7. Connect the motor plug to the plug provided with the har-

ness. Be sure the wires will not interfere with any moving
parts. Secure the wires with wire ties if needed. (See
Fig. 5.)

8. Pass the harness wires through the plastic bushing in the

compressor section partition, and into the control box sec-
tion. Be sure to secure the wires so that they will not inter-
fere with any moving parts.

9. Install the insulated partition (block-off panel) by sliding

the panel into the unit from the side. The damper side of
the panel will slide along the top of the flange of the
damper assembly, between the return and outdoor air
damper blades. The panel should then be rotated upwards
so that the mounting holes align with the holes in the pan-
els at the end of the unit. Once in the correct position, the
partition will be horizontal inside the unit as shown in
Fig. 6.

10. Secure the partition to the frame using the screws saved

from Step 3, at the edges of the partition as shown in
Fig. 7.

11. The installation of the damper assembly is now complete

and the outer unit panels can now be replaced using the
screws saved from the earlier steps. Be sure to inspect all
panel seals prior to re-assembly and replace any seals that
appear damaged.

12. The control wiring can now be completed.
13. Open the hinged control box compartment on the unit and

remove the control box cover. Save the screws for use lat-
er. Be sure not to place sharp objects on any surface that
could be damaged.

14. Install the Economizer board (P/N 50TG000596) into the

control box using the no. 6 

3

/

4

-in. screws provided. The

economizer board will mount into the pre-drilled holes on
the right side flange of the control box as shown in Fig. 8.

15. Connect the communications and power harness

(P/N 50TG400612) into the Economizer Control Board
(ECB) plugs J1 and J2 and to the Main Base Board plugs
J2 and J3. See Fig. 9 and 10. Be sure to connect the plugs
with the proper orientation such that the locking tabs cap-
ture the plug.

IMPORTANT: If the return duct opening was covered
prior to installation, remember to remove the covering so
as not to block off the return air to the unit.

MOUNTING
HOLES

INSULATED
BLOCK-OFF
PANEL

Fig. 5 — Economizer Plug and Wiring

Fig. 6 — Economizer Block-Off Panel Location

MOUNTING
HOLES

Fig. 7 — Secure Block-Off Panel to Frame

Summary of Contents for 48HG014-028

Page 1: ...nnel When working on air conditioning equipment observe precau tions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire extinguishers available for all brazing operations INSTALLATION 1 Remove two manual dampers and one mist eliminating ...

Page 2: ...stic bushing being careful not to damage the wires Route the harness across the back of the top member of the frame as shown and attach to the frame us ing the wire ties provided See Fig 4 RETURN END OF UNIT FRAME SUPPORT BRACKETS SIDE PANEL REMOVED WIRE ROUTING PLASTIC BUSHING EXISTING WIRE TIES PLASTIC BUSHING Fig 1 Return End of Unit Fig 2 Frame Support Brackets Side Panel Removed Fig 3 Slide E...

Page 3: ... unit panels can now be replaced using the screws saved from the earlier steps Be sure to inspect all panel seals prior to re assembly and replace any seals that appear damaged 12 The control wiring can now be completed 13 Open the hinged control box compartment on the unit and remove the control box cover Save the screws for use lat er Be sure not to place sharp objects on any surface that could ...

Page 4: ...J4 CEPL130346 01 STATUS LEN J1 J2 J4 J3 J5 J6 J7 J8 J9 J10 CCN YELLOW LED CCN CARRIER COMFORT NETWORK INSTANCE JUMPER RED LED STATUS MAIN BASE BOARD PART NUMBER GREEN LED LEN LOCAL EQUIPTMENT NETWORK Fig 8 Economizer Board Mounting Location Fig 9 Economizer Control Board Fig 10 Main Base Board ...

Page 5: ...lug marked ECB J8 16 18 to the J8 connector on the Economizer Control Board plug J8 pins 16 through 18 Connect the plug marked ECB J7 to the J7 plug on the Economizer Control Board 20 Several wires will need to be connected to the BACK SIDE of the terminal strips TB4 and TB5 The wires are marked with the appropriate locations Connect the wires as marked to the back of the TB4 terminal strip locati...

Page 6: ...then Use the arrow keys to scroll down to the Economizer High Temperature Lockout setting ECL H and press twice Use the arrow keys to increase or decrease the economizer lockout temperature and press and then Use the arrow keys to scroll down to the Economizer Low Temperature Lock out setting ECL L and press twice Use the ar row keys to increase or decrease the economizer lockout temperature and p...

Page 7: ...connections Damper is jammed Identify the obstruction and safely remove Economizer operation is limited to minimum position Minimum position is set incorrectly Adjust minimum position setting Outdoor air temperature is above economizer high temperature lockout Adjust the high temperature lockout setting if it is incorrect otherwise economizer is operating correctly Outdoor air temperature is below...

Page 8: ...any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80034 Printed in U S A Form 48 50HG 5SI Pg 8 8 01A 6 01 Replaces New Copyright 2001 Carrier Corporation Book 1 1 4 4 Tab 1a 1b 6a 6b 3 2 3 3 3 4 3 5 3 6 3 7 ...

Reviews: