background image

31

Following the piping diagrams in Fig. 52-56, make all con-

nections while observing the following precautions:
• Install a drip line and trap on the pressure side of the

inlet control valve. Connect the drip line to the return

line downstream of the return line trap.

• To prevent scale or foreign matter from entering the con-

trol valve and coil, install a 

3

/

32

-in. mesh strainer in the

steam supply line upstream from the control valve.

• Provide air vents for the coils to eliminate noncondens-

able gases.

• Select a control valve according to the steam load, not

the coils supply connection size. Do not use an oversized

control valve.

• Do not use bushings that reduce the size of the header

return connection. The return connection should be the

same size as the return line and reduced only at the

downstream trap.

• To lift condensate above the coil return line into over-

head steam mains, or pressurized mains, install a pump

and receiver between the condensate trap and the

pressurized main. Do not try to lift condensate with

modulating or on-and-off steam control valves. Use only

15-degree check valves, as they open with a lower water

head. Do not use 45-degree or vertical-lift check valves.

• Use float and thermostatic traps. Select the trap size

according to the pressure difference between the steam

supply main and the return main.

• Load variations can be caused by uneven inlet air distri-

bution or temperature stratification.

• Drain condensate out of coils completely at the end of

the heating season to prevent the formation of acid.

Coil Freeze-Up Protection

WATER COILS  — If a chilled water coil is applied with out-

side air, provisions must be made to prevent coil freeze-up.

Install a coil freeze-up thermostat to shut down the system if

any air temperature below 36 F is encountered entering the

water coil. Follow thermostat manufacturer’s instructions.

When a water coil is applied downstream of a direct-

expansion (DX) coil, a freeze-up thermostat must be installed

between the DX and water coil and electrically interlocked to

turn off the cooling to prevent freeze-up of the water coil. 

For outdoor-air application where intermittent chilled water

coil operation is possible, one of the following steps should be

taken:
• Install an auxiliary blower heater in cabinet to maintain

above-freezing temperature around coil while unit is

shut down.

• Drain coils and fill with an ethylene glycol solution suit-

able for the expected cold weather operation. Shut down

the system and drain coils. See Service section, Winter

Shutdown.

STEAM COILS — When used for preheating outdoor air in

pressure or vacuum systems, an immersion thermostat to con-

trol outdoor-air damper and fan motor is recommended. This

control is actuated when steam supply fails or condensate tem-

perature drops below an established level, such as 120 to 150 F.

A vacuum breaker should also be used to equalize coil pressure

with the atmosphere when steam supply throttles close. Steam

should not be modulated when outdoor air is below 40 F.

On low-pressure and vacuum steam-heating systems, the

thermostat may be replaced by a condensate drain with a ther-

mal element. This element opens and drains the coil when con-

densate temperature drops below 165 F. Note that condensate

drains are limited to 5 psig pressure.
INNER DISTRIBUTING TUBE STEAM COILS  —   The

inner distributing tube (IDT) steam coil used in the 39S air-

handling units has an inner tube pierced to facilitate the distri-

bution of the steam along the tube's length. The outer tubes are

expanded into plate fins. The completed assembly includes the

supply and condensate header and side casings which are built

to slant the fin/tube bundle back toward the condensate header.

The slanting of the assembly ensures that condensate will flow

toward the drains. This condensate must be removed through

the return piping to prevent premature failure of the coil. The

fin/tube bundle is slanted vertically for horizontal airflow coils,

and horizontally for vertical airflow coils.
IDT Steam Coil Piping — The following piping guidelines

will contribute to efficient coil operation and long coil life:

1. Use full size coil outlets and return piping to the steam

trap. Do not bush return outlet to the coil. Run full size to

the trap, reduce at the trap.

2. Use float and thermostatic (F & T) traps only for conden-

sate removal. Trap size selection should be based on the

difference in pressure between the steam supply main and

the condensate return main. It is good practice to select a

trap with 3 times the condensate rating of the coil to

which it is connected.

3. Use thermostatic traps for venting only.
4. Use only 

1

/

2

-in., 15-degree swing check valves installed

horizontally, piped open to atmosphere, and located at

least 12 in. above the condensate outlet. Do not use

45-degree, vertical lift and ring check valves.

5. The supply valve must be sized for the maximum antici-

pated steam load.

6. Do not drip steam mains into coil sections. Drip them on

the pressure side of the control valve and trap them into

the return main beyond the trap for the coil.

7. Do not use a single trap for two or more coils installed in

series. Where two or more coils are installed in a single

bank, in parallel, the use of a single trap is permissible,

but only if the load on each coil is equal. Where loads in

the same coil bank vary, best practice is to use a separate

trap for each coil.
Variation in load on different coils in the same bank may

be caused by several factors. Two of the most common

are uneven airflow distribution across the coil and stratifi-

cation of inlet air across the coil.

8. Do not try to lift condensate above the coil return into an

overhead main, or drain into a main under pressure with a

modulating or on/off steam control valves. A pump

and receiver should be installed between the coil conden-

sate traps and overhead mains and return mains under

pressure.

9. Use a strainer (

3

/

32

-in. mesh) on the steam supply side,

as shown in the piping diagrams, to avoid collection of

scale or other foreign matter in the inner tube distributing

orifices.

NOTE: IDT coils must be installed with the tubes draining

toward the header end of the coil. The IDT steam coils are

pitched toward the header end as installed in the unit.

10. Ensure the AHU (air-handling unit) is installed level to

maintain the inherent slope. Also ensure the unit is in-

stalled high enough to allow the piping to be installed cor-

rectly, especially the traps which require long drip legs.

11. Do not fail to provide all coils with the proper air vents to

eliminate noncondensable gasses.

12. Do not support steam piping from the coil units. Both

mains and coil sections should be supported separately.

IDT Steam Coil Installation — Refer to drawings to position

the coils properly with regard to the location of the supply and

return connections. Ensure that the IDT coil is pitched with the

tubes draining toward the header. The AHUs provide proper

coil pitch when the AHU is installed level.

Refer to schematic piping diagrams and piping connection

notes for the recommended piping methods.

Summary of Contents for 39SH

Page 1: ...ERATIONS Air handling equipment is designed to provide safe and reli able service when operated within design specifications To avoid injury to personnel and damage to equipment or property when operating this equipment use good judgment and follow safe practices as outlined below DANGER NEVER enter an enclosed fan cabinet or reach into a unit while the fan is running LOCK OPEN AND TAG the fan mot...

Page 2: ... 09 13 17 CHILLED WATER Nominal Capacity at 400 fpm cfm 632 716 800 1224 1612 2000 2916 3832 5500 7084 Face Area sq ft 1 58 1 79 2 3 06 4 03 5 7 29 9 58 13 75 17 71 Coil Connection Size in OD sweat 4 Row Qty 3 4 3 4 3 4 3 4 7 8 11 8 11 8 13 8 13 8 15 8 2 6 Row Qty 3 4 3 4 3 4 7 8 11 8 11 8 13 8 15 8 15 8 15 8 2 HOT WATER Nominal Capacity at 400 fpm cfm 632 716 624 956 1612 2000 2688 3544 5348 6640...

Page 3: ...x25 2 20x25 4 20x25 4 Nominal Face Area sq ft 2 78 2 78 3 52 5 56 13 89 13 89 39SM UNIT SIZE 04 05 07 09 13 17 CHILLED WATER Nominal Capacity at 400 fpm cfm 1668 2084 2776 3332 5000 7084 Face Area sq ft 4 17 5 21 6 94 8 33 12 5 17 71 Coil Connection Size in OD sweat 4 Row Qty 7 8 11 8 11 8 13 8 13 8 15 8 2 6 Row Qty 11 8 11 8 13 8 15 8 15 8 15 8 2 HOT WATER Nominal Capacity at 400 fpm cfm 1668 208...

Page 4: ...5124 7000 Face Area sq ft 2 3 06 4 03 5 8 13 9 48 12 81 17 5 Connection Size in OD sweat Qty Liquid Line 3 8 3 8 1 2 1 2 5 8 5 8 7 8 2 7 8 2 Suction Line 3 4 3 4 7 8 11 8 11 8 13 8 13 8 2 15 8 2 STEAM Nominal Capacity at 400 fpm cfm 752 1144 1452 1800 3088 3576 4956 6768 Face Area sq ft 1 88 2 86 3 63 4 5 7 72 8 94 12 39 16 92 FILTER DATA Single Wall Unit Throwaway Filter Size in Qty 16x32 16x32 2...

Page 5: ...3 37 1 36 6 18 1 19 0 1 0 14 1 1 0 1 5 1 5 2 9 8 4 10 6 27 6 16 4 04 42 0 45 0 22 1 23 0 1 0 17 9 1 0 1 5 1 5 2 7 9 1 13 8 36 0 20 0 05 42 0 45 0 22 1 23 0 1 0 14 3 1 0 1 5 1 5 2 7 12 5 13 8 36 0 20 0 07 09 52 5 57 0 34 8 34 8 1 0 21 8 9 1 2 8 2 8 2 8 16 2 16 2 48 0 32 2 13 57 5 67 2 43 0 43 0 N A 11 4 8 0 3 7 3 7 3 7 16 4 2 16 4 2 57 9 40 5 17 57 5 72 3 48 0 48 0 N A 14 0 13 0 3 7 3 7 3 7 16 4 2 ...

Page 6: ... 8 0 9 1 1 6 13 9 7 8 7 8 7 8 7 8 1 2 7 8 05 29 5 26 0 59 5 8 4 12 6 1 3 13 9 1 1 8 1 1 8 1 1 8 1 1 8 1 2 1 1 8 CW Chilled Water MSS Motor Start Stop Station DX Direct Expansion w o Without HW Hot Water 4 x 4 J Box w o MSS F G D 12 5 B E 6 3 1 9 Right View 8 2 2 5 875 24V Control Conn 875 OPP SIDE Power Conn Motor Start Stop MSS optional Conn Liquid Conn DX Front View Supply Conn CW Top View Suppl...

Page 7: ...875 CW Chilled Water MSS Motor Start Stop Station DX Direct Expansion w o Without HW Hot Water Motor Start Stop opt 31 00 Iso View w o panels Front View Right View Top View 4 x 4 J Box w o MSS Power Conn 875 20 3 16 3 13 3 875 24V Control Conn 6 3 2 4 34 2 54 0 DX Conn 20 5 2 3 Return CW Liquid 2 0 1 5 Drain Conn Supply Conn HW Supply CW Suction 10 1 84 4 19 5 9 DX Conn Return Conn HW a39 4066 Fig...

Page 8: ... shown in inches 39SV UNIT SIZE WIDTH DEPTH HEIGHT SUPPLY DUCT CONNECTION SIZES OD A B C D E F G CW Supply Return HW Supply Return DX Liquid Suction 02 22 3 24 0 50 0 6 9 8 5 3 0 11 8 3 4 3 4 7 8 7 8 3 8 3 4 03 22 3 24 0 50 0 6 9 8 5 3 0 11 8 3 4 3 4 7 8 7 8 3 8 3 4 04 25 1 24 3 56 5 8 0 9 1 1 6 13 9 7 8 7 8 7 8 7 8 1 2 7 8 05 29 5 26 0 59 5 8 4 12 6 1 3 13 9 1 1 8 1 1 8 1 1 8 1 1 8 1 2 1 1 8 CW C...

Page 9: ... 25 0 15 2 07 50 0 68 5 34 0 34 5 34 0 6 8 13 0 48 0 32 0 1 0 1 0 13 4 16 2 1 1 15 4 3 6 25 0 22 5 09 50 0 68 5 34 0 34 5 34 0 6 8 13 0 48 0 32 0 1 0 1 0 13 4 16 2 1 1 15 4 3 6 30 0 22 5 13 72 0 81 5 34 0 47 5 34 0 6 7 13 0 66 0 45 0 2 0 6 0 16 4 16 4 1 1 14 0 3 6 30 0 23 0 17 72 0 81 5 34 0 47 5 34 0 6 7 13 0 66 0 45 0 2 0 6 0 16 4 16 4 1 1 14 0 3 6 42 6 23 0 CW Chilled Water HW Hot Water w o MSS...

Page 10: ... K L M N O P Q R 04 40 0 27 5 52 0 27 5 26 0 2 7 8 9 36 0 25 5 1 0 2 0 13 6 11 9 1 1 13 1 3 6 20 0 15 2 05 40 0 27 5 52 0 27 5 26 0 2 7 8 9 36 0 25 5 1 0 2 0 13 6 11 9 1 1 13 1 3 6 25 0 15 2 07 50 0 34 5 68 0 34 5 34 0 6 8 12 9 48 0 32 0 1 0 1 0 13 4 16 2 1 1 15 4 3 6 25 0 22 5 09 50 0 34 5 68 0 34 5 34 0 6 8 12 9 48 0 32 0 1 0 1 0 13 4 16 2 1 1 15 4 3 6 30 0 22 5 13 72 0 47 5 68 0 47 5 34 0 6 7 1...

Page 11: ...own 5 Top and rear inlets shown Bottom and rear inlets are also available 39SM UNIT SIZE LENGTH WIDTH HEIGHT DUCT WIDTH DUCT HEIGHT TOP CLEARANCE FILTERS A B C D E F SIZE QTY 04 05 27 0 36 2 25 5 34 3 15 0 2 0 16 x 32 x 2 2 07 09 32 0 48 2 32 4 46 3 15 0 9 7 20 x 24 x 2 4 13 17 40 0 66 2 45 0 64 3 16 0 15 5 30 x 20 x 2 6 a39 4079 Fig 7 39SM Unit Mixing Box ...

Page 12: ...5 1 17 5 6 2 07 09 75 0 53 0 42 2 14 0 44 0 16 4 13 1 15 0 8 0 37 2 24 3 46 0 10 1 20 0 3 5 13 75 1 53 0 55 7 14 0 44 0 16 4 19 4 15 0 8 0 37 3 32 7 46 0 23 5 16 8 3 5 17 96 0 76 3 53 3 15 0 62 0 19 6 22 0 15 0 8 0 50 3 47 0 68 2 17 4 27 1 4 1 Section View A A Right View A 4 0 A A HORIZONTAL DISCHARGE OPT Front View O F G N 875 POWER CONN 4X4 J BOX Rear View B M C L P Pipe Chase F G J K H D E 4 0 ...

Page 13: ... 8 5 16 6 7 0 04 05 74 0 50 5 33 6 12 0 34 0 14 1 13 4 10 0 6 0 38 9 21 2 18 2 36 1 4 2 18 6 7 2 07 09 77 4 55 5 50 9 14 0 44 0 16 4 13 1 15 0 8 0 38 0 35 1 24 3 45 9 19 9 21 2 4 8 13 77 4 55 5 60 6 14 0 44 0 16 4 18 9 15 0 8 0 38 0 48 9 32 8 45 9 29 7 18 3 4 8 17 96 5 76 5 64 1 14 0 62 0 19 0 22 0 15 0 8 0 51 9 48 2 46 9 65 8 24 0 27 3 5 4 F 4 0 J G H 4 0 D K E Front View HORIZONTAL DISCHARGE OPT...

Page 14: ...UNIT SIZE A B C D E F G 02 03 30 6 19 9 26 1 2 0 7 7 26 2 19 9 04 05 39 9 18 0 25 0 1 8 9 9 40 0 22 1 B A F Outdoor Air Hood Return Air Duct G D E C a39 4070 Fig 10 39SR Unit Sizes 02 05 Horizontal Return Economizer Package ...

Page 15: ...39SR UNIT SIZE A B C D E F 02 03 32 100 18 940 42 075 17 260 25 950 16 150 04 05 39 725 22 825 44 025 21 125 27 750 16 250 E F Return Air Outdoor Air C D A B Fig 11 39SR Unit Sizes 02 05 Bottom Return Economizer Package ...

Page 16: ... J 07 09 13 8 44 1 35 2 34 9 15 4 16 5 48 3 13 18 8 44 1 39 0 48 6 20 1 20 0 48 3 17 19 0 62 9 43 4 45 1 20 1 20 0 66 1 E H conversion remove for HBREP Barometric Relief Damper Outdoor Air Hood G F B HBREP A HBREP J a39 4072 Fig 12 39SR Unit Sizes 07 17 Bottom and Horizontal Return Economizer Package ...

Page 17: ...SR UNIT SIZE A B C D E F G H 02 03 29 9 19 1 8 7 5 6 24 1 2 9 13 4 10 4 04 05 37 8 23 5 14 6 5 6 25 3 6 3 17 3 13 8 07 09 48 8 28 4 17 4 5 6 44 4 2 2 21 8 19 6 13 48 8 34 9 22 3 5 6 40 5 4 1 28 3 25 8 17 30 3 46 8 25 0 5 6 25 2 2 5 38 9 31 8 LEGEND MOAD Motorized Outside Air Damper Fig 13 39SR Unit Motorized Outside Air Damper a39 4128 ...

Page 18: ... sheet metal screws are located on the discharge duct collar All red bolts and screws must be removed for the blower assembly to be isolated from the cabinet See Fig 14 Unit Suspension 39SH and 39SM Units Acceptable forms of unit suspension are shown in Fig 15 A field supplied platform mount is recommended especially for larger unit sizes Units can also be supported by suspending the unit from cro...

Page 19: ...mechani cally controlled damper To install BREP 1 Check for correct number of parts shown in Fig 17 and the following list 1 Economizer assembly 1 Barometric relief hood 1 Outdoor air hood 1 Hardware bag 2 Disconnect all power to unit 3 Remove return air access panel from unit and rear access panel s if applicable as shown in Fig 18 4 To assemble the barometric relief hood the following will be ne...

Page 20: ...w into place b Take right hood panel and screw in place like Step a c Take top rail and place flanges over left hood panel and right hood panel and secure d Take side rail and line up to holes in left hood panel and secure e Repeat Step d for side rail and right hood panel f Take front panel and slide inside of side rails g Take top panel and do the same as Step c h Place 1 8 in x 1 2 in gasket on...

Page 21: ...y Check unit wiring for actual unit wiring 2 Relays 1K and 2K actuate when the outdoor air enthalpy is higher than the return air enthalpy 3 1S is an electronic switch which closes when powered by a 24 VAC input 4 Factory installed resistor should be removed only if C7400 differential enthalpy sensor is added a39 4094 ...

Page 22: ...g 28 a Secure the filter channels to the hood sides using the supplied no 10 16 x 1 2 screws b Place the hood sides to the inside of the side flange of the hood top and secure with the supplied no 10 16 x 1 2 screws c Slide the filter inside the filter channels d Place the filter access panel over the hood side panels and secure with no 10 16 x 1 2 screws 3 Adjust the position of the outside air s...

Page 23: ...Remove lock nut from swivel nut assembly Place swivel nut assembly into slot on actuator arm Hand tighten lock nut onto swivel nut assembly Swivel nut assembly will need to be adjusted once installed for proper actuator motion 3 Attach actuator arm assembly to actuator with four 1 4 in screws Arm may need to be repositioned once installed to ensure proper actuator motion Fig 30 Secure Adapter Pane...

Page 24: ...nd linkage arm are parallel 4 Ensure linkage assemblies are properly secured as shown in the linkage assembly instructions sent with the unit 5 Open one set of dampers to 100 open and the other to 100 closed Ensure actuator motion will operate as needed and tighten all linkages swivel assemblies and linkage rods into place 6 Ensure actuator motion opens and closes damper assem blies fully If not a...

Page 25: ...y from the unit NOTE Hanging brackets shipped loose as shown in Fig 41 are recommended for 39SH and 39SM unit sizes 07 and above To install brackets place in approximate location and use self drilling screws to attach to mixing box Brackets are sized to allow hanging from Unistrut Unistrut should be cut to the length one to two inches shorter than the width of the mixing box to avoid any in terfer...

Page 26: ... 6 Insert linkage rod into swivel joints and tighten Linkage rod may need to be cut down to size Linkage arms should be parallel Assembly should still be loose on damper rods This will be linkage assembly no 1 7 Place linkage arm onto DR1 and DR2 Ensure swivel joints are fully extended to the end of the linkage arm and tighten 8 Insert linkage rod into swivel joints and tighten Linkage rod may nee...

Page 27: ... maximum service If misalignment is in the sheave belts will enter and leave the grooves at an angle causing excessive belt cover and sheave wear 1 Shaft alignment can be checked by measuring the distance between the shafts at 3 or more locations If the distances are equal then the shafts will be parallel 2 Check alignment of sheaves Fixed sheaves To check the location of the fixed sheaves on the ...

Page 28: ...Section A Super Belt Small Sheave Pitch Diameter 5 in Solution 1 From Fig 50 find that deflection force for type A super belt with 5 in small sheave pitch diameter is 4 to 51 2 lb 2 3 Increase or decrease belt tension until force required for 1 4 in deflection is 51 2 lb Check belt tension at least twice during first operating day Readjust as required to maintain belt tension within the recommende...

Page 29: ... ahead of the trap This will shut down the supply fan and close the out door damper whenever the condensate falls to a predetermined point perhaps 120 F NOTE Do NOT use an immersion thermostat to override a duct thermostat and open the steam supply valve For vacuum return systems the vacuum breaking check valve would be piped into the condensate line between the trap and the gate valve instead of ...

Page 30: ... 4131 NOTES 1 A bypass is necessary around trap and valves when continu ous operation is necessary 2 Bypass to be the same size as trap orifice but never less than 1 2 inch Fig 53 Dripping Steam Supply to Condensate Return a39 2362tf tif 3 NOTES 1 Flange or union is located to facilitate coil removal 2 When a bypass with control is required 3 Flash trap can be used if pressure differential between...

Page 31: ...itate the distri bution of the steam along the tube s length The outer tubes are expanded into plate fins The completed assembly includes the supply and condensate header and side casings which are built to slant the fin tube bundle back toward the condensate header The slanting of the assembly ensures that condensate will flow toward the drains This condensate must be removed through the return p...

Page 32: ... in a circuit loading of 0 8 to 2 0 tons per circuit at design load Circuit loading must be evaluated at minimum load to ensure that it does not drop below 0 6 tons per circuit Solenoid valves may be used if nec essary to shut off the refrigerant supply to individual expansion valves to maintain adequate coil circuit loading Compressor minimum unloading and TXV quantity is nec essary to determine ...

Page 33: ...or Start Stop Stations All field installed wiring including the electrical ground MUST comply with the National Electrical Code NEC as well as applicable local codes In addition all field wiring must conform to the Class II temperature limitations described in the NEC Refer to Fig 59 and 60 for optional factory installed motor start stop station wiring diagrams WARNING To avoid possible injury or ...

Page 34: ... mounting bolts g Motor out of balance h Sheaves eccentric or out of balance i Vibration isolators improperly adjusted j Out of balance or corroded wheel rebalance or replace if necessary k Accumulation of material on wheel remove excess material SERVICE General 1 Place a suitable walkway to protect floor insulation whenever entering the fan section 2 Review Safety Considerations at beginning of t...

Page 35: ...nd thermostatic trap will contain a thermostatic air vent When the bellows is ruptured it will fail closed 7 Check operation of vacuum breakers 8 Check operation of the thermal protection devices used for freeze up protection 9 Steam or condensate should not be allowed to remain in the coil during the off season This will prevent the forma tion and build up of acids There are additional precaution...

Page 36: ... manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs are available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training which includes hands on experience with the products in our labs can mean increased confidence that really pays...

Reviews: