Table 10 — Menu Structure* (cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
NOTES
SYSTEM
SETUP
INSTALL
01/01/10
N/A
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG
F
F or C
Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT
CONV
Conventional or HP
CONV = conventional;
HP O/B = Ena
b
le Heat Pump mode. Use AUX2 I for Heat Pump input from
thermostat or controller.
See Menu Note 4.
AUX2 IN
W
SD/W or HP(O)/
HP(B)
In CONV mode:
SD + Ena
b
les configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for W.
Shutdown is not availa
b
le in 2-speed fan mode. See Menu Note 4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
FAN SPEED
2 speed
1 speed/2 speed
Sets the economizer controller for operation of 1 speed or 2 speed supply fan.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.
See Menu Note 4.
FAN CFM
5000cfm
100 to 15000 cfm;
increment
b
y 100
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate la
b
el for the specific unit.
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
††
• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal
OCC
INPUT
INPUT or ALWAYS
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a set
b
ack thermostat with occupancy out (24 vac), the 24 vac is
input “INPUT” to the OCC terminal. If no occupancy output from the thermostat
then change program to “ALWAYS” OR add a jumper from terminal R to OCC
terminal.
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD will
b
riefly flash
YES and change to NO
b
ut all parameters will change to the factory default
values.
NOTE: RECHECK AUX2 IN and FANTYPE for re
q
uired 2-speed values.
ADVANCED
SETUP
MA LO SET
45°F
35 to 55 F;
Incremented
b
y 10
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if tem-
perature falls
b
elow setup value).
FREEZE POS
CLO
CLO or MIN
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN POS).
CO2 ZERO
0ppm
0 to 500 ppm;
Increment
b
y 10
CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN
2000ppm
1000 to 3000 ppm;
Increment
b
y 10
CO
2
ppm span to match CO
2
sensor.
STG3 DLY
2.0h
0 min, 5 min, 15 min,
then 15 min intervals.
Up to 4 hrs or OFF
COOLING STAGE 3 DELAY
Delay after stage 2 cool has
b
een active. Turns on second stage of cooling
when economizer is first stage and mechanical cooling is second stage.
Allows three stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling
SD DMPR POS
CLO
CLO or OPN
Indicates shutdown signal from space thermostat or unitary controller. When
controller receives 24 Vac input on the SD terminal in conventional mode, the
OA damper will open if programmed for OPN and OA damper will close if pro-
grammed for CLO. All other controls, e.g., fans, etc. will shut off.
DA LO ALM
45 F (7 C)
35 to 65 F; (2 to
18 C) Incremented
b
y 5 deg.
Used for alarm for when the DA air temperature is too low. Set lower range of
alarm,
b
elow this temperature the alarm will show on the display.
DA HI ALM
80 F (27 C)
70 to 180 F; (21 to
82 C) Incremented
b
y 5 deg.
Used for alarm for when the DA air temperature is too high. Set upper range of
alarm, a
b
ove this temperature the alarm will show on the display.
DCVCAL ENA
MAN
MAN (manual) AUTO Turns on the DCV automatic control of the dampers. Resets ventilation
b
ased
on the RA, OA, and MA sensor conditions. Re
q
uires all 3 RA, OA, and MA
sensors.
Summary of Contents for 50HCQA04-06
Page 22: ...22 Fig 36 Electro Mechanical Control Wiring 208 230v 460v ...
Page 23: ...23 Fig 37 Electro Mechanical Control Wiring 575v ...
Page 24: ...24 Fig 38 Electro Mechanical Power Wiring 208 230 1 60 ...
Page 25: ...25 Fig 39 Electro Mechanical Power Wiring 208 230 3 60 ...
Page 26: ...26 Fig 40 Electro Mechanical Power Wiring 460 3 60 ...
Page 27: ...27 Fig 41 Electro Mechanical Power Wiring 575 3 60 ...
Page 28: ...28 Fig 42 PremierLink Wiring Schematic 208 230 460v ...
Page 29: ...29 Fig 43 PremierLink Wiring Schematic 575v ...