Installation and Maintenance Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

 . . . . . . . . . . . . . . . . . . . 1

GENERAL

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

DIMENSIONS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

FAN CURVE CHARACTERISTICS

. . . . . . . . . . . . . . . 5

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Step 1 — Unpack and Inspect Units

 . . . . . . . . . . . . 7

Step 2 — Position the Unit

 . . . . . . . . . . . . . . . . . . . 8

Step 3 — Mount the Unit

 . . . . . . . . . . . . . . . . . . . . . . 8

Step 4 — Connect Piping

. . . . . . . . . . . . . . . . . . . . . . 9

Step 5 — Complete the Electrical Connections

 . 10

Step 6 — Installing the LED Display Panel

 . . . . . 12

Step 7 — Position and Connect Controller

 . . . . . 12

MAINTENANCE

 . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

TROUBLESHOOTING

 . . . . . . . . . . . . . . . . . . . . . . 19

REPLACEMENT PARTS

. . . . . . . . . . . . . . . . . . . . . 21

APPENDIX - DIP SWITCH SETTINGS

 . . . . . . . . . . 22

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, 

maintenance, or use can cause explosion, fire, electrical shock, 

or other conditions; which may cause death, personal injury or 

property damage. The qualified installer or agency must use 

factory-authorized kits or accessories when modifying this 

product.

Follow all safety codes. Wear safety glasses, protective 

clothing, and work gloves. Use quenching cloth for brazing 

operations. Have fire extinguisher available. Read these 

instructions thoroughly and follow all warnings or cautions 

included in the literature and attached to the unit. Consult local 

building codes and the current editions of the National 

Electrical Code (NEC) ANSI/NFPA (American National 

Standards Institute/National Fire Protection Association) 70. In 

Canada, refer to the current editions of the Canadian Electrical 

Code CSA (Canadian Standards Association) C22.1.

Understand the signal words — 

DANGER

WARNING

, and

CAUTION

DANGER

  identifies  the  most  serious  hazards,

which result in severe personal injury or death. 

WARNING

signifies hazards that could result in personal injury or death.

CAUTION

 is used to identify unsafe practices, which would

result  in  minor  personal  injury  or  product  and  property

damage.

Recognize safety information. This is the safety-alert      

symbol (

). When this symbol is displayed on unit and in 

instructions or manuals, be alert to potential for personal     

injury.

WARNING

Electrical shock can cause personal injury and death. 

Shut off all power to this equipment during installation. 

There may be more than one disconnect switch. Tag all 

disconnect locations to alert others not to restore power 

until work is completed.

WARNING

DO NOT re-use compressor oil or any oil that has been 

exposed to the atmosphere. Dispose of oil per local codes 

and regulations. DO NOT leave refrigerant system open to 

air any longer than the actual time required to service the 

equipment. Seal circuits being serviced and charge with dry 

nitrogen to prevent oil contamination when timely repairs 

cannot be completed. Failure to follow these procedures 

may result in damage to equipment. 

For information about replacement oil type and viscosity, 

see the Installation, Start-Up, and Service Instructions for 

the 38VMAH and 38VMAR outdoor units.

WARNING

DO  NOT  USE TORCH  to  remove  any  component. The

system contains oil and refrigerant under pressure.

To  remove  a  component,  wear  protective  gloves  and

goggles and proceed as follows:

A. Shut off electrical power to unit.

B. Recover refrigerant to relieve all pressure from the

system  using  both  the  high-pressure  and  low

pressure ports.

C. Traces of vapor should be displaced with nitrogen

and  the  work  area  should  be  well  ventilated.

Refrigerant in contact with an open flame produces

toxic gases.

D. Cut the component connection tubing with a tubing

cutter and remove the component from unit. Use a

pan to catch any oil that may come out of the lines

and as a gage for how much oil to add to the system.

E. Carefully  unsweat  remaining  tubing  stubs  when

necessary.  Oil  can  ignite  when  exposed  to  torch

flame.

Failure to follow these procedures may result in personal

injury or death.

WARNING

When installing the equipment in a small space, provide 

adequate measures to avoid refrigerant concentration 

exceeding safety limits due to refrigerant leak. 

In case of refrigerant leak during installation, ventilate 

the space immediately. Failure to follow this procedure 

may lead to personal injury.

40VMZ009-024

Reheat Unit for

Variable Refrigerant Flow (VRF) Systems

Summary of Contents for 40VMZ

Page 1: ...his symbol is displayed on unit and in instructions or manuals be alert to potential for personal injury WARNING Electrical shock can cause personal injury and death Shut off all power to this equipme...

Page 2: ...ons BEFORE proceeding See Fig 1 for the model number nomenclature Table 1 shows components that may or may not be used for a particular installation Table 2 lists physical data for each unit sizes Fig...

Page 3: ...DOOR EXTERNAL STATIC PRESSURE High in wg 0 8 1 0 INDOOR NOISE LEVEL dBA Low 31 6 32 5 34 2 42 2 44 5 Medium 34 0 38 6 38 4 43 8 47 0 High 35 2 39 3 39 8 44 5 47 7 UNIT Unit Dimensions W x H x D in 37...

Page 4: ...OLBOX SAFETYDRAINCONNECTINGPIPE CONNECTINGPOINTOF DRAINPIPE 27 3 16 33 3 4 8 7 16 3 3 8 37 1 2 16 1 2 3 3 8 13 3 8 16 7 8 10 211 7 21 4 12 25OBLONGSUSPENTIONBOLTHOLES AIRINTAKE AIROUTLET AIROUTLETDUCT...

Page 5: ...48 0 48 0 43 0 48 0 52 0 52 0 47 0 52 0 56 0 56 0 50 0 56 0 60 0 60 0 54 0 60 0 64 0 64 0 57 0 64 0 68 0 68 0 61 0 68 0 72 0 72 0 65 0 72 0 76 0 76 0 69 0 76 0 80 0 80 0 73 0 80 0 84 ESP Fan Speed Ra...

Page 6: ...0 60 0 53 0 60 0 66 0 64 0 57 0 64 0 71 0 68 0 60 0 68 0 76 0 72 0 64 0 72 0 80 0 76 0 68 0 76 0 84 0 80 0 72 0 80 0 88 ESP Fan Speed Range of Available Airflow Rate in H Speed Max Point Rating Point...

Page 7: ...the factory shipping carton with internal packaging in place until installation PROTECTING UNITS FROM DAMAGE Do not apply force or pressure to the coil piping or drain stub outs during handling All un...

Page 8: ...support the total weight of the unit refrigerant piping and condensate optional Proper access should be provided for maintenance for refrigerant piping EEV electronic expansion valve electrical box A...

Page 9: ...es See Fig 13 Fig 13 Using a Main Drain to Serve Multiple Indoor Units When multiple units are connected to a common condensate drain ensure that the drain is large enough to accommodate the volume of...

Page 10: ...lure of units caused by incorrect wiring or voltage is not covered by the warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls that are us...

Page 11: ...put for Fan Operation FM Indoor Fan Motor HTON Output for Heating Operation T0 Return Air Temperature Sensor TA SupplyAir Temperature Sensor T2A Evaporator Inlet Temperature Sensor T2B Evaporator Outl...

Page 12: ...windows and doors Avoid positioning near shelves and curtains as these restrict air movement Avoid heat sources such as direct sunlight heaters dimmer switches and other electrical devices See Fig 19...

Page 13: ...ypical communication wiring of the heat recovery systems IMPORTANT Wiring for communication shall be 2 inches or more apart from power source wiring to avoid electric noise DO NOT insert control commu...

Page 14: ...wired controller MAXIMUM WIRING LENGTH CN51 CN50 ACB interface FAN CTONHTONAUXH CN54 OFF GND 3GOT HUGXJ Outside Air Unit Reheat unit L11 wired controller wired controller wired controller wired contr...

Page 15: ...pen posi tion System Operation Check Follow these steps once the installation and pre start checks are completed 1 Using remote controller select cooling or heating mode to check the operation of the...

Page 16: ...actory approved service replacement parts Refer to the rating plate on the unit for complete unit model number serial number and company address Any substitution of parts or controls not approved by t...

Page 17: ...ntil it cannot move any further See Fig 30 2 Lift up slightly and take it down to remove it 3 After motor maintenance reinstall the fan assemblies apply steps in reverse order step 2 then step 1 4 Con...

Page 18: ...hold LOCK for at least 10 seconds and press to query the address Programmable Controller When setting an address connect only one wired controller to an indoor unit 1 Press FAN and BACK simultaneousl...

Page 19: ...g OFF Operation and Defrost Fan Light ON System Defrost ON Operation and Defrost Fan Light OFF System Defrost OFF Operation Light ON Only FAN dd None Heating Cooling Mode Conflict E1 Communication Err...

Page 20: ...Sensor is short circuited Using multi meter measure resistance of sensor if resistance is 100 ohms change the sensor PC board fault Replace PC board E6 DC Fan Motor Operating beyond limits Check and c...

Page 21: ...Unit Size Filter Dimension W x H x D 009 to 024 28 3 8 x 13 1 4 x 3 8 MODEL R410A HIGH LOW REFRIGERANT 0 88 A 15 A 0 70 A 750 W 33 32HP 40VMZ009 3 208 230V 1Ph 60Hz 320 PSIG 580 PSIG DESIGN PRESSURE P...

Page 22: ...ns Catalog No 20 40VMZ001 01 Printed in U S A Form 40VMZ 1SI Pg 22 08 20 Replaces New Carrier Corporation 2020 APPENDIX A DIP SWITCH SETTINGS There are two DIP switches on the main board Figs A and B...