12
Step 6 — Installing the LED Display Panel —
1. The display panel has buckles on the bottom that are used
to secure it to the control box. See Fig. 16.
Fig. 16 —LED Display Panel
2. Insert the buckles into the grooves in the electronic
control box, and slide the display panel horizontally to
lock in place. See Figs. 17 and 18.
Fig. 17 —LED Display Panel Installation Location
3.
Connect the 10-core wire of the display board to control
board assembly through wire aperture on electronic
control box
.
Fig. 18 —LED Display Panel Installed
Step 7 — Position and Connect Controller —
Wired controllers should be installed in a position that
maintains good temperature control:
• Position the thermostat approximately 48 inches above
floor level
• Do not position thermostat where it can be directly
affected by the unit’s discharge air-stream.
• Avoid external walls and drafts from windows and doors.
• Avoid positioning near shelves and curtains as these
restrict air movement.
• Avoid heat sources such as direct sunlight, heaters,
dimmer switches, and other electrical devices.
• See Fig. 19 for an example of communication wire
connection.
CONTROL WIRING —
1. Use copper core PVC insulated sheathed shielded twisted
cord.
2. For indoor unit and outdoor unit communication, use P, Q
terminals. Shielded core should be used for ground.
3. Wiring should be done according to wiring diagram.
4.
Communication wire must not form a closed loop.
Fig. 19 —Communication Wire Connection
OPTION/EXTENSIONS OF COMMUNICATION
WIRING — To extend control wiring or make terminal
connections, use the PQE connection wire supplied in the
accessory kit and follow these steps.
1. Cut the connector on the outdoor unit side. See Fig. 20.
Fig. 20 —Shearing Outdoor Connector
2.
Strip a suitable length of the insulation layer. See Fig. 21.
Fig. 21 —Stripping the Wire
Buckle
10-core wire
5-core wire
(reserved)
Display board
Groove
Electronic control box
Wire aperture
Effect diagram
of assembly