background image

d. HUM terminal is energized with the gas valve. See

Accessories in Electrical Connections section.

e. Flame-sensing—When burner flame is sensed, the control

begins the blower on delay period and continues holding
the gas valve open. If burner flame is not sensed, the
control closes the gas valve and repeats the ignition cycle.

NOTE:

Ignition sequence will repeat 3 additional times before a

lockout occurs. Lockout automatically resets after 3 hr, or can be
manually reset by turning 115v off (not at thermostat) for 3 sec
minimum, then on again.

f. Blower on delay—Forty sec after burner flame is proven,

the blower motor is energized on heating speed. Simulta-
neously, terminals HUM and C

OM

for humidifier, and

EAC-1 and EAC-2 for EAC are energized. If jumper is on
pin 6 and pin 9, the blower on delay period is 60 sec.

g. Blower off delay—When the thermostat is satisfied, the

circuit between R and W is broken, de-energizing the gas
valve and stopping gas flow to the burners. The blower
motor, and EAC remain energized 90, 135, 180, or 225 sec
(depending on the blower off time selection). The furnace
is factory set for a 135-sec blower off delay period.

h. Post-purge—The inducer motor remains energized 5 sec

after the burners are extinguished. If jumper is on pin 6 and
pin 9, the post-purge period is 15 sec.

2. Cooling mode

When the thermostat "calls for cooling," R-G and R-Y circuits
close. The R-Y circuit starts the outdoor condensing unit and
combined R-Y and R-G circuits start the furnace blower motor
on cooling speed. The EAC-1 terminal is energized with 115v
whenever the blower is operating on cooling speed.

When the thermostat is satisfied, R-G and R-Y circuits are
broken. Furnace blower and EAC continue operating on
cooling speed for an additional 90 sec.

3. Continuous blower mode

NOTE:

EAC-1 terminal is energized with 115v whenever blower

is operating.

When the R-G circuit is made, the blower motor operates on
heating speed. During a call for heat, the blower stops,
allowing the furnace heat exchangers to heat up more quickly,
then restarts at the end of the 40-sec blower on delay period.
If jumper is on pin 6 and pin 9, the blower on delay period is
60 sec.

The blower reverts to continuous operation after the heating
cycle is completed.

When the thermostat "calls for cooling," the blower operates
on cooling speed. When the thermostat is satisfied, the blower
operates an additional 90 sec before reverting back to con-
tinuous operation on heating speed.

4. Heat pump mode

When installed with a heat pump, the furnace control auto-
matically changes the timing sequence to avoid long blower
off time during demand defrost cycles. When the W-Y or
W-Y-G thermostat inputs are received at the same time, the
control changes the blower to heating speed or starts the
blower if it was off, and begins a heating cycle. The blower
remains on until the end of the prepurge period, then shuts off
until the end of the ignition warm up and trial for ignition
periods (a total of 24 sec). The blower then comes back on at
heating speed.

When the W input signal disappears, the control begins the
normal inducer post-purge period and the blower changes to
cooling speed after a 1-sec delay. If the W-Y-G signals
disappear at the same time, the blower remains on for the
selected heating blower off delay period and the inducer goes
through its normal post-purge period. If the W-Y inputs
should disappear, leaving the G signal input, the control goes
into continuous blower and the inducer remains on for the
normal post-purge period.

Anytime the control senses false flame, the control locks out
of the heating mode. This occurs because the control cannot
sense the W input due to the false flame signal and, as a result,
sees only the Y input and goes into cooling mode blower off
delay. All other control functions remain in standard format.

NOTE:

EAC-1 terminal is energized whenever blower operates.

HUM terminal is only energized when gas valve is energized.

START-UP PROCEDURES

1. Purge gas lines—After all connections have been made, purge

the lines and check for leaks.

Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition to check
for gas leakage. Use a soap-and-water solution to check for
gas leaks. Failure to follow this warning could result in fire,
explosion, personal injury, or death.

2. Component test—The furnace control board allows all com-

ponents, except gas valve, to be run for a short period of time.

This feature helps diagnose a system problem in case of a
component failure. To initiate component test procedure, short
(jumper) the TEST 1/4-in. quick connect terminal on control
board (adjacent to diagnostic light) and the C

OM

terminal on

thermostat connection block for approximately 2 sec. (See Fig.
13.)

NOTE:

Component test feature will not operate if any thermostat

signal is present at control board.

Component test sequence is as follows.

a. Momentarily jumper TEST and C

OM

terminals until LED

goes off.

b. LED will display previous fault 4 times.

c. Inducer motor starts and continues to run for entire com-

ponent test.

d. Hot surface ignitor is energized for 15 sec, then de-

energized.

e. Blower motor operates on cooling speed for 10 sec, then

stops.

Fig. 15—EAC Terminals on Control Board

A93053

EAC2

EAC1

12

Summary of Contents for 58ZAV Series

Page 1: ...enance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel When working on ama CANADIAN GAS ASSOCIATION APPROVED R Table 1 Clearances From Combustible Materials In UNIT SIZE 050 AND 070 096 135 DOWNFLOW In Alcove or Closet Sides Single Wall Vent 1 0 Type B 1 Double Wall Vent 0 0 Back 0 0 Top 1 1 Front Single Wall Vent 6 6 Type B ...

Page 2: ...arge can affect electronic components Take precautions during furnace installation and servicing to protect the furnace electronic control Precautions will pre vent electrostatic discharges from personnel and hand tools which are held during the procedure These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace the control and the person at the sa...

Page 3: ...e NFGC This furnace is designed for a minimum continuous return air temperature of 60 F db or intermittent operation down to 55 F db such as when used with a night setback thermostat Return air temperature must not exceed a maximum of 85 F db Improper installation adjustment alteration service mainte nance or use can cause carbon monoxide poisoning explo sion fire electrical shock or other conditi...

Page 4: ...s or spaces freely communicating with the outdoors Combustion and ventilation openings must be sized the same as for a confined space A minimum opening with a total of at least 1 sq in per 5000 Btuh of total input rating for all equipment must be provided Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room CONFINED SPACE A confined space has ...

Page 5: ...No CD5 or CK5 or Coil Box Part No KCAKC is used 1 Determine application being installed from Table 3 2 Construct hole in floor per dimensions specified in Table 3 and Fig 4 3 Construct plenum to dimensions specified in Table 3 4 If downflow subbase KGASB is used install as shown in Fig 5 If coil assembly CD5 CK5 or Coil Box KCAKC is used install as shown in Fig 6 INSTALLATION ON A COMBUSTIBLE FLOO...

Page 6: ...lat washer 3 8 in lockwasher and 3 8 in nut Dimples are provided for hole locations See Fig 1 Since horizontal crawlspace installation is very similar to attic installation refer to Step 4 The installation of a sheet metal shield in front of louvered control panel is covered in Step 4 For a crawlspace installation this same sheet metal shield must be installed above louvered control panel Extend s...

Page 7: ...s must be installed in accordance with NSC NGPIC and all authorities having jurisdiction Refer to Table 5 for recommended gas pipe sizing Risers should be used to connect to the furnace and to the meter Fig 5 Furnace Plenum and Subbase Installed on a Combustible Floor A96285 DOWNFLOW SUBBASE SHEET METAL PLENUM FLOOR OPENING FURNACE OR COIL CASING WHEN USED COMBUSTIBLE FLOORING Fig 6 Furnace Plenum...

Page 8: ...tant to the action of propane gas An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in of the furnace A 1 8 in NPT plugged tapping accessible for test gage connection MUST be installed immediately upstream of the gas supply connection to the furnace and downstream of the manual shutoff valve Place a ground joint union between the gas control ma...

Page 9: ...NFPA 70 1996 and any local codes or ordinances that might apply For Canadian installations all electrical connections must be made in accordance with Canadian Electrical Code CSA C22 1 or authori ties having jurisdiction NOTE Proper polarity must be maintained for 115 v wiring If polarity is incorrect control board fault code indicator light will flash rapidly and furnace will not operate Table 4 ...

Page 10: ... GENERAL NOTE Proper polarity must be maintained for 115 v wiring If polarity is incorrect control board fault indicator light will flash rapidly and furnace will not operate The furnace must have a 115 v power supply properly connected and grounded Proper polarity must be maintained for correct operation Thermostat wire connections at R W C and Y must be made at the 24 v terminal block on the con...

Page 11: ...E R G C W C R G Y GND GND FIELD 24 VOLT WIRING FIELD 115 208 230 460 VOLT WIRING FACTORY 24 VOLT WIRING FACTORY 115 VOLT WIRING 208 230 OR 460 VOLT THREE PHASE 208 230 VOLT SINGLE PHASE WHT BLK WHT BLK NOTES Connect Y terminal as shown for proper operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be replaced use same type or equivalent ...

Page 12: ...ol auto matically changes the timing sequence to avoid long blower off time during demand defrost cycles When the W Y or W Y G thermostat inputs are received at the same time the control changes the blower to heating speed or starts the blower if it was off and begins a heating cycle The blower remains on until the end of the prepurge period then shuts off until the end of the ignition warm up and...

Page 13: ... WIRING 24VAC FIELD WIRING 115VAC FIELD WIRING 24VAC CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 NEUTRAL L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 8 COM HSIR EAC 1 START OL COM HI MED HI MED LO LO BLWM SCHEMATIC DIAGRAM NATURAL GAS PROPANE EAC 2 1 1 HSI 2 PL5 2 PL2 3 PL3 PR2 115VAC PR1 TR...

Page 14: ...is can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures NOTE If orifice hole appears damaged or it is suspected to have been redrilled check orifice hole with a numbered drill bit of correct size Never redrill an orifice A burr free and squarely aligned orifice hole is essential for proper flame characteristics 3 After correct manifold pressure is o...

Page 15: ... 3 1 43 3 2 to 1000 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 4500 1025 43 2 6 43 2 6 43 2 7 43 2 8 43 2 9 ALTITUDE RANGE FT AVG GAS HEAT VALUE AT ALTITUDE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 0 66 Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure U S A Only 750 42 3 4 42 3 6 42 3 7 42 ...

Page 16: ... 7 43 2 8 7000 825 43 2 3 43 2 4 43 2 5 43 2 5 43 2 6 850 43 2 2 43 2 2 43 2 3 43 2 4 43 2 5 875 43 2 0 43 2 1 43 2 2 43 2 3 43 2 3 ALTITUDE RANGE FT AVG GAS HEAT VALUE AT ALTITUDE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 0 66 Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure U S A O...

Page 17: ... 22 500 Btuh Deduct 0 1 in wc from manifold pressure shown in table Change orifice size if manifold pressure falls below 3 2 in wc on altitudes up to 2000 ft otherwise change orifice size if manifold pressure falls below 2 0 in wc Table 9 Gas Rate Cu Ft Hr SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1 cu ft 2 cu ft 5 cu ft 1 cu ft 2 cu ft 5 cu ft 10 11 12 ...

Page 18: ...circulating air blower motor if the furnace overheats The preferred method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes As soon as the limit has shut off the burners the return air opening should be unblocked By using this method to check the limit control it can be established that the limit is funct...

Page 19: ...oor k Turn on 115 v power to furnace CHECKLIST 1 Put away tools instruments and clean up debris 2 Verify manual reset switches have continuity 3 Ensure blower and control access doors are properly installed 4 Cycle test furnace with room thermostat 5 Check operation of accessories per manufacturer s instruc tions 6 Review User s Manual with owner 7 Leave literature packet near furnace A94328 SERVI...

Page 20: ...6231 58zav9si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 860 Printed in U S A Form 58ZAV 9SI Pg 20 1 97 Replaces 58ZAV 8SI ...

Reviews: