ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will pre-
vent electrostatic discharges from personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electrostatic discharge
by putting the furnace, the control, and the person at the same
electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CON-
TROL PRIOR TO DISCHARGING YOUR BODY’S ELEC-
TROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s
hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc.).
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touching
control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control
or yourself into contact with the furnace. Put all used AND
new controls into containers before touching ungrounded
objects.
7. An ESD service kit (available from commercial sources) may
also be used to prevent ESD damage.
LOCATION
Step 1—General
Do not use this furnace during construction when adhesives,
sealers, and/or new carpets are being installed and curing. If
the furnace is required during construction, use clean outside
air for combustion and ventilation. Compounds of chlorine
and fluorine, when burned in combustion air, form acids
which will cause corrosion of the heat exchangers and metal
vent system. Some of these compounds are released from
paneling and dry wall adhesives, paints, thinners, masonry
cleaning materials, and many other solvents commonly used
in the construction process. Excessive exposure to contami-
nated combustion air will result in safety and performance
related problems.
Do not install furnace in a corrosive or contaminated atmo-
sphere. Make sure all combustion and circulating air require-
ments are met in addition to all local codes and ordinances.
This furnace must be installed so the electrical components are
protected from water.
Locate furnace as near the center of the air distribution system and
chimney or vent as possible. The furnace should be installed as
level as possible. When a furnace is installed so that supply ducts
carry air to areas outside the space containing the furnace, return
air must also be handled by a duct(s) sealed to the furnace casing
and terminating outside the space containing the furnace.
Provide ample space for servicing and cleaning. Always comply
with the minimum fire protection clearances shown on furnace
clearance-to-combustible construction label. This furnace shall not
be installed directly on carpeting, tile, or any combustible material
other than wood flooring.
Step 2—Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchangers. When
installed parallel with a furnace, dampers or other means used to
control flow of air must prevent chilled air from entering furnace.
If dampers are manually operated, they must be equipped with
means to prevent operation of either unit unless damper is in
full-heat or full-cool position.
Step 3—Hazardous Locations
When furnace is installed in a residential garage, it must be
installed so that burners and ignition sources are located a
minimum of 18 in. above floor. The furnace must be located
or protected to avoid physical damage by vehicles. When
furnace is installed in a public garage, airplane hangar, or
other building having a hazardous atmosphere, unit must be
installed in accordance with requirements of National Fire
Protection Association, Inc. (See Fig. 4.)
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3, Air for Combustion and
Ventilation, of the NFGC or applicable provisions of the local
building codes.
Canadian installations must be in accordance with NSCNGPIC
and all authorities having jurisdiction.
Fig. 4—Installation in a Garage
A93044
18-IN. MINIMUM
TO BURNERS
4