58SP0A/58SP1A: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
40
a.
Single-Speed Cooling
-
The thermostat closes the R-to-G-and-Y circuits. The R-to- Y
circuit starts the outdoor unit, and the R-to-G-and-Y/Y2 circuits
start the furnace blower motor BLWM on cooling airflow.
Cooling airflow is based on the A/C selection (shown in
).
The electronic air cleaner terminal EAC-1 is energized with 115
vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y circuits are
opened. The outdoor unit will stop, and the furnace blower motor
BLWM will continue operating at cooling airflow for an
additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the
cooling off-delay to 5 seconds, see
.
b.
Single-Stage Thermostat and Two-Speed Cooling (Adaptive
Mode)
-
This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU
includes a programmed adaptive sequence of controlled
operation, which selects low-cooling or high-cooling operation.
This selection is based upon the stored history of the length of
previous cooling period of the single-stage thermostat.
NOTE:
The air conditioning relay disable jumper ACRDJ must be
connected to enable the adaptive cooling mode in response to a call for
cooling, see
. When ACRDJ is in place the furnace control CPU
can turn on the air conditioning relay ACR to energize the Y/Y2 terminal
and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either low- or
high-cooling. If starting up in low-cooling, the furnace control CPU
determines the low-cooling on-time (from 0 to 20 minutes) which is
permitted before switching to high-cooling. If the power is interrupted,
the stored history is erased and the furnace control CPU will select
low-cooling for up to 20 minutes and then energize the air conditioning
relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to
high-cooling, as long as the thermostat continues to call for cooling.
Subsequent selection is based on stored history of the thermostat cycle
times.
The wall thermostat “calls for cooling”, closing the R-to-G-and-Y
circuits. The R-to-Y1 circuit starts the outdoor unit on low-cooling
speed, and the R-to-G-and-Y1 circuits starts the furnace blower motor
BLWM at low-cooling airflow which is the true on-board CF selection,
see
If the furnace control CPU switches from low-cooling to high-cooling,
the furnace control CPU will energize the air conditioning relay ACR.
When the air conditioning relay ACR is energized the R-to-Y1-and-Y2
circuits switch the outdoor unit to high-cooling speed, and the
R-to-G-and-Y1-and-Y/Y2 circuits transition the furnace blower motor
BLWM to high-cooling airflow. High-cooling airflow is based on the
A/C selection, see
.
NOTE:
When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the furnace
blower motor BLWM transitions to run at high-cooling airflow.
The electronic air cleaner terminal EAC-1 is energized with 115 vac
whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y circuit are opened.
The outdoor unit stops, and the furnace blower BLWM and electronic air
cleaner terminal EAC-1 will remain energized for an additional 90
seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5
seconds, see
.
c.
Two-Stage Thermostat and Two-Speed Cooling
See
for thermostat connections
NOTE:
The air conditioning relay disable jumper ACRDJ must be
disconnected to allow thermostat control of the outdoor unit staging, see
The thermostat closes the R-to-G-and-Y1 circuits for low-cooling or
closes the R-to-G-and-Y1-and-Y2 circuits for high-cooling. The
R-to-Y1 circuit starts the outdoor unit on low-cooling speed, and the
R-to-G-and-Y1 circuit starts the furnace blower motor BLWM at
low-cooling airflow which is the true on-board CF selection as shown in
(and also
). The R-to-Y1-and-Y2 circuits start the
outdoor unit on high-cooling speed, and the R-to- G-and-Y/Y2 circuits
start the furnace blower motor BLWM at high-cooling airflow.
High-cooling airflow is based on the A/C (air conditioning) selection,
.
The electronic air cleaner terminal EAC-1 is energized with 115 vac
whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y1 or R-to-
G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, and the
furnace blower BLWM and electronic air cleaner terminal EAC-1 will
remain energized for an additional 90 seconds. Jumper Y1 to DHUM to
reduce the cooling off-delay to 5 seconds, see
.
3.
Thermidistat Mode
The dehumidification output, DHUM on the thermostat should be
connected to the furnace control thermostat terminal DHUM. When
there is a dehumidify demand, the DHUM input is activated, which
means 24 vac signal is removed from the DHUM input terminal. In
other words, the DHUM input logic is reversed. The DHUM input
is turned ON when no dehumidify demand exists. Once 24 vac is
detected by the furnace control on the DHUM input, the furnace
control operates in Thermidistat mode. If the DHUM input is low
for more than 48 hours, the furnace control reverts back to
non-Thermidistat.
The cooling operation described in item 3. above also applies to
operation with a thermostat with humidity control. The exceptions
are listed below:
a.
Low cooling
-When the R-to-G-and-Y1 circuit is closed and
there is a demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 90 percent of low-cooling
airflow which is the true on-board CF selection as shown in
and
b.
High cooling
-When the R-to-G-and Y/Y2 circuit is closed and
there is a demand for dehumidification, the furnace blower motor
BLWM will drop the blower airflow to 90 percent of
high-cooling airflow. High-cooling airflow is based on the A/C
(air conditioning) selection shown in
c.
Cooling off-delay
-When the “call for cooling” is satisfied and
there is a demand for dehumidification, the cooling blower-off
delay is decreased from 90 seconds to 5 seconds.
4.
Continuous Blower Mode
When the R-to-G circuit is closed by the thermostat, the blower
motor BLWM will operate at continuous blower airflow.
Continuous blower airflow selection is initially based on the CF
Factory default is shown in
. Terminal EAC-1 is energized as long as the blower motor
BLWM is energized.
During a call for heat, the furnace control CPU will transition the blower
motor BLWM to continuous blower airflow or heat airflow whichever is
lowest. The blower motor BLWM will remain ON until the main burners
ignite then shut OFF and remain OFF for the blower-ON delay (25
seconds in heat), allowing the furnace heat exchangers to heat up more
quickly, then restarts at the end of the blower-ON delay period at heat.