35
Table 10 — Menu Structure*
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
NOTES
STATUS
ECONO AVAIL
NO
YES/NO
FIRST STAGE COOLING DEMAND (Y1–IN)
YES = economizing availa
b
le; the system can use outside air for free cooling
when re
q
uired
ECONOMIZING
NO
YES/NO
FIRST STAGE COOLING RELAY OUTPUT
YES = outside air
b
eing used for 1 stage cooling
OCCUPIED
NO
YES/NO
OCCUPIED
YES = OCC signal received from space thermostat or
unitary controller
YES = 24 Vac on terminal OCC
NO = 0 Vac on terminal OCC
HEAT PUMP
N/A**
COOL
HEAT
HEAT PUMP MODE
Displays COOL or HEAT when system is set to heat pump
(Non-conventional)
COOL Y1—IN
OFF
ON/OFF
FIRST STAGE COOLING DEMAND (Y1-IN)
Y1–I signal from space thermostat or unitary controller for cooling stage 1.
ON = 24 Vac on terminal Y1–I
OFF = 0 Vac on terminal Y1–I
COOL Y1—OUT
OFF
ON/OFF
FIRST STAGE COOLING RELAY OUTPUT
Cool stage 1 Relay Output to stage 1 mechanical cooling
(Y1–OUT terminal)
COOL Y2—IN
OFF
ON/OFF
SECOND STAGE COOLING DEMAND (Y2–IN)
Y2–I signal from space thermostat our unitary controller for second stage cool-
ing.
ON = 24 Vac on terminal Y2–I
OFF = 0 Vac on terminal Y2–I
COOL Y2—OUT
OFF
ON/OFF
SECOND STAGE COOLING RELAY OUTPUT
Cool Stage 2 Relay Output to mechanical cooling
(Y2–OUT terminal)
MA TEMP
_ _ . _ F
0 to 140 F
SUPPLY AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed air from MAT sensor.
Displays _ _ . _ F if not connected, short or out-of-range.
DA TEMP
_ _ . _ F
0 to 140 F
DISCHARGE AIR TEMPERATURE, after Heating section
Displays when Discharge Air sensor is connected and displays measured dis-
charge temperature.
Displays _ _ . _F if sensor sends invalid value, if not connected, short or out-of-
range.
OA TEMP
_ _ . _ F
-40 to 140 F
OUTSIDE AIR TEMP
Displays measured value of outdoor air temperature.
Displays _ _ . _F if sensor sends invalid value, short or
out-of-range.
OA HUM
_ _ %
0 to 100%
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from
OA sensor.
Displays _ _% if not connected short, or out-of-range.
RA TEMP
_ _ . _ F
0 to 140 F
RETURN AIR TEMPERATURE
Displays measured value of return air temperature from
RAT sensor.
Displays _ _ . _ F if sensor sends invalid value, if not connected, short or out-
of-range
RA HUM
_ _ %
0 to 100%
RETURN AIR RELATIVE HUMIDITY
Displays measured value of return air humidity from
RA sensor.
Displays _ _% if sensor sends invalid value, if not connected, short or out-of-
range
IN CO2
_ _ _ ppm
0 TO 2000 ppm
SPACE/RETURN AIR CO
2
Displays value of measured CO
2
from CO
2
sensor. Invalid if not connected,
short or out-of-range
DCV STATUS
N/A
ON/OFF
DEMAND CONTROLLED VENTILATION STATUS
Displays ON if a
b
ove setpoint and OFF if
b
elow setpoint, and ONLY if a CO
2
sensor is connected.
DAMPER OUT
2.0v
2.0 TO 10.0v
Displays voltage output to the damper actuator.
ACT POS
N/A
0 to 100%
Displays actual position of outdoor air damper actuator
Summary of Contents for 50HCQA04-06
Page 22: ...22 Fig 36 Electro Mechanical Control Wiring 208 230v 460v ...
Page 23: ...23 Fig 37 Electro Mechanical Control Wiring 575v ...
Page 24: ...24 Fig 38 Electro Mechanical Power Wiring 208 230 1 60 ...
Page 25: ...25 Fig 39 Electro Mechanical Power Wiring 208 230 3 60 ...
Page 26: ...26 Fig 40 Electro Mechanical Power Wiring 460 3 60 ...
Page 27: ...27 Fig 41 Electro Mechanical Power Wiring 575 3 60 ...
Page 28: ...28 Fig 42 PremierLink Wiring Schematic 208 230 460v ...
Page 29: ...29 Fig 43 PremierLink Wiring Schematic 575v ...