3
Table 2 — Physical Data — 39SV Coil and Filter Data
Table 3 — Physical Data — 39SM Coil and Filter Data
*4 and 6 row hot water coils have the same face area as 4 and 6 row
chilled water coils.
39SV UNIT SIZE
02
03
04
05
07
09
CHILLED WATER
Nominal Capacity at 400 fpm (cfm)
1200
1200
1600
2000
2932
3668
Face Area (sq ft)
3
3
4
5
7.33
9.17
Coil Connection Size (in. OD sweat)
3
/
4
3
/
4
7
/
8
1
1
/
8
1
1
/
8
1
3
/
8
HOT WATER
Nominal Capacity at 400 fpm (cfm)
804
804
964
1276
2292
3124
Face Area (sq ft)
2.01
2.01
2.41
3.19
5.73
7.81
Coil Connection Size (in. OD sweat)
7
/
8
7
/
8
7
/
8
1
1
/
8
1
1
/
8
1
1
/
8
DIRECT EXPANSION
Nominal Capacity at 400 fpm (cfm)
1200
1200
1600
2000
2932
3668
Face Area (sq ft)
3
3
4
5
7.33
9.17
Connection Size (in. OD sweat) (Qty)
Liquid Line
3
/
8
3
/
8
1
/
2
1
/
2
5/8
1
/
2
(2)
Suction Line
3
/
4
3
/
4
7
/
8
1
1
/
8
1
1
/
8
7
/
8
(2)
STEAM
Nominal Capacity at 400 fpm (cfm)
624
624
688
1268
1750
2452
Face Area (sq ft)
1.56
1.56
1.72
3.17
4.375
6.13
FILTER DATA
Size (in.) (Qty)
20x20
20x20
22.5x22.5
16x25 (2)
20x25 (4)
20x25 (4)
Nominal Face Area (sq ft)
2.78
2.78
3.52
5.56
13.89
13.89
39SM UNIT SIZE
04
05
07
09
13
17
CHILLED WATER
Nominal Capacity at 400 fpm (cfm)
1668
2084
2776
3332
5000
7084
Face Area (sq ft)
4.17
5.21
6.94
8.33
12.5
17.71
Coil Connection Size (in. OD sweat)
4 Row (Qty)
7
/
8
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
1
5
/
8
(2)
6 Row (Qty)
1
1
/
8
1
1
/
8
1
3
/
8
1
5
/
8
1
5
/
8
1
5
/
8
(2)
HOT WATER
Nominal Capacity at 400 fpm (cfm)
1668
2084
2776
3332
5000
7084
Face Area (sq ft)
4.17
5.21
6.94
8.33
12.5
17.71
Coil Connection Size (in. OD sweat)
2 Row (Qty)
7
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
(2)
4 Row* (Qty)
7
/
8
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
1
5
/
8
(2)
6 Row* (Qty)
1
1
/
8
1
1
/
8
1
3
/
8
1
5
/
8
1
5
/
8
1
5
/
8
(2)
DIRECT EXPANSION
Nominal Capacity at 400 fpm (cfm)
1668
2000
2668
3332
5000
7000
Face Area (sq ft)
4.17
5
6.67
8.33
12.5
17.5
Connection Size (in. OD sweat)
Liquid Line
1
/
2
1
/
2
5
/
8
5
/
8
5
/
8
5
/
8
(2)
Suction Line
7
/
8
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
1
5
/
8
(2)
STEAM
Nominal Capacity at 400 fpm (cfm)
1492
1960
2472
3028
4752
6700
Face Area (sq ft)
3.73
4.9
6.18
7.57
11.88
16.75
FILTER DATA
Size (in.) (Qty)
20x25 (2)
20x25 (2)
16x25 (4)
16x25 (4)
16x20 (2)
20x20 (2)
16x25 (2)
20x25 (2)
16x20 (2)
20x20 (2)
16x25 (2)
20x25 (2)
Nominal Face Area (sq ft)
6.94
6.94
11.11
11.11
22.5
22.5