59CU5A: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
A200065
Fig. 16 – Upflow - Offset of Condensate Drain
A200119
Fig. 17 – Upflow Right Side Return Configuration - Trap
Interference
A200120
Fig. 18 – Upflow Right Side Return Configuration - Required
Upflow Offset Installation
A200077
Fig. 19 – Example of Tube Connection
Upflow Specific Steps – Standard Installation
1. Install trap adapter to the collector box using provided machine
.
2. Screw the adapter plate to the trap adapter using provided machine
screw, see
Fig. 15
.
3. Screw the adapter plate to the side of casing using six (6) of the
provided sheet metal screws, see
Fig. 15
. Drilling pilot holes is
recommended to better align the plate with the knockout opening.
4. Screw the trap to the adapter plate using provided machine screw,
see
Fig. 15
.
5. Remove factory-installed collector box cap. Run tube from port on
upper left of the collector box to the relief port on the trap adapter,
see
. If the tube is too long, cut any extra length from the
tube.
Upflow Specific Steps – Offset Installation
1. Trap Offset Adapter Accessory Kit (purchased separately) is
required. Instead of installing the trap to the adapter plate, screw
the trap offset adapter to the adapter plate, see
.
2. Screw the trap to the trap offset adapter, see
.
3. Screw the trap adapter plate to the casing using the supplied sheet
metal screw, see
4. Remove factory-installed collector box cap. Run tube from port on
upper left of the collector box to the relief port on the trap adapter,
see Fig 19. If the tube is too long, cut any extra length from the
tube.
Horizontal Specific Steps
1. Accessory Horizontal Installation Kit (trap grommet) is required for
all direct-vent horizontal installations (only). The kit contains a
rubber casing grommet designed to seal between the furnace casing
and the condensate trap, see
A200067
Fig. 20 – Horizontal Right - Trap Assembly Aid
NOTICE
!
Upflow installations utilizing the right side air return opening
should follow the Upflow Specific Steps - Offset Installation
to ensure the full opening is available for return ductwork.