Table 6 —
Troubleshooting
Replacement Parts
Quote the unit model number and
unit serial number when ordering replacement parts or
contacting the factory about the unit. This information can be
found on the serial plate attached to the unit. See Fig. 21.
MODEL
Vertical Air Handler
R410A
HIGH
LOW
REFRIGERANT
3.8 A
15 A
3.0 A
40VMV018---3
370W (1/2HP)
320 PSIG
208/230V-1Ph-60Hz
DESIGN
PRESSURE
580 PSIG
POWER SUPPLY
MINIMUM CIRCUIT AMPACITY
FAN MOTOR
FLA
OUTPUT
MAX
FUSE
OR
HACR
BREAKER
SERIAL NO.
1716V00001
Installed Heater Kit
Model
Electric
Heat (KW)
Min.Circuit
Ampacity
Max.Fuse or Breaker
(HACR) Ampacity
5
40WA910005
240
240
208
208
29.8
26.8
30
30
CONFORMS TO UL STD 1995
CERTIFIED TO CSA STD.
C22. 2 No. 236
ONLY FOR INDOOR UNIT.
MAX EXTERNAL STATIC PRESSURE 0.8 IN.W.C.
Fig. 21 — Unit Serial Plate (Example)
ERROR
DESCRIPTION
POSSIBLE CAUSES
POSSIBLE SOLUTIONS
dd
Heating / Cooling Mode Conflict
System is in cooling or fan only mode and
heating signal is received from a unit on the
system.
All units should be in cooling mode for system to
stay in cooling mode.
System is in heating mode and cooling
signal is received from a unit in the system.
All units should be in heating mode.
E1
Communication Error Between
Indoor & Outdoor Unit
Signal wires are short-circuited or
disconnected.
Check or reconnect signal wire.
Signal wire close to electromagnetic
source.
Distance signal wires from electromagnetic
source.
PC board fault.
Replace PC board.
E2, E4,
E5
Check Temperature Sensor
Loose connection at port on PC board.
Tighten the connection at port on PC board.
Sensor is short-circuited.
Using multi-meter, measure resistance of the
sensor. If the resistance is £ 100 ohms, change
the sensor.
PC board fault.
Replace PC board.
E6
DC Fan Motor
Operating Beyond Limits.
Check and correct external static pressure on the
unit.
DC motor fault.
Replace DC motor.
PC board fault.
Replace PC board.
E7
EEPROM Error (Data Storage)
Chip or PC board fault.
Replace PC board.
E9
Communication Error Between
Indoor Unit & Controller
Signal wires are short-circuited or
disconnected.
Check or reconnect signal wires.
Signal wires close to electromagnetic
source.
Distance signal wires from electromagnetic
source.
PC board fault.
Replace PC board.
Eb
EEV Error
EEV wires are short-circuited or
disconnected.
Replace EEV wires.
EEV stop.
Replace EEV.
PC Board fault.
Replace PC board.
Ed
Outdoor Unit Error
Outdoor unit fault.
Refer to outdoor unit troubleshooting guide.
EE
Condensate Error
Loose connection or disconnected.
Tighten the connection or reconnect at port on
PC board.
Water level float is stuck.
Inspect the slope.
Trap slope is too steep.
Adjust the trap slope.
Drain pipe is too long.
Adjust the length of drain pipe.
Drain pump faulty.
Replace the drain pump.
FE
No Address When Power ON for first
time
Indoor unit without address.
Run automatic addressing option at the outdoor
unit.
Use remote wireless or wired controller to
readdress indoor unit.
UU
MDC Auto System-Check Mode
MDC fault
Refer to MDC troubleshooting guide.