background image

5

INSTALLATION

Step 1 — Unpack and Inspect Units

 Units are 

packaged for shipment to avoid damage during normal transit 
and handling. It is the receiving party’s responsibility to inspect 
the equipment upon arrival. Any obvious damage to the carton

 

and/or its contents should be reported on the bill of lading and a 
claim should be filed with the transportation company and the

 

factory. Unit should always be stored in a dry place, and in the 
proper orientation as marked on the carton.

CAUTION

To avoid equipment damage, do not lift unit by the drain

 

pipe or refrigerant piping. Unit should be lifted using the

 

mounting brackets.

After determining the condition of the carton exterior, 

carefully remove each unit from the carton and inspect for 
hidden damage. Check to make sure that items such as 
thermostats, controller etc. are accounted for, whether 
packaged separately or shipped at a later date. Any hidden

 

damage should be recorded, a claim should be filed with the 
transportation company, and the factory should be notified. In

 

the event a claim for shipping damage is filed, the unit, 
shipping carton, and all packing must be retained for physical 
inspection by the transportation company. All units should be 
stored in the factory shipping carton with internal packaging in

 

place until installation.
PROTECTING UNITS FROM DAMAGE Do not apply

 

force or pressure to the coil, piping, or drain stub-outs during

 

handling. All units should be handled by the chassis or as close

 

as possible to the unit mounting point locations. 

The unit must always be properly supported. Temporary

 

supports used during installation or service must be adequate to

 

hold the unit securely. To maintain warranty, protect units 
against hostile environments (such as rain, snow or extreme 
temperature), theft, vandalism, and debris on jobsite. 
Equipment covered in this manual is not suitable for outdoor 
installations. Do not allow foreign material to fall into drain

 

pan. Prevent dust and debris from being deposited on motor, 
fan wheels and coils. Failure to do so may have serious adverse 
effects on unit operation and in the case of motor and blower 
assembly, may result in immediate or premature failure. Failure 
of any unit caused by deposits of foreign material on the motor 
or blower wheels will not be covered by the manufacturer’s 
warranty. Some units and/or job conditions may require some 
form of temporary covering during construction.
PREPARING JOBSITE FOR UNIT INSTALLATION To

 

save time and to reduce the possibility of costly errors, set up a 
complete sample installation in a typical room at jobsite. 
Check all critical dimensions such as pipe, wire, and duct 
connections requirements. Refer to job drawings and product 
dimension drawings as required. Instruct all trades in their 
parts of the installation. Units must be installed in compliance 
with all applicable local code requirements.
IDENTIFYING AND PREPARING UNITS Be sure power 
requirements match available power source. Refer to unit 
nameplate and wiring diagram. In addition:
• Check all tags on unit to determine if shipping screws are 

to be removed. Remove screws as directed.

• Rotate the fan wheel by hand to ensure that the fan is 

unrestricted and can rotate freely. Check for shipping

 

damage and fan obstructions. Adjust blower motor as 
required. 

Step 2 — Position the Unit

DANGER

Units must not be installed where they may be exposed to

 

potentially explosive or flammable atmosphere. If this 
instruction is not followed exactly, a fire or explosion may

 

result, causing property damage, injury, or loss of life.

Install the unit in a location that meets the following

 

requirements:
• Allow adequate space for installation, service clearance, 

piping and electrical connections, and necessary

 

ductwork. For specific unit dimensions, refer to Table 2
Fig. 2, and Fig. 3. Allow clearance according to local and

 

national codes. 

• Unit can be installed standing vertically on the floor or 

on a field-provided stand. If a stand is used, be sure it can

 

support the weight of the unit. Unit can also be installed

 

horizontally, either resting on the floor or suspended

 

from the ceiling. If suspended, confirm that the ceiling is 
able to support the weight of the unit. See Table 2 fo
nominal weight.

• If the unit is to be installed over a finished ceiling and/or 

living area, building codes may require a field-supplied

 

secondary condensate drain pan to be installed under the 
entire unit. Consult local codes inspector for additional 
information.

Select the unit position with the following points in mind:
• The unit should be installed on a structure that is suitable 

to support the total weight of the unit, refrigerant piping

 

and condensate.

• Proper access should be provided for maintenance for 

refrigerant piping, EEV (electronic expansion valve), 
electrical box, and condensate pump. A 2-ft. clearance is 
recommended all around the unit. 

• The unit should not be positioned close to a wall or 

similar obstruction, or in a position where the discharge 
air could blow directly on the thermostat. See Fig. 3.

Fig. 3 — Clearances

AIRFLOW

HORIZONTAL INSTALLATION

t

39

3

/

8

t

39

3

/

8

t

39

3

/

8

t

7

7

/

8

t

7

7

/

8

t

7

7

/

8

VERTICAL INSTALLATION

NOTE: All dimensions shown in inches.

• The unit should not be positioned directly above any

 

obstruction.

• The unit must be installed square and level.
• The condensate drain should have sufficient downward

 

slope (1 in. per 100 in.) in any horizontal run between

 

unit and drain.

Summary of Contents for 40VMV012

Page 1: ...Canadian Electrical Code CSA Canadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal...

Page 2: ...at the steps outlined in this manual for initial inspection proper installation regular periodic maintenance and everyday operation of the unit be followed in detail This manual should be fully review...

Page 3: ...20 1260 Medium 320 510 680 850 1020 1360 1530 High 400 600 800 1000 1200 1600 1800 EXTERNAL STATIC PRESSURE in wg 0 8 INDOOR UNIT NOISE LEVEL dBA Low 34 5 34 4 37 9 44 4 39 3 43 8 47 9 Medium 34 5 37...

Page 4: ...mensions shown in inches 40VMV UNIT SIZE A B C D 012 030 46 1 2 19 5 8 18 21 5 8 036 054 54 1 2 22 19 1 2 24 RIGHT SIDE A FRONT B C D DRAIN PIPE LEFT SIDE AIR RETURN REFRIGERANT SIDE PIPE LIQUID REFRI...

Page 5: ...al dimensions such as pipe wire and duct connections requirements Refer to job drawings and product dimension drawings as required Instruct all trades in their parts of the installation Units must be...

Page 6: ...ould slope downward in the direction of condensate flow with a minimum gradient of 1 in per 100 inches Condensate piping should be installed in such a way that it does not block the front service pane...

Page 7: ...rect wiring or voltage is not covered by warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls that are used with the unit See Table 4 for...

Page 8: ...ce N C 5 N 1 1 5 C Voltage range 0 24V AC DC Current range 0 1A FAN CTON HTON AUXH RED BLACK XS4 XP4 XS5 XP5 XS6 XP6 XT1 BLACK RED Y G CN27 CN3 CN18 CN31 CN54 CN4 CN15 CN19 CN8 CN21 CN12 CN26 CN14 CN2...

Page 9: ...e to buy communication wires from Carrier connect the indoor unit side of the communication wires using the connector provided with the accessories as shown in Fig 11 13 CAUTION Failure to follow thes...

Page 10: ...Fig 11 Connecting the Communication Cable to Indoor Unit to Outdoor Unit Using the Supplied Connector Connector in accessory kit Connector on indoor unit Communication cable in field 10...

Page 11: ...oor To Sub MDC To outdoor Indoor unit 1 L1 L2 L3 L3 L3 L3 L4 L5 L6 L7 L8 L9 L10 1 1 L Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 HA HB HA HB HA HB HA HB HA HB HA HB Touch sc...

Page 12: ...t Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 P Q HA HB HA HB HA HB HA HB HA HB HA HB Network Resistor Maximum wiring length L1 L3 3937 ft 16 AWG 2 Core Strande...

Page 13: ...he power is restored MAINTENANCE CAUTION When servicing or repairing this unit use only factory approved service replacement parts Refer to the rating plate on the unit for complete unit model number...

Page 14: ...o an indoor unit Press ROOM TEMP and SWING simultaneously for 3 seconds If there is no address for this indoor unit the display shows FE 00 see Fig 16 otherwise the display shows the current address o...

Page 15: ...M Electronically Erasable Programmable Read only Memory EEV Electronic Expansion Valve MDC Multiport Distribution Controller ERROR CODE MODE STATUS NO ERROR Setting Temperature Starting Shutdown Stand...

Page 16: ...ignal wire close to electromagnetic source Distance signal wires from electromagnetic source PC board fault Replace PC board E2 E4 E5 Check Temperature Sensor Loose connection at port on PC board Tigh...

Page 17: ...1 START UP OFF Auto Addressing Mode Default ON Factory Test Mode POSITION 2 OFF Normal Mode Default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF Standard...

Page 18: ...speed M speed 500 AIRFLOW cfm L speed 700 300 400 600 Upper Limit of ESP Fig B 40VMV018 Fan Curves Fig A 40VMV012 Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 EXTERNAL STATIC PRESSURE in wg H speed 500 A...

Page 19: ...0VMV048 Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 1000 1200 1400 1600 1800 2000 EXTERNAL STATIC PRESSURE in wg H speed M speed Upper Limit of ESP L speed AIRFLOW cfm Fig G 40VMV054 Fan Curves 0 00 0 20...

Page 20: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 16 40VMV001 01 Printed in U S A Form 40VM 2SI Pg 20 2 17 Replaces 40VM 1...

Reviews: