supply of a battery charger for a portable computer at 1 A maximum at 230 V The connection is via a CEE7 7 type socket 2 poles with earth located under the control box and accessible from outside 6 APPLICATION DATA 6 1 Op...

Page 19: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Condenser Standard 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Option 102C 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 High efficiency units 30XW P Size 512 562 712 812 862 1012 1162 1314 1464 1612 1762 Evaporator Standard 2 2 2 2 2 2 2 2 2 2 2 Option 100C 1 1 1 1 1 1 1 1 1 1 1 Condenser Standard 2 2 2 2 2 2 2 2 2 2 2 Option 102C 1 1 1 1 1 1 1 1 1 1 1 6 6 Evaporator and c...

Page 20: ...1 12 10 20 30 40 50 60 70 80 90 100 110 120 0 10 20 30 40 50 60 70 80 90 100 110 120 1 2 3 4 9 12 11 10 7 8 5 6 3 6 9 12 15 18 21 24 27 30 33 36 0 10 20 30 40 50 60 70 80 90 100 110 1 2 3 4 5 6 7 8 9 12 11 10 Legend 1 254 2 304 3 354 4 402 452 552 602 5 512 562 6 652 702 802 7 852 8 1002 1052 9 1154 10 712 812 862 11 1012 1162 12 1252 1352 1452 1552 13 1314 1464 14 1652 1702 15 1612 1762 Legend 1 ...

Page 21: ...regard to the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping could generate eletrolytic pairs and consequently corrosion Verify then the need to install sacrificial anodes In case additives or other fluids than those recommend ed by Carrier are used ens...

Page 22: ...6 6 6 6 8 8 8 8 8 8 8 Actual outside diameter mm 141 3 141 3 141 3 141 3 141 3 141 3 141 3 168 3 168 3 168 3 168 3 168 3 168 3 219 1 219 1 219 1 219 1 219 1 219 1 219 1 Option 100C Nominal diameter in 5 5 5 6 6 6 6 6 6 6 6 6 6 8 8 8 8 8 8 8 Actual outside diameter mm 141 3 141 3 141 3 168 3 168 3 168 3 168 3 168 3 168 3 168 3 168 3 168 3 168 3 219 1 219 1 219 1 219 1 219 1 219 1 219 1 Condenser Un...

Page 23: ...pening and closing by the control of each unit in this case the valves are controlled using the dedicated water pump outputs See the 30XA 30XW Pro Dialog Control IOM for a more detailed explanation 30XW with configuration leaving water control 8 HEAT MACHINE UNITS 30XWH AND 30XWHP 8 1 Physical data for Heat Machine units The physical data for the Heat Machine units 30XWH 30XWHP are the same as for...

Page 24: ...8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Max water side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 High efficiency units option 150 30XW P 30XWHP 512 562 712 812 862 1012 1162 1314 1464 1612 1762 Sound levels unit with option 150 Sound power level 1 dB A 99 99 102 102 102 102 102 105 105 105 105 Sound pressure level at 1 m 2 ...

Page 25: ...HP 512 562 712 812 862 1012 1162 1314 1464 1612 1762 Power circuit Nominal power supply V ph Hz 400 3 50 Voltage range V 360 440 Control circuit 24 V via the built in transformer Nominal start up current Circuit A A 587 587 772 772 772 587 587 772 772 772 772 Circuit B A 587 587 587 772 772 772 Option 81 A 749 757 943 965 986 1004 Maximum start up current Circuit A A 587 587 772 772 772 587 587 77...

Page 26: ...start up 35 0 C Leaving temperature during operation 3 3 C 1 15 0 C Entering leaving temperature difference at full load 2 8 K 11 1 K Condenser Entering temperature at start up 13 0 C 2 Leaving temperature during operation 23 0 C 2 63 0 C Entering leaving temperature difference at full load 2 8 K 11 1 K 1 For low temperature applications where the leaving water temperature is below 3 3 C a frost p...

Page 27: ...d but performances are not optimised Full load with option 5 6 and ethylene or propylene glycol Part load limit approx 80 Part load limit approx 50 Part load limit approx 30 EG 5 PG 5 EG 6 PG 6 10 5 Minimum recommended evaporator flow rate with options 5 and 6 Option 5 medium temperature Option 6 low temperature Reference number P0512 P0562 P1012 1154 P0512 P0562 P1012 1154 Minimum evaporator flow...

Page 28: ...water connection of the heat exchanger is a Victaulic connection The products that may be added for thermal insulation of the containers during the water piping connection procedure must be chemically neutral in relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier 11 MAJOR SYSTEM COMPONENTS AND OPERATION DATA 11 1 Di...

Page 29: ...vaporator via the principal EXV This permits increasing the cooling capacity of the system as well as its efficiency 11 3 High pressure safety switch 30XW units are equipped with high pressure safety switches In accordance with the applicable code the high pressure switches with manual reset called PZH former DBK may be backed up by high pressure switches that require resetting with a tool The hig...

Page 30: ...nser with reversed water inlet outlet Easy installation on sites with specific requirements 254 1762 J Bus gateway 148B Bi directional communication board complying with JBus protocol Connects the unit by communication bus to a building management system 254 1762 Lon gateway 148D Bi directional communication board complying with Lon Talk protocol Connects the unit by communication bus to a buildin...

Page 31: ...C 25 Tunnel terminal screw water pump disconnect Disconnect switch 3RV101 QM90 2 5 Disconnect switch 3RV102 QM90 2 5 Disconnect switch 3RV103 QM90 4 Tunnel terminal screw water pump contactor Contactor 3RT102 KM90 2 5 Contactor 3RT103 KM90 4 13 STANDARD MAINTENANCE Air conditioning equipment must be maintained by profes sional technicians whilst routine checks can be carried out locally by special...

Page 32: ... bar The pressure drop across the filter can be determined by measuring the pressure at the discharge port at the oil separator and the oil pressure port at the compressor The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop across the check valve and solenoid valve is approximately 0 4 bar which should be subtracted fro...

Page 33: ...the compressor a low pressure switch is included with the compressor This low pressure switch should be temporarily installed as a hard safety on the high pressure part of the compressor The purpose of this switch is to protect the compressor against any wiring errors at the compressor terminal pin The electrical contact of the switch would be wired in series with the high pressure switch The swit...

Page 34: ... Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is connected properly All air has been vented from the chilled water circuit The unit is switched off again after the pump test has been completed C...

Page 35: ...s nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if required litres of Piping includes electric heater tape if exposed to temperatures below 0 C Inlet piping to cooler includes a 20 mesh strainer with a mesh size of 1 2 mm Check press...

Page 36: ...des order No 13458 03 2017 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www eurovent certification com www certiflash com ...