38
Table 10 — Menu Structure* (cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
NOTES
ADVANCED
SETUP (CONT)
MAT T CAL
0.0°F
±2.5 F
SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali
b
ration temperature sensor.
OAS T CAL
0.0°F
±2.5 F
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali
b
ration temperature sensor.
OA H CAL
0% RH
±10% RH
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of cali
b
ration humidity sensor.
RA T CAL
0.0°F
±2.5 F
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali
b
ration temperature sensor.
RA H CAL
0% RH
±10% RH
RETURN AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of cali
b
ration humidity sensor.
DA T CAL
0.0°F
±2.5 F
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali
b
ration temperature sensor.
2SP FAN DELAY
5 Minutes
0 to 20 minutes in 1
minute increments
TIME DELAY ON SECOND STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try to sat-
isfy the call for second stage cooling
b
efore the first stage mechanical cooling
is ena
b
led.
CHECKOUT
DAMPER MINIMUM
POSITION
N/A
N/A
The checkout for the damper minimum position is
b
ased on the system.
DAMPER OPEN
N/A
N/A
Position damper to the full open position.
Exhaust fan contacts ena
b
le during the DAMPER OPEN test. Make sure you
pause in the mode to allow exhaust contacts to energize due to the delay in
the system.
DAMPER CLOSE
N/A
N/A
Positions damper to the fully closed position
CONNECT Y1–O
N/A
N/A
Closes the Y1-O relay (Y1-O)
CONNECT Y2–O
N/A
N/A
Closes the Y2-O relay (Y2-O)
CONNECT AUX1-O
N/A
N/A
Energizes the AUX output. If Aux setting is:
• NONE — not action taken
• ERV — 24 Vac out. Turns on or signals an ERV that the conditions are not
good for economizing
b
ut are for ERV operation.
††
• SYS — 24 Vac out. Issues a system alarm
CONNECT EXH1
N/A
N/A
Closes the power exhaust fan 2 relay (EXH1)
ALARMS
Alarms display only when they are active. The menu title “ALARMS(#)” includes the num
b
er of active alarms in parenthesis ( ). When using SYLK
b
us
sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will appear on the screen
MA T SENS ERR
N/A
N/A
SUPPLY AIR TEMPERATURE SENSOR ERROR
Mixed air sensor has failed or
b
ecome disconnected - check wiring then
replace sensor if the alarm continues.
CO2 SENS ERR
N/A
N/A
CO
2
SENSOR ERROR
CO
2
sensor has failed, gone out of range or
b
ecome disconnected - check wir-
ing then replace sensor if the alarm continues.
OA SYLK T ERR
N/A
N/A
OUTSIDE AIR S-BUS SENSOR ERROR
Outdoor air enthalpy sensor has failed or
b
ecome disconnected - check wiring
then replace sensor if the alarm continues.
OA SYLK H ERR
N/A
N/A
RA SYLK T ERR
N/A
N/A
RETURN AIR S-BUS SENSOR ERROR
Return air enthalpy sensor has failed or
b
ecome disconnected - check wiring
then replace sensor if the alarm continues.
RA SYLK H ERR
N/A
N/A
DA SYLK T ERR
N/A
N/A
DISCHARGE AIR S-BUS SENSOR ERROR
Discharge air sensor has failed or
b
ecome disconnected - check wiring then
replace sensor if the alarm continues.
OA SENS T ERR
N/A
N/A
OUTSIDE AIR TEMPERATURE SENSOR ERROR
Outdoor air temperature sensor has failed or
b
ecome disconnected - check
wiring then replace if the alarm continues.
ACT ERROR
N/A
N/A
ACTUATOR ERROR
Actuator has failed or
b
ecome disconnected - check for stall, over voltage,
under voltage and actuator count. Replace actuator if damper is mova
b
le and
supply voltage is
b
etween 21.6 V and 26.4 V. Check actuator count on STA-
TUS menu.
FREEZE ALARM
N/A
N/A
Check if outdoor temperature is
b
elow the LOW Temp Lockout on setpoint
menu. Check if Mixed air temperature on STATUS menu is
b
elow the Lo Set-
point on Advanced menu. When conditions are
b
ack in normal range then the
alarm will go away.
Summary of Contents for 50HCQA04-06
Page 22: ...22 Fig 36 Electro Mechanical Control Wiring 208 230v 460v ...
Page 23: ...23 Fig 37 Electro Mechanical Control Wiring 575v ...
Page 24: ...24 Fig 38 Electro Mechanical Power Wiring 208 230 1 60 ...
Page 25: ...25 Fig 39 Electro Mechanical Power Wiring 208 230 3 60 ...
Page 26: ...26 Fig 40 Electro Mechanical Power Wiring 460 3 60 ...
Page 27: ...27 Fig 41 Electro Mechanical Power Wiring 575 3 60 ...
Page 28: ...28 Fig 42 PremierLink Wiring Schematic 208 230 460v ...
Page 29: ...29 Fig 43 PremierLink Wiring Schematic 575v ...