HIGH HEAT TEMPERATURE RISE TOO LOW — Generally, this indicates the HI solenoid in gas valve GV has failed or the furnace is
extremely underfired.
STEP
ACTION
YES
NO
GO TO
1
Remove the blower access panel. Make sure the thermo-
stat is NOT calling for heat. If setup switch SW1-2 is ON
then set it to OFF.
2
2
Depress the door switch. Use piece of tape to hold it
closed.
3
3
Set thermostat to call for heat or jumper R and W/W1 ther-
mostat terminals.
4
4
When the furnace is running in low heat, clock the low heat
gas rate. You have 16 minutes on this first call for heat be-
fore unit switches to high heat. On propane installations
check the manifold pressure.
5
5
When the furnace is running in high heat, clock the high
heat gas rate. On propane installations check the manifold
pressure.
6
6
Is the high heat rate approximately the same as the low
heat rate?
7
11
7
Do you have 24 vac across gas valve terminals HI and
C
OM
-24V on 2-stage gas valve during high heat?
10
8
8
You have an open wire or bad terminal on the BROWN
wire from the high heat pressure switch HPS to the gas
valve GV. Repair it or replace the harness.
9
9
Go to the page number indicated in Index for the CLEANUP
AND STARTUP INSTRUCTIONS.
INDEX
10
Replace the gas valve.
9
11
Is the high heat rate within 2of that specified on the rating
plate?
13
12
12
Ensure the gas inlet pressure and burner orifice are correct.
Then adjust the gas valve to the proper rate. If it cannot be
adjusted to the proper rate, replace the gas valve.
9
Table 2—Cooling Tonnage vs. Airflow (CFM)
AIR CONDITIONING TONS
(12,000 BTU/HR)
AIRFLOW
(CFM)
040, 060, AND 3T-080 MODEL
5T-080 AND 100 MODEL
120 MODEL
1-1/2
525
X
2
700
X
X
X
2-1/2
875
X
X
X
3
1050
X
X
X
3-1/2
1225
X
X
X
4
1400
X
X
5
1750
X
X
6
2100
X
Table 2a—A/C or CF Airflow Selection Chart
A02277
A/C OR CF AIRFLOW SELECTION CHART
BASED ON 350 CFM/TON
MODEL
SIZE
040,060, 3T-080
5T-080, 100
120
DEF.
525
2
700
875
1050
1
1225
1225
1225
DEF.
700
2
875
1050
1225
1400 1750
1
1750
DEF.
700
875
2
1050
1225
1400 1750
1
2100
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
13