UNIT
48HJ
MAXIMUM SHIPPING WEIGHT
Lb
Kg
D015
1920
871
E015
1940
880
E017
2310
1048
UNIT
48HJ
DIMENSIONS
X
Y
Ft-in.
mm
Ft-in.
mm
D015
3-2
965
4-0
1219
E015
3-2
965
4-0
1219
E017
3-7
3
⁄
8
1102
3-6
5
⁄
8
1083
UNIT
48HJ
WEIGHT OF CORNER*
A
B
C
D
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
D015
365
166
360
163
373
169
540
245
E015
372
169
363
165
377
171
547
248
E017
509
231
506
230
475
216
519
235
*Weights are for unit only and do not include options or crating.
NOTES:
1. Dimensions in (
) are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:
a. Rear: 7
8
-0
9
(2134) for coil removal. This dimension can be reduced
to 4
8
-0
9
(1219) if conditions permit coil removal from the top.
b. Left side: 4
8
-0
9
(1219) for proper condenser coil airflow.
c. Front: 4
8
-0
9
(1219) for control box access.
d. Right side: 4
8
-0
9
(1219) for proper operation of damper and power
exhaust (if so equipped).
e. Top: 6
8
-0
9
(1829) to assure proper condenser fan operation.
f. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser coil and the damper/
power exhaust as stated in Note No. 5, a removable fence or barri-
cade requires no clearance.
7. Dimensions are from outside of corner post. Allow 0
8
-
5
⁄
16
9
(8) on each
side for top cover drip edge.
Fig. 4 — Base Unit Dimensions, 48HJ015,017