background image

2. Weatherstripping has been added on operable windows and

doors, and/or

3. Caulking or sealants are applied to areas such as joints around

window and door frames; between sole plates and floors;
between wall-ceiling joints; between wall panels; at penetra-
tions for plumbing, electrical, and fuel lines; and at other
openings.

If combustion and ventilation air must be supplied to an uncon-
fined space from outside, an opening with a FREE AREA of not
less than 1 sq in. per 1000 Btuh of total input of all appliances
within unconfined space (but not less than 100 sq in.) must be
provided. This opening must be located such that it can not be
blocked at any time.

When furnace is installed in a closet or enclosure, 2 ventilation
openings, with OPEN AREA as dimensioned in example below
are required for combustion air. The openings should be located
about 6 in. from top and bottom of enclosure at front of furnace.

For a confined space, where air is taken from an interior space, 2
permanent openings of equal area are required. One opening must
be within 12 in. of ceiling and the other within 12 in. of floor. Each
opening must have a free area of at least 1 sq in. per 1000 Btuh of
total input rating but not less than 100 sq in.

If outside air is supplied to a confined space, then the 2 openings
must be equal and located as above. The free area of each must be:

1. One sq in. per 4000 Btuh of total input rating when air is

directly communicated from outdoors.

2. One sq in. per 4000 Btuh of total input rating when air is

brought in through vertical ducts.

3. One sq in. per 2000 Btuh of total input rating when air is

transferred through horizontal ducts.

When ducts are used to supply air, they must be of the same cross
sectional area as free area of openings to which they connect.

The minimum dimension of rectangular air ducts must not be less
than 3 in.

In calculating free area, consideration shall be given to blocking
effect of louvers, grilles, or screens protecting openings. Screens
used shall not be smaller than 1/4-in. mesh and shall be readily
accessible for cleaning. If free area through a design of louver or
grille is known, it shall be used in calculating size design and free
area specified. If design and free area are not known, it may be
assumed that wood louvers have 20 percent free area and metal
louvers and grilles have 60 percent free area. Louvers shall be
fixed in open position or interlocked with furnace so they open
automatically at furnace start-up and remain open during furnace
operation.

Do not block combustion-air openings in the furnace. Any
blockage will result in improper combustion which may result
in a fire hazard and/or cause bodily harm.

The lack of a proper amount of combustion air can lead to serious
furnace operational problems. Some of these problems are:

1. Excessive oil burner after drip and oil fumes.

2. Sooting.

3. Melted oil burner couplings and/or ignitor/relay control.

4. A condition where air band or air shutter settings must be

more open than normal to achieve proper combustion.

5. Lockouts on start-up.

Step 2—Duct Work Recommendations

The proper sizing of warm air ducts is necessary to ensure
satisfactory furnace operation. Duct work should be in accordance
with the latest editions of NFPA-90A (Installation of Air Condi-
tioning and Ventilating Systems) and NFPA-90B (Warm Air
Heating and Air Conditioning Systems) or Canadian equivalent.

The supply duct work should be attached to flanged opening
provided at discharge end of furnace. See Fig. 5 for dimensions of
this opening.

The following recommendations should be followed when install-
ing duct work:

1. Install locking-type dampers in all branches of individual

ducts to balance out system. Dampers should be adjusted to
impose proper static at outlet of furnace.

2. A flexible duct connector of noncombustible material should

be installed at unit on both supply- and return-air systems. In
applications where extremely quiet operation is necessary, the
first 10 ft (if possible) of supply and return ducts should be
internally lined with acoustical material.

3. In cases where return-air grille is located close to fan inlet,

there should be at least one 90° air turn between fan inlet and
grille. Further reduction in sound level can be accomplished
by installing acoustical air turning vanes or lining duct as
described in item 2 above.

4. When a single air grille is used, duct between grille and

furnace must be the same size as return opening in furnace.

Return-air grilles and warm air registers MUST not be
obstructed.

When supply ducts carry air circulated by furnace to areas
outside spaces containing furnace, return air MUST also be
handled by a duct sealed to furnace casing and terminating
outside space containing furnace. Incorrect duct work termi-
nation and sealing will create a hazardous condition which
could lead to bodily harm.

When installing furnace with cooling equipment for year-round
operation, the following recommendations must be followed for
series or parallel airflow:

1. In series airflow applications, coil is mounted after furnace in

an enclosure in supply-air stream. The furnace blower is used
for both heating and cooling airflow.

The coil MUST be installed on air discharge side of furnace.
Under no circumstances should airflow be such that cooled,
conditioned air can pass over furnace heat exchanger. This
will cause condensation in heat exchanger and possible
failure of heat exchanger which could lead to a fire hazard
and/or a hazardous condition which may lead to bodily harm.
Heat exchanger failure due to improper installation may not
be covered by warranty.

For Example:

UNIT

SIZE

LENGTH

(IN.)

HEIGHT

(IN.)

105-12

18

9

125-16

20

10

155-20

20

10

3

Summary of Contents for 58BLA

Page 1: ... BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT For use with grade 2 Fuel Oil maximum Do not use Gasoline Crankcase Oil or any Oil containing Gasoline Failure to follow this warning could lead to sooting fire explosion and or severe bodily harm Never burn garbage or paper in the heating system and never leave rags paper or any fl...

Page 2: ...i nation would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetra chloride cleaning solvents hydrochloric acid water soften ing chemicals and similar chemicals Failure to follow this warning will lead to premature rusting of heat exchanger and possible premature furnace failure and or vent failure which could result in fire hazard and or bodily harm This ...

Page 3: ...urnace operational problems Some of these problems are 1 Excessive oil burner after drip and oil fumes 2 Sooting 3 Melted oil burner couplings and or ignitor relay control 4 A condition where air band or air shutter settings must be more open than normal to achieve proper combustion 5 Lockouts on start up Step 2 Duct Work Recommendations The proper sizing of warm air ducts is necessary to ensure s...

Page 4: ...Never reduce pipe size below minimum certified furnace pipe size as shown in Table 2 4 All pipe should be supported using proper clamps and or straps These supports should be at least every 4 ft 5 All horizontal runs of pipe should have at least 1 4 in per ft of upward slope 6 All runs of pipe should be as short as possible with as few turns as possible 7 Seams should be tightly joined and checked...

Page 5: ...en valve on oil supply line 3 Reset primary control 4 Set thermostat above room temperature 5 Set main electrical switch to ON position Burner should start DO NOT TAMPER WITH UNIT OR CONTROLS CALL YOUR SERVICE TECHNICIAN Step 2 Recommended Installation Practices and Combustion Check In order to obtain optimum performance from oil burner the following setup procedures must be followed 1 A test kit ...

Page 6: ... to be changed to obtain necessary cooling airflow Step 6 Heating The blower speed is factory set to deliver required airflow at normal duct static pressure Step 7 Cooling The blower speed may be field adjusted to deliver required airflow for cooling application See Table 5 Step 8 Constant Blower Switch This furnace is equipped with a constant low speed blower option Whenever room thermostat is no...

Page 7: ...cal supplies upstream of furnace If furnace has been in operation some surfaces may be hot Allow time for unit to cool down 2 Disconnect flue pipe 3 For access to cleanout ports remove blower door and filter The 2 cleanout ports are located in blower compartment They protrude through the partition and are located on the left and right of flue pipe See Fig 2 4 Unscrew wing clamp nuts and remove cle...

Page 8: ...r observa tion door limit wiring and oil burner 21 Replace collector box on secondary tube flange ensuring proper placement of gasket Tighten screws to 35 45 lb in of torque 22 Replace top partition inside collar on flue pipe top rear panel outside flue collar and blower door 23 Reconnect flue pipe and oil line s 24 Readjust burner for proper operation Check limit operation as outlined in Limit Co...

Page 9: ...STATIC PRESSURE IN WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 105 12 High 1795 1735 1675 1605 1550 1485 1425 1350 1275 1220 Medium 1365 1335 1305 1275 1255 1215 1155 1105 1050 985 Low 995 965 945 925 900 870 825 775 725 670 125 16 High 1905 1845 1770 1695 1630 1565 1490 1425 1325 1220 Medium 1750 1675 1620 1560 1500 1440 1370 1305 1235 1130 Low 1390 1350 1305 1260 1220 1180 1120 1060 985 880 155 2...

Page 10: ...Fig 6 Barometric Damper Locations A95117 FIG A FIG G FIG D FIG L FIG B FIG C FIG J FIG H FIG K POOR WRONG WRONG WRONG WRONG WRONG BAROMETRIC DAMPER LOCATIONS GOOD LOCATIONS BAD LOCATIONS 10 ...

Page 11: ... CONFORM TO N E C AND LOCAL CODES IN CANADA WIRING MUST CONFORM TO CURRENT CSA 22 1 CANADIAN ELECTRICAL CODE PART 1 AND OR LOCAL CODES 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C AND BE A MINIMUM OF 16 GA AWG COPPER STRAND WIRE USE COPPER WIRE ONLY FOR FIELD WIRING 4 CONNECT REQUI...

Page 12: ...ructions exactly a fire or explosion may result causing property damage personal injury or loss of life 1 Open all warm air registers and make sure all return air grilles are unobstructed 2 If a humidifier is installed with your system open water supply valve 3 Set thermostat to lowest setting 4 Turn on electric power to furnace 5 Open oil supply valve 6 Check all connections to ensure there are n...

Reviews: