LEGEND

EEPROM

Electronically Erasable Programmable Read-only 
Memory

EEV

Electronic Expansion Valve

MDC

Multiport Distribution Controller

PC

Process Controller

16

Table 6 —

Troubleshooting

Replacement Parts

 

Quote the unit model number and

 

unit serial number when ordering replacement parts or 
contacting the factory about the unit. This information can be 
found on the serial plate attached to the unit. See Fig. 21. 

MODEL

Vertical Air Handler

R410A

HIGH

LOW

REFRIGERANT

3.8 A

15 A

3.0 A

40VMV018---3

370W (1/2HP)

320 PSIG

208/230V-1Ph-60Hz

DESIGN
PRESSURE

580 PSIG

POWER SUPPLY

MINIMUM CIRCUIT AMPACITY

FAN MOTOR

FLA

OUTPUT

MAX

 FUSE

 OR

 HACR

 BREAKER

SERIAL NO.

1716V00001

Installed Heater Kit

Model

Electric

Heat (KW)

Min.Circuit
Ampacity

Max.Fuse or Breaker
(HACR) Ampacity

5

40WA910005

240

240

208

208

29.8

26.8

30

30

CONFORMS TO UL STD 1995
CERTIFIED TO CSA STD.
C22. 2 No. 236

ONLY FOR INDOOR UNIT.

MAX EXTERNAL STATIC PRESSURE 0.8 IN.W.C.

Fig. 21 — Unit Serial Plate (Example)

ERROR

DESCRIPTION

POSSIBLE CAUSES

POSSIBLE SOLUTIONS

dd

Heating / Cooling Mode Conflict

System is in cooling or fan only mode and 
heating signal is received from a unit on the 
system.

All units should be in cooling mode for system to 
stay in cooling mode.

System is in heating mode and cooling 
signal is received from a unit in the system.

All units should be in heating mode.

E1

Communication Error Between 
Indoor & Outdoor Unit

Signal wires are short-circuited or 

disconnected.

Check or reconnect signal wire.

Signal wire close to electromagnetic 
source.

Distance signal wires from electromagnetic 
source.

PC board fault.

Replace PC board.

E2, E4, 

E5

Check Temperature Sensor

Loose connection at port on PC board.

Tighten the connection at port on PC board.

Sensor is short-circuited.

Using multi-meter, measure resistance of the 
sensor. If the resistance is £ 100 ohms, change 
the sensor.

PC board fault.

Replace PC board.

E6

DC Fan Motor

Operating Beyond Limits.

Check and correct external static pressure on the 
unit.

DC motor fault.

Replace DC motor.

PC board fault.

Replace PC board.

E7

EEPROM Error (Data Storage)

Chip or PC board fault.

Replace PC board.

E9

Communication Error Between 
Indoor Unit & Controller

Signal wires are short-circuited or 
disconnected.

Check or reconnect signal wires.

Signal wires close to electromagnetic 
source.

Distance signal wires from electromagnetic 
source.

PC board fault.

Replace PC board.

Eb

EEV Error

EEV wires are short-circuited or 
disconnected.

Replace EEV wires.

EEV stop.

Replace EEV.

PC Board fault.

Replace PC board.

Ed

Outdoor Unit Error

Outdoor unit fault.

Refer to outdoor unit troubleshooting guide.

EE

Condensate Error

Loose connection or disconnected.

Tighten the connection or reconnect at port on 
PC board.

Water level float is stuck.

Inspect the slope.

Trap slope is too steep.

Adjust the trap slope.

Drain pipe is too long.

Adjust the length of drain pipe.

Drain pump faulty.

Replace the drain pump.

FE

No Address When Power ON for first 
time

Indoor unit without address.

Run automatic addressing option at the outdoor 
unit.
Use remote wireless or wired controller to 
readdress indoor unit.

UU

MDC Auto System-Check Mode

MDC fault

Refer to MDC troubleshooting guide.

Summary of Contents for 40VMV012

Page 1: ...Canadian Electrical Code CSA Canadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal...

Page 2: ...at the steps outlined in this manual for initial inspection proper installation regular periodic maintenance and everyday operation of the unit be followed in detail This manual should be fully review...

Page 3: ...20 1260 Medium 320 510 680 850 1020 1360 1530 High 400 600 800 1000 1200 1600 1800 EXTERNAL STATIC PRESSURE in wg 0 8 INDOOR UNIT NOISE LEVEL dBA Low 34 5 34 4 37 9 44 4 39 3 43 8 47 9 Medium 34 5 37...

Page 4: ...mensions shown in inches 40VMV UNIT SIZE A B C D 012 030 46 1 2 19 5 8 18 21 5 8 036 054 54 1 2 22 19 1 2 24 RIGHT SIDE A FRONT B C D DRAIN PIPE LEFT SIDE AIR RETURN REFRIGERANT SIDE PIPE LIQUID REFRI...

Page 5: ...al dimensions such as pipe wire and duct connections requirements Refer to job drawings and product dimension drawings as required Instruct all trades in their parts of the installation Units must be...

Page 6: ...ould slope downward in the direction of condensate flow with a minimum gradient of 1 in per 100 inches Condensate piping should be installed in such a way that it does not block the front service pane...

Page 7: ...rect wiring or voltage is not covered by warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls that are used with the unit See Table 4 for...

Page 8: ...ce N C 5 N 1 1 5 C Voltage range 0 24V AC DC Current range 0 1A FAN CTON HTON AUXH RED BLACK XS4 XP4 XS5 XP5 XS6 XP6 XT1 BLACK RED Y G CN27 CN3 CN18 CN31 CN54 CN4 CN15 CN19 CN8 CN21 CN12 CN26 CN14 CN2...

Page 9: ...e to buy communication wires from Carrier connect the indoor unit side of the communication wires using the connector provided with the accessories as shown in Fig 11 13 CAUTION Failure to follow thes...

Page 10: ...Fig 11 Connecting the Communication Cable to Indoor Unit to Outdoor Unit Using the Supplied Connector Connector in accessory kit Connector on indoor unit Communication cable in field 10...

Page 11: ...oor To Sub MDC To outdoor Indoor unit 1 L1 L2 L3 L3 L3 L3 L4 L5 L6 L7 L8 L9 L10 1 1 L Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 HA HB HA HB HA HB HA HB HA HB HA HB Touch sc...

Page 12: ...t Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 P Q HA HB HA HB HA HB HA HB HA HB HA HB Network Resistor Maximum wiring length L1 L3 3937 ft 16 AWG 2 Core Strande...

Page 13: ...he power is restored MAINTENANCE CAUTION When servicing or repairing this unit use only factory approved service replacement parts Refer to the rating plate on the unit for complete unit model number...

Page 14: ...o an indoor unit Press ROOM TEMP and SWING simultaneously for 3 seconds If there is no address for this indoor unit the display shows FE 00 see Fig 16 otherwise the display shows the current address o...

Page 15: ...M Electronically Erasable Programmable Read only Memory EEV Electronic Expansion Valve MDC Multiport Distribution Controller ERROR CODE MODE STATUS NO ERROR Setting Temperature Starting Shutdown Stand...

Page 16: ...ignal wire close to electromagnetic source Distance signal wires from electromagnetic source PC board fault Replace PC board E2 E4 E5 Check Temperature Sensor Loose connection at port on PC board Tigh...

Page 17: ...1 START UP OFF Auto Addressing Mode Default ON Factory Test Mode POSITION 2 OFF Normal Mode Default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF Standard...

Page 18: ...speed M speed 500 AIRFLOW cfm L speed 700 300 400 600 Upper Limit of ESP Fig B 40VMV018 Fan Curves Fig A 40VMV012 Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 EXTERNAL STATIC PRESSURE in wg H speed 500 A...

Page 19: ...0VMV048 Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 1000 1200 1400 1600 1800 2000 EXTERNAL STATIC PRESSURE in wg H speed M speed Upper Limit of ESP L speed AIRFLOW cfm Fig G 40VMV054 Fan Curves 0 00 0 20...

Page 20: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 16 40VMV001 01 Printed in U S A Form 40VM 2SI Pg 20 2 17 Replaces 40VM 1...

Reviews: