background image

Is LED status light on?

Is LED status light b

linking r

apidly

without a pause?

Is LED status light b

linking ON/OFF slo

wly

with a combination of shor

t and long flashes?

Deter

mine status code

.  

The status code is a

2 digit n

umber with the first digit deter

mined

b

y

 the n

umber of shor

t flashes and the second

digit b

y

 the n

umber of long flashes?

Go to section belo

w f

or the status code that

w

as flashed.

Is there 115V at L1 and L2?

Is there 24V at SEC-1 and SEC-2?

Replace fur

nace control.

Chec

k f

or correct line v

oltage polar

ity

.  If

units are twinned, chec

k f

or proper lo

w-

v

oltage (24V) tr

ansf

or

mer phasing.

T

o

 recall status code br

iefly remo

v

e

 and reconnect one RED wire from the

limit s

witch or flame rollout s

witch to displa

y stored status code

.  On RED LED

control do not remo

v

e

 po

w

er or b

lo

w

er access panel bef

ore initiating status

code recall.

  

Y

ou can also recall the pre

vious status code b

y

 momentar

ily

shor

ting the 

TEST/TWIN ter

minal to Com24V ter

minal until the LED goes out.

 LED will flash the status of the pre

vious code or status code #11 (1 shor

t and

1 long flash) if there w

as no pre

vious code

.  After the control repeats the code

4 times

, the control will star

t the component test sequence

. Once initiated

the control will tur

n ON at HI HEA

T speed.

 The inducer will r

un f

or the entire

component test.

  The HSI, b

lo

w

er motor LO HEA

T speed, HI HEA

T speed, and

COOL speed will r

un f

or 10 

 15 seconds each.

  Gas v

alv

e and humidifier will

not be tur

ned on.

 When the b

lo

w

er motor is tur

ned OFF the inducer will be

s

witched to lo

w-speed f

or 10 seconds

.

W

as there a pre

vious status code other

than #11?

Is door s

witch closed?

Is there 115V going to s

witch?

Replace door s

witch.

Replace tr

ansf

or

mer

.

Does the control respond to 

W/W1, 

W2, 

Y1,

Y/Y2, and G (24V)  ther

mostat signals?

Run system through a lo

w-heat, high-heat,

or cooling cycle to chec

k oper

ation.

  Status

codes are er

ased after 72 hours

.  On RED

LED boards stored status codes can also be

er

ased whene

ver (115V or 24V) is interr

upted.

Replace fur

nace control.

Close door s

witch and go bac

k to ST

AR

T

.

Is circuit break

er closed?

Chec

k f

or contin

uity in wire from circuit

break

er to fur

nace

.

Close circuit break

er and go bac

k to ST

AR

T

.

Chec

k room ther

mostat or

interconnecting cab

le

.

Is 24V present at 

W/W1, 

W2, 

Y1, 

Y/Y2 or G

ther

mostat ter

minals on the fur

nace control?

Disconnect all the ther

mostat wires from the

fur

nace control.

Does the prob

lem repeat when using a

jumper wire?

The ther

mostat is not compatib

le with the

fur

nace control.

  Either install a ballast resistor

,

connect the Com24V ther

mostat ter

minal to

the ther

mostat, or replace the ther

mostat.

NO

YES

YES

NO

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

YES

NO

NO

NO

YES

YES

NO

NO

ST

AR

T

NO

TR

OUBLESHOO

TING GUIDE 

 TW

O-ST

A

G

E

A02189a

14

Summary of Contents for 58MTA Series

Page 1: ...g Collector Box and Drainage System 6 Servicing Hot Surface Igniter 7 Electrical Controls and Wiring 8 Checking Heat Tape Operation If Applicable 8 Winterizing 9 WIRING DIAGRAM 10 TROUBLESHOOTING 10 Status Codes 10 Component Test 11 SAFETY CONSIDERATIONS Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to t...

Page 2: ...e to the control Tools held in a person s hand during grounding will be satisfactorily discharged 3 After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity for example DO NOT move or shuffle your feet DO NOT touch ungrounded objects etc 4 If you touch ungrounded objects recharge your body with ...

Page 3: ...ectrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory authorized filte...

Page 4: ... assembly on blower shelf 12 Reinstall condensate trap and tubing if previously removed a Reinstall condensate trap in hole in blower shelf b Connect condensate trap drain tubes See Fig 8 or tubing diagram on main furnace door for proper tube location 1 Connect 1 tube blue or blue and white striped from collector box 2 Connect 1 tube violet or unmarked from inducer housing 3 Connect 1 tube relief ...

Page 5: ...rs get an accumulation of light dirt or dust on the inside they may be cleaned by the following procedure NOTE If the heat exchangers get a heavy accumulation of soot and carbon both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design A build up of soot and carbon indicates that a problem exists which needs to be co...

Page 6: ...s can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removing inducer assembly Step 5 Flushing Collector Box and Drainage System 1 Turn off gas and electrical supplies to furnace 2 Remove main furnace door 3 Disconnect inducer motor and pressure switch wires or connectors 4 Disconnect pressure switch tubes 5 Disconnect vent pipe ...

Page 7: ...e Trap on LEFT Side Optional CAP COLLECTOR BOX DRAIN TUBE BLUE PLUGGEDEND COLLECTORBOX DRAIN TUBE BLUE WHITE STRIPED COLLECTOR BOX TUBE GREEN COLLECTOR BOX TUBE PINK COLLECTOR BOX EXTENSIONTUBE CONDENSA TE TRAP INDUCERHOUSINGDRAINTUBE VIOLET COLLECTOR BOX EXTENSIONTUBE Condensate Trap on RIGHT Side PLUG CAP COLLECTOR BOX DRAIN TUBE BLUE WHITE STRIPED CONDENSA TE TRAP COLLECTOR BOX EXTENSIONTUBE CO...

Page 8: ...tion NOTE If the polarity is not correct the STATUS LED on the furnace control board will flash rapidly and prevent the furnace from operating The control system also requires an earth ground for proper operation of the furnace control board and flame sensor The 24 v circuit contains an automotive type 3 amp fuse located on the control See Fig 12 Any direct shorts of the 24 v wiring during install...

Page 9: ...GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE WHT BLK WHT BLK W W1 W2 Y Y2 G NOTES 1 Connect Y terminal as shown for proper operation 2 Some thermostats require a C terminal connection as shown 3 If any of the original wire as supplied must be replaced use same type or equivalent wire 115 V FUSE...

Page 10: ... and all blower off delays must be completed to view previous codes To retrieve previous codes remove 1 of the red main limit or flame rollout switch wires 1 to 4 sec until the LED light goes out then reconnect it Do not leave red wire disconnected for longer periods of time as the control will assume an overtemperature condition exists and will respond with blower operation This places the contro...

Page 11: ...R lead from furnace control 3 Manually close blower door switch 4 For approximately 2 sec short jumper the COM 24v terminal on control to the TEST TWIN 3 16 in quick connect terminal on control until LED turns off Remove jumper from termi nals See Fig 12 NOTE If TEST TWIN and COM 24v terminals are jumpered loner than 2 sec LED will flash rapidly and ignore status code retrieval request Component t...

Page 12: ... EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 12 CIRCUIT PCB CONNECTOR PL2 3 CIRCUIT PCB HSI IDM CONNECTOR PL3 6 CIRCUIT ICM MOTOR CONNECTOR NOT SHOWN PL4 4 CIRCUIT IDM CONNECTOR PL5 2 CIRCUIT HSI...

Page 13: ...ITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry If opens during blower on delay period blower will come on for the selected blower off delay Check for Excessive wind Restricted vent Defective inducer motor Low inlet gas pressure if LGPS used Defective pressure switch Low inducer voltage 115 VAC Inadequate combustion air supply Proper ve...

Page 14: ...ducer will run for the entire component test The HSI blower motor LO HEAT speed HI HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on When the blower motor is turned OFF the inducer will be switched to low speed for 10 seconds Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch ...

Page 15: ...ION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow w...

Page 16: ...31 58mta4sm Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 80098 Printed in U S A Form 58MTA 4SM Pg 16 11 02 Replaces 58MTA 3SM ...

Reviews: