background image

17

INDOOR-AIR QUALITY SENSOR INSTALLATION —
The indoor-air quality (IAQ) sensor accessory monitors carbon
dioxide levels. This information is used to increase the airflow
to the zone and may also modify the position of the outdoor-air
dampers to admit more outdoor air as required to provide the
desired ventilation rate. The wall sensor is used to monitor the
conditioned space. The sensor uses infrared technology to
measure the levels of CO

2

present in the air. The wall sensor is

available with or without an LCD readout to display the CO

2

level in ppm and is also available in a combination model
which senses both temperature and CO

2

level.

The CO

2

sensors are factory set for a range of 0 to

2000 ppm and a linear voltage output of 0 to 10 vdc. Refer to
the instructions supplied with the CO

2

sensor for electrical re-

quirements and terminal locations. The sensor requires a sepa-
rate field-supplied 24 vac 25 va transformer to provide power
to the sensor. The transformer may be mounted in the control
box if space is provided (except electric heat units).

For factory configuration changes to some models of the

sensor, the User Interface Program (UIP) or Sensor Calibration
Service Kit is required.

To accurately monitor the quality of the air in the condi-

tioned air space, locate the sensor near the return air grille so it
senses the concentration of CO

2

leaving the space. The sensor

should be mounted in a location to avoid direct breath contact.

Do not mount the space sensor in drafty areas such as near

supply diffusers, open window, fans, or over heat sources. Al-
low at least 3 ft between the sensor and any corner. Avoid
mounting the sensor where it is influenced by the supply air;
the sensor gives inaccurate readings if the supply air is blown
directly onto the sensor.

To mount the sensor, refer to the installation instructions

shipped with the accessory kit.
INDOOR AIR QUALITY SENSOR WIRING — To wire the
sensor after it is mounted in the conditioned air space, see
Fig. 23-25 and the instructions shipped with the sensor. Use
two 2-conductor 20 American Wire Gage (AWG) twisted-pair
cables (see Table 7) to connect the field-supplied separate iso-
lated 24 vac power source to the sensor and to connect the sen-
sor to the control terminals. To connect the sensor to the
control, identify the positive (+) and ground (GND) terminals
on the sensor and connect the positive terminal to the RH/IAQ
terminal on the control and connect the ground terminal to
terminal GND.
HUMIDITY

SENSOR

(Wall-Mounted)

INSTALLA-

TION — The accessory space humidity sensor is field sup-
plied and installed on an interior wall to measure the relative
humidity of the air within the occupied space. See Fig. 26.

The use of a standard 2 x 4-in. electrical box to accommo-

date the wiring is recommended for installation. The sensor can
be mounted directly on the wall, if acceptable by local codes.

If the sensor is installed directly on a wall surface, install the

humidity sensor using 2 screws and 2 hollow wall anchors
(field-supplied);

do not overtighten screws

.

The sensor must be mounted vertically on the wall. The

Carrier logo should be oriented correctly when the sensor is
properly mounted.

Do NOT clean or touch the sensing element with chemical
solvents; they can permanently damage the sensor.

Fig. 24 — Ventilation Rates Based on

CO

2

Set Point

Fig. 23 — Indoor Air Quality Sensor

(Wall-Mounted Version Shown) 33ZCSENCO2

Fig. 22 — Primary Air Temperature

Sensor Installation

(Air-Handling Unit Discharge Locations)

Summary of Contents for 35E

Page 1: ... ADJUSTMENT SLIDEBAR WIRING THE CCN NETWORK COMMUNICATION SERVICE JACK PRIMARY AIR TEMPERATURE SENSOR INSTALLATION INDOOR AIR QUALITY SENSOR INSTALLATION INDOOR AIR QUALITY SENSOR WIRING HUMIDITY SENSOR Wall Mounted INSTALLATION Connect the CCN Communication Bus 19 COMMUNICATION BUS WIRE SPECIFICATIONS CONNECTION TO THE COMMUNICATION BUS Water Valve Installation 19 ComfortID Start Up 19 GENERAL PR...

Page 2: ...ls or controls File damage claim immediately with transportation agency and notify Carrier UNIT IDENTIFICATION Each unit is supplied with a shipping label and an identification label Fig 2 INSTALLATION PRECAUTION Check that construction debris does not enter unit or ductwork Do not operate the central station air handling fan without final or construction filters in place Accumulated dust and cons...

Page 3: ...urn tracking 4149 Proportional floating hot water with supply return tracking 4150 Return air damper CCN Thermostats Ordered Separately Thermostat 33ZCT56SPT RT room temperature sensor with set point adjust and override Thermostat 33ZCT55SPT RT room temperature sensor with override only Thermostat 33ZCT58SPT Communicating room tempera ture sensor with LCD liquid crystal diode set point adjust fan ...

Page 4: ...ion area Remove unit from ship ping package Do not handle by controls or damper extension rod 2 The unit has factory installed brackets on unit as shown in Fig 3 3 Suspend units from building structure with straps rods or hanger wires Secure the unit and level it in each direc tion Note that reheat coil is in heavy end of unit Step 2 Make Duct Connections 1 Install supply ductwork on unit inlet co...

Page 5: ...04 0 35 675 13 0 21 0 09 0 27 0 44 0 60 0 76 0 09 925 13 0 39 0 17 0 51 0 82 1 13 1 43 0 17 240 240 or 0 240 4 9 0 02 0 01 0 02 0 03 0 04 0 05 0 01 9 550 11 3 0 08 0 07 0 12 0 17 0 22 0 27 0 07 0 44 875 16 0 21 0 17 0 31 0 44 0 57 0 69 0 17 1200 16 0 40 0 32 0 59 0 83 1 07 1 31 0 32 300 290 or 0 300 6 2 0 02 0 01 0 02 0 04 0 05 0 07 0 01 10 675 13 9 0 08 0 04 0 12 0 20 0 27 0 35 0 04 0 55 1075 21 ...

Page 6: ...is typical of 480V 3 phase 4 wire heater and control Refer to actual unit wiring diagram AFS Airflow Switch DDC Direct Digital Controls Fig 5 Typical Power Connections for 35E Units with 3 Stage Electric Heat ANALOG OR DDC CONTROLLER 24VAC BLU YEL CLASS II TRANSFORMER OPTIONAL 120VAC 208VAC 240VAC 277VAC L1 GROUND 24 VAC POWER LEGEND NOTE Drawing is typical refer to actual unit wiring diagram for ...

Page 7: ...s will provide a permanent record of the balanc ing information installation location information box size cooling minimum airflow cfm limit cooling maximum airflow cfm limit reheat cfm limit if applicable heating minimum airflow cfm limit if applicable heating maximum airflow cfm limit if applicable calibration gain after balancing set points PNEUMATIC CONTROLS Preparation for Balancing Control S...

Page 8: ...______ ENGINEER ______________________________________________ BUILDING LOCATION FLOOR ______________________________ BUS NUMBER ___________________________________________ Fig 7 Air Terminal Performance Sheet CONTROL SET POINTS Tag Number Zone Address Box Size in cfm Cooling cfm Reheat cfm Heating cfm Heat kW Occupied Unoccupied Calibration Gain min max min max Type Btu min max min max mult ...

Page 9: ...DAMPER Control Sequence 1103 Refer to Fig 9 1 Maximum volume setting a Disconnect the thermostat line from the velocity controller b Adjust the maximum volume control knob marked HI and located in the center of the con troller to achieve the required minimum flow To determine the required pressure differential refer to Tables 2 and 5 and the Linear Averaging Probe Chart provided on the side of the...

Page 10: ... initial adjustments are made cycle the thermostat pressure a few times to settle the internal reset mechanisms and verify set tings Fine tune the settings if necessary The thermostat pres sure may be left at a high pressure and the G port cap may be removed and replaced to cycle the reset mechanism RESET START setting is factory set at 8 0 psig This is the lowest thermostat pressure that the LO S...

Page 11: ... heating set point slider all the way to the right for maximum heating 5 Read the DC voltage across the meter taps on the heating left side Adjust the maximum set point MAX INCR potentiometer clockwise to increase or counterclockwise to decrease to the DC voltage equal to the desired air flow cfm as shown on the calibration curve Fig 14 NOTE The maximum set point must be adjusted last Adjust ment ...

Page 12: ...adjusted first Adjust ment of the MIN INCR potentiometer directly affects the max imum set point and auxiliary set point 2 Adjustment of auxiliary set point if required Read the DC voltage across the meter taps on the heating left side Adjust the MAX AUX INCR potentiometer clockwise to increase or counterclockwise to decrease to the DC voltage equal to the desired airflow cfm 3 Return the cooling ...

Page 13: ... and 2 of connector J1 Refer to unit wire label diagram for minimum size VA and grounding requirements for each unit SUPPLY AIR TEMPERATURE SAT SENSOR INSTAL LATION On terminals with heat the SAT sensor is provid ed The sensor is factory wired to the controller and shipped in the control box The SAT must be field installed in the duct downstream from the air terminal The SAT sensor part num ber is...

Page 14: ... connection will be made If connection is desired the CCN communication cable should be available at time of sensor installation for convenient wiring connections The cable selected must meet the requirements for the entire network See Connect the CCN Communication Bus section for CCN communication cable specifications RESISTANCE Ohms TEMP F RESISTANCE Ohms TEMP F RESISTANCE Ohms TEMP F RESISTANCE...

Page 15: ...inches Fig 18 Space Temperature Sensor and Wall Mounted Humidity Sensor Mounting 2 3 4 5 6 1 SW1 SEN BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING Fig 19 Space Temperature Sensor Wiring 33ZCT55SPT 2 3 4 5 6 1 SW1 SEN SET Cool Warm WHT T56 BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING JUMPER TERMINALS AS SHOWN Fig 20 Space Temperature Sensor Wiring 33ZCT56SPT ...

Page 16: ...he sensor end of the cable 3 Connect the sensor cable as follows a Connect one wire from the cable RED to the SPT terminal on the controller Connect the other end of the wire to the left terminal on the SEN ter minal block of the sensor b Connect another wire from the cable BLACK to the ground terminal on the controller Connect the other end of the wire to the remaining open termi nal on the SEN t...

Page 17: ... the sensor where it is influenced by the supply air the sensor gives inaccurate readings if the supply air is blown directly onto the sensor To mount the sensor refer to the installation instructions shipped with the accessory kit INDOOR AIR QUALITY SENSOR WIRING To wire the sensor after it is mounted in the conditioned air space see Fig 23 25 and the instructions shipped with the sensor Use two ...

Page 18: ...he center of the sensor 2 Connect the RED wire to the sensor screw terminal marked 3 Install one lead from the resistor supplied with the sen sor and the WHITE wire into the sensor screw terminal marked After tightening the screw terminal test the connection by pulling gently on the resistor lead 4 Connect the remaining lead from the resistor to the BLACK wire and secure using a field supplied clo...

Page 19: ...nal zone controllers in a daisy chain fashion following the color coded wiring scheme in Table 9 NOTE The communication bus drain wires shield must be tied together at each zone controller If the communica tion bus is entirely within one building the resulting contin uous shield must be connected to ground at only one single point If the communication bus cable exits from one build ing and enters ...

Page 20: ...s a portable device to change system set up and set points from a zone sensor or ter minal control module During start up the Building Supervisor or the Network Service Tool can also be used to verify commu nication with each controller For specific operating instructions refer to the appropriate user manual See Table 11 for troubleshooting information ComfortID TEST AND BALANCE TOOL SOFT WARE The...

Page 21: ...n electric box mounted horizontally may be used instead of cutting the hole 2 Remove the cover from the thermostat controller Care fully remove the circuit board from the backplate of the thermostat controller Line up the backplate with the hole in the wall Push the protruding part of the backplate into the hole Pull the thermostat controller wires out through the backplate 3 Attach backplate to w...

Page 22: ... board Slide the cir cuit board under the back plate securing bars DO NOT CREASE RIBBON CABLE 7 Align thermostat board with alignment pin Gently pull down on the thermostat latch and press firmly until the circuit board snaps into place 8 If optional locking thermostat cover is purchased insert locking clip on the inside of the thermostat cover Push firmly into place 9 Insert tabs on thermostat co...

Page 23: ...k system Variable Volume and Temperature VVT Product Data literature and the configura tion instructions provided with the thermostat Refer to the specific control sequence 35E 82XX for de tailed operational information This information should be used to test and commission the control Control Start Up GENERAL Air volume delivery to the conditioned space is controlled by the modulating of the prim...

Page 24: ... discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 533 530 Printed in U S A Form 35E 2SI Pg 24 3 06 Replaces 35E 1SI Copyright 2006 Carrier Corporation Book 3 Tab 6a ...

Reviews: